(1) IPC, Section 602.3, is deleted and replaced with the following: "602.3 Individual water supply. Where a potable public water supply is not available, individual sources of potable water supply shall be utilized provided that the source has been developed in accordance with Utah Code, Sections 73-3-1, 73-3-3, and 73-3-25, as administered by the Department of Natural Resources, Division of Water Rights. In addition, the quality of the water shall be approved by the local health department having jurisdiction. The source shall supply sufficient quantity of water to comply with the requirements of this chapter."
(2) IPC, Sections 602.3.1, 602.3.2, 602.3.3, 602.3.4, 602.3.5, and 602.3.5.1, are deleted.
(3) A new IPC, Section 604.4.1, is added as follows: "604.4.1 Manually operated metering faucets. Self closing or manually operated metering faucets shall provide a flow of water for at least 15 seconds without the need to reactivate the faucet."
(4) IPC, Section 606.5, is deleted and replaced with the following: "606.5 Water pressure booster systems. Water pressure booster systems shall be provided as required by Section 606.5.1 through 606.5.11."
(5) A new IPC, Section 606.5.11, is added as follows: "606.5.11 Prohibited installation. In no case shall a booster pump be allowed that will lower the pressure in the public main to less than the minimum water pressure specified in Utah Administrative Code R309-105-9."
(6) In IPC, Section 608.1, the words "and pollution" are added after the word "contamination."
(7) IPC, Table 608.1, is deleted and replaced with the following:"TABLE 608.1Application of Back Flow PreventersDEVICEDEGREE OF HAZARDaAPPLICATIONbAPPLICABLE STANDARDSBACKFLOW PREVENTION ASSEMBLIES:Double check backflow prevention assembly and double check fire protection backflow prevention assemblyLow hazardBackpressure or backsiphonage Sizes 3/8" - 16"ASSE 1015, AWWA C510, CSA B64.5, CSA B64.5.1Double check detector fire protection backflow prevention assembliesLow hazardBackpressure or backsiphonage Sizes 3/8" - 16"ASSE 1048Pressure vacuum breaker assemblyHigh or low hazardBacksiphonage only Sizes 1/2" - 2"ASSE 1020, CSA B64.1.2Reduced pressure principle backflow prevention assembly and reduced pressure principle fire protection backflow assemblyHigh or low hazardBackpressure or backsiphonage Sizes 3/8" - 16"ASSE 1013, AWWA C511, CSA B64.4, CSA B64.4.1Reduced pressure detector fire protection backflow prevention assembliesHigh or low hazardBackpressure or backsiphonage (Fire Sprinkler Systems)ASSE 1047Spill-resistant vacuum breaker assemblyHigh or low hazardBacksiphonage only Sizes 1/2" - 2"ASSE 1056BACKFLOW PREVENTER PLUMBING DEVICES:Antisiphon-type fill valves for gravity water closet flush tanksHigh hazardBacksiphonage onlyASSE 1002, CSA B125.3Backflow preventer for carbonated beverage machinesLow hazardBackpressure or backsiphonage Sizes 1/4" - 3/8" ASSE 1022Backflow preventer with intermediate atmospheric ventsLow hazardBackpressure or backsiphonage Sizes 1/4" - 3/8"ASSE 1012, CSA B64.3Dual check valve type backflow preventersLow hazardBackpressure or backsiphonage Sizes 1/4" - 1"ASSE 1024, CSA B64.6Hose connection backflow preventerHigh or low hazardBacksiphonage only Sizes 1/2" - 1"ASSE 1052, CSA B64.2, B64.2.1Hose connection vacuum breakerHigh or low hazardBacksiphonage only Sizes 1/2", 3/4", 1"ASSE 1011, CAN/CSA B64.1.1Atmospheric type vacuum breakerHigh or low hazardBacksiphonage only Sizes 1/2" - 4"ASSE 1001, CSA B64.1.1Vacuum breaker wall hydrants, frost resistant, automatic draining typeHigh or low hazardBacksiphonage only Sizes 3/4", 1"ASSE 1019, CSA B64.2.2OTHER MEANS or METHODS:Air gapHigh or low hazardBacksiphonage onlyASME A112.1.2Air gap fittings for use with plumbing fixtures, appliances and appurtenancesHigh or low hazardBackpressure or backsiphonageASME A112.1.3For SI: 1 inch = 25.4 mma. Low Hazard - See Pollution (Section 202), High Hazard - See Contamination (Section 202)b. See Backpressure (Section 202), See Backpressure, low head (Section 202), See Backsiphonage (Section 202)Installation Guidelines: The above specialty devices shall be installed in accordance with their listing and the manufacturer's instructions and the specific provisions of this chapter."
(8) In IPC, Section 608.3, the word "and" after the word "contamination" is deleted and replaced with a comma and the words "and pollution" are added after the word "contamination" in the first sentence.
(9) In IPC, Section 608.5, the words "with the potential to create a condition of either contamination or pollution or" are added after the word "substances".
(10) In IPC, Section 608.6, the following sentence is added at the end of the paragraph: "Any connection between potable water piping and sewer-connected waste shall be protected by an air gap in accordance with Section 608.13.1."
(11) IPC, Section 608.7, is deleted and replaced with the following: "608.7 Stop and Waste Valves installed below grade. Combination stop-and-waste valves shall be permitted to be installed underground or below grade. Freeze proof yard hydrants that drain the riser into the ground are considered to be stop-and-waste valves and shall be permitted."
(12) In IPC, Section 608.11, the following sentence is added at the end of the paragraph: "The coating and installation shall conform to NSF Standard 61 and application of the coating shall comply with the manufacturers instructions."
(13) IPC, Section 608.13.3, is deleted and replaced with the following: "608.13.3 Backflow preventer with intermediate atmospheric vent. Backflow preventers with intermediate atmospheric vents shall conform to ASSE 1012 or CSA CAN/CSA-B64.3. These devices shall be permitted to be installed on residential boilers only, without chemical treatment, where subject to continuous pressure conditions. The relief opening shall discharge by air gap and shall be prevented from being submerged."
(14) IPC, Section 608.13.4, is deleted.
(15) IPC, Section 608.13.9, is deleted and replaced with the following: "608.13.9 Chemical dispenser backflow devices. Backflow devices for chemical dispensers shall comply with Section 608.16.7."
(16) IPC, Section 608.15.3, is deleted and replaced with the following: "608.15.3 Protection by a backflow preventer with intermediate atmospheric vent. Connections to residential boilers only, without chemical treatment, shall be protected by a backflow preventer with an intermediate atmospheric vent."
(17) IPC, Section 608.15.4, is deleted and replaced with the following: "608.15.4 Protection by a vacuum breaker. Openings and outlets shall be protected by atmospheric-type or pressure-type vacuum breakers. Vacuum breakers shall not be installed under exhaust hoods or similar locations that will contain toxic fumes or vapors. Fill valves shall be set in accordance with Section 425.3.1. Atmospheric Vacuum Breakers - The critical level of the atmospheric vacuum breaker shall be set a minimum of 6 inches (152 mm) above the flood level rim of the fixture or device. Pipe-applied vacuum breakers shall be installed not less than 6 inches (152 mm) above the flood level rim of the fixture, receptor, or device served. No valves shall be installed downstream of the atmospheric vacuum breaker. Pressure Vacuum Breaker - The critical level of the pressure vacuum breaker shall be set a minimum of 12 inches (304 mm) above the flood level of the fixture or device."
(18) In IPC, Section 608.15.4.2, the following is added after the first sentence: "Add-on-backflow prevention devices shall be non-removable. In climates where freezing temperatures occur, a listed self-draining frost proof hose bibb with an integral backflow preventer shall be used."
(19) In IPC, Section 608.16.2, is deleted and replaced as follows: "608.16.2 Connections to boilers. The potable supply to a boiler shall be protected by an air gap or a reduced pressure principle backflow preventer, complying with ASSE 1013, CSA B64.4 or AWWA C511. Exception: The potable supply to a residential boiler without chemical treatment may be equipped with a backflow preventer with an intermediate atmospheric vent complying with ASSE 1012 or CSA CAN/CSA-B64.3."
(20) IPC, Section 608.16.3, is deleted and replaced with the following: "608.16.3 Heat exchangers. Heat exchangers shall be separated from potable water by double-wall construction. An air gap open to the atmosphere shall be provided between the two walls. Exceptions: 1. Single wall heat exchangers shall be permitted when all of the following conditions are met: a. It utilizes a heat transfer medium of potable water or contains only substances which are recognized as safe by the United States Food and Drug Administration (FDA); b. The pressure of the heat transfer medium is maintained less than the normal minimum operating pressure of the potable water system; and c. The equipment is permanently labeled to indicate only additives recognized as safe by the FDA shall be used. 2. Steam systems that comply with paragraph 1 above. 3. Approved listed electrical drinking water coolers."
(21) In IPC, Section 608.16.4.1, a new exception is added as follows: "Exception: All class 1 and 2 systems containing chemical additives consisting of strictly glycerine (C.P. or U.S.P. 96.5 percent grade) or propylene glycol shall be protected against backflow with a double check valve assembly. Such systems shall include written certification of the chemical additives at the time of original installation and service or maintenance."
(22) IPC, Section 608.16.7, is deleted and replaced with the following: "608.16.7 Chemical dispensers. Where chemical dispensers connect to the water distribution system, the water supply system shall be protected against backflow in accordance with Section 608.13.1, Section 608.13.2, Section 608.13.5, Section 608.13.6 or Section 608.13.8. Chemical dispensers shall connect to a separate dedicated water supply separate from any sink faucet."
(23) IPC, Section 608.16.8, is deleted and replaced with the following: "608.16.8 Portable cleaning equipment. Where the portable cleaning equipment connects to the water distribution system, the water supply system shall be protected against backflow in accordance with Section 608.13.1, Section 608.13.2 or Section 608.13.8."
(24) A new IPC, Section 608.16.11, is added as follows: "608.16.11 Automatic and coin operated car washes. The water supply to an automatic or coin operated car wash shall be protected in accordance with Section 608.13.1 or Section 608.13.2."
(25) IPC, Section 608.17, is deleted and replaced with the following: "608.17 Protection of individual water supplies. See Section 602.3 for requirements."