(a) The facility shall have an alternate source(s) of electrical power that provides for the simultaneous operations of life safety systems including:
- (1) emergency lighting;
- (2) illuminated emergency exit lights and signs;
- (3) emergency audible communication systems and equipment;
- (4) fire detection and alarm systems;
- (5) ventilation and smoke management systems; and
- (6) all secure door locking mechanisms which operate exclusively on electric current.
- (b) The alternate power source system shall be tested at least every 15 calendar days to ensure the system is in working condition.
- (c) The alternate power system (e.g., the alternate power source and the life safety systems required to be operated) shall be inspected at least every 365 calendar days. This inspection must be completed by a person with qualifications established through work experience, relevant training, specialized licensure or certification.
- (d) All of the aforementioned tests shall be documented to minimally include test date and test results.
- (e) Any system malfunctions or maintenance needs that are identified during a test, or at any other time, shall require that a written maintenance request be immediately submitted to the appropriate personnel.
Source Note:The provisions of this §343.224 adopted to be effective January 1, 2010, 34 TexReg 7095.