- (a) The maximum contaminant level (MCL) for total trihalomethanes shall be 0.10 milligrams/liter. The MCL shall apply only to those systems which serve a population of 10,000 or more individuals.
(b) Sampling and analytical requirements for total trihalomethanes:
- (1) For the purpose of this section, the minimum number of samples required to be taken shall be based on the number of treatment plants used by the system, except that multiple wells drawing raw water from a single aquifer shall be considered as one treatment plant for determining the minimum number of samples. All samples taken within one sampling period shall be collected within a 24-hour period.
- (2) For all community water systems utilizing surface water sources in whole or in part, and for all water systems utilizing only groundwater sources that have not been determined to qualify for the reduced monitoring requirements of paragraph (4) of this subsection, analyses for total trihalomethanes shall be performed on at least four samples of water per quarter from each treatment plant used by the system. At least 25% of the samples shall be taken at locations within the distribution system reflecting the maximum residence time of the water in the system. The remaining 75% shall be taken at representative locations in the distribution system, taking into account number of persons served, different sources of water, and different treatment methods employed. The results of all analyses per quarter shall be arithmetically averaged and reported to the commission within 30 days of the system's receipt of such results. All samples collected shall be used in computing the average, unless the analytical results are invalidated for technical reasons.
(3) Upon the written request of a community water system, the monitoring frequency required by paragraph (2) of this subsection may be reduced by the commission to a minimum of one sample analyzed for TTHM's per quarter taken at a point in the distribution system reflecting the maximum residence time of the water in the system, upon a written determination by the commission that the data from at least one year of monitoring in accordance with paragraph (2) of this subsection and local conditions demonstrate that total trihalomethane concentrations will be consistently below the maximum contaminant level.
- (A) If at any time during which the reduced monitoring frequency prescribed under this subsection applies, the results from any analysis exceed 0.10 milligrams/liter of TTHM's and such results are confirmed by at least one check sample taken promptly after such results are obtained, or if the system makes any significant change to its source of water or treatment program, the system shall immediately begin monitoring in accordance with the requirements of paragraph (2) of this subsection.
- (B) If a system is required to begin monitoring in accordance with paragraph (2) of this subsection, such monitoring shall continue for at least one year before a reduction in monitoring frequency may be considered.
(4) Upon the written request to the commission, a community water system utilizing only groundwater sources may seek to have the monitoring frequency reduced to a minimum of one sample for maximum TTHM potential per year taken at a point in the distribution system reflecting maximum residence time of the water in the system. The system shall submit to the commission the results of at least one sample analyzed for maximum TTHM potential taken at a point in the distribution system reflecting the maximum residence time of the water in the system. The system's monitoring frequency may only be reduced upon a written determination by the commission that, based upon the data submitted by the system, the system has a maximum TTHM potential of less than 0.10 milligrams/liter and that, based upon an assessment of the local conditions of the system, the system is not likely to approach or exceed the maximum contaminant level for TTHM's. The results of all analyses shall be reported to the commission within 30 days of the system's receipt of such results. All samples collected shall be used for determining whether the system must comply with the monitoring requirements of paragraph (2) of this subsection, unless the analytical results are invalidated for technical reasons.
- (A) If at any time during which the reduced monitoring frequency prescribed under this subsection is in effect, the result from any analysis taken by the system for the maximum TTHM potential is equal to or greater than 0.10 milligrams/liter, and such results are confirmed by at least one check sample taken promptly after such results are received, the system shall begin immediately to monitor in accordance with the requirements of paragraph (2) of this subsection.
- (B) If it becomes necessary to begin monitoring in accordance with paragraph (2) of this subsection, such monitoring shall continue for at least one year before the monitoring frequency may be reduced.
- (C) In the event of any significant change to the system's raw water or treatment program, the system shall immediately analyze an additional sample for maximum TTHM potential taken at a point in the distribution system reflecting the maximum residence time of the water in the system for the purpose of determining whether the system must comply with the monitoring requirement of paragraph (2) of this subsection.
- (5) Compliance with the MCL of 0.10 milligrams/liter for total trihalomethanes shall be determined based on a running annual average of quarterly samples collected by the system as prescribed in paragraph (2) of this subsection. If the average of samples covering any 12-month period exceeds the maximum contaminant level, the supplier of water shall report to the commission within 30 days and notify the public as required under §290.103(8) of this title (relating to Standards of Chemical Quality). Monitoring after public notification shall be at a frequency designated by the commission and shall continue until a monitoring schedule as a condition of a variance, exemption, or enforcement action shall become effective.
- (6) Before a community water system makes any significant modification to its existing treatment process for the purpose of achieving compliance with this subsection, the system must submit and obtain commission approval of a detailed plan setting forth its proposed modifications and those safeguards that it will implement to ensure that the bacteriological quality of the drinking water served by such system will not be adversely affected by such modifications.
- (7) All analyses for determining compliance with the provisions of this subsection shall be conducted in accordance with the procedures required by the U.S. Environmental Protection Agency.
Source Note:The provisions of this §290.116 adopted to be effective April 15, 1994, 19 TexReg 2282; amended to be effective February 4, 1999, 24 TexReg 738.