- (a) An approach channel must be unobstructed and have a minimum length of 4.0 feet before the first ultraviolet (UV) bank.
- (b) The downstream channel length must be unobstructed for a minimum length of 4.0 feet following the last bank of UV lamps and before a fluid-level control device.
- (c) Inlet channels must provide equal flow distribution across all UV channels.
- (d) A downstream discharge point of a UV system must include a level control that ensures that the UV lamps remain submerged, according to the manufacturer's recommendations, regardless of flow.
- (e) The UV system must prevent an individual's exposure to UV light from the UV system, including upstream and downstream portions of a UV channel.
- (f) An enclosed UV system must have a dehumidifier or must be designed to prevent corrosion of electrical components.
Source Note:The provisions of this §217.297 adopted to be effective August 28, 2008, 33 TexReg 6843; amended to be effective December 4, 2015, 40 TexReg 8254.