(a) Horizontal Pump Suctions.
- (1) Each pump must have a separate suction pipe that uses an eccentric reducer.
- (2) Pipes in a wet well must have a turndown type flared intake.
(b) Valves.
(1) The discharge side of each pump followed by a full-closing isolation valve must also have a check valve.
- (A) A check valve must be a swing type valve with an external lever.
- (B) A valve must include a position indicator to show its open and closed positions, unless a full-closing valve is a rising-stem gate valve.
- (2) A grinder pump installation may use a rubber-ball check valve or a swing-type check valve.
- (3) A butterfly valve, tilting-disc check valve, or any other valve using a tilting-disc in a flow pipe is prohibited.
(c) Pipes.
- (1) A lift station pipe must have flanged or flexible connections to allow for removal of pumps and valves without interruption of the lift station operations.
- (2) Wall penetrations must allow for pipe flexure while excluding exfiltration or infiltration.
- (3) Pipe suction velocities must be at least 3.0 feet per second but not more than 7.0 feet per second.
Source Note:The provisions of this §217.62 adopted to be effective August 28, 2008, 33 TexReg 6843.