- (a) At least once every two years a DPR must be completed on each registered device.
(b) To be valid, a service company must complete a DPR of a device on a single day. A DPR must include:
- (1) performance testing;
- (2) calibration, if necessary; and
(3) inspection of the device:
- (A) to ensure operation within NIST Handbook 44 specifications, tolerances and other technical requirements along with specified manufacturer guidelines; and
- (B) to detect the presence of skimmers.
- (c) A DPR report must be submitted by a service company within 10 business days of the DPR in a manner prescribed by the department.
(d) Effective date.
- (1) Beginning September 1, 2020, devices with a maximum flow rate of 20 GPM or less are subject to this section.
(2) Beginning September 1, 2021, the following devices will also be subject to this section.
- (A) Devices with a maximum flow rate of greater than 20 GPM to 100 GPM;
- (B) Devices with a maximum flow rate of greater than 100 GPM; and
- (C) LPG meters.
- (e) A supplier is exempt from this section.
Source Note:The provisions of this §97.23 adopted to be effective September 1, 2020, 45 TexReg 6082.