- (a) ICC or DOT containers for use with LP-gas shall not be installed either completely or partially buried in the ground.
- (b) Containers shall be set upon a firm masonry or rock foundation so that the bottom of the container is not in contact with the ground. Such containers shall be securely strapped to a post, or other means shall be taken to insure container against being accidentally displaced.
- (c) To guard against the effects of possible settling, containers shall be connected to house piping by means of a semiflexible connector of copper tubing or its equivalent.
Source Note:The provisions of this §9.304 adopted to be effective June 1, 1994, 19 TexReg 3151.