(a) Proper sizing of footings depends on the load carrying capacity of both the piers and the soil. To determine the load bearing capacity of the soil, the installer may use any of the following methods:
- (1) Using a pocket penetrometer;
- (2) Soil surveys from the U.S. Department of Agriculture;
- (3) Values from tables of allowable or presumptive bearing capacities given in local building codes. Such tables are commonly available from the local authority having jurisdiction; or
- (4) Any other test data from soil analysis reports.
Attached Graphic
- (b) The footing must be placed on firm, undisturbed soil, or fill compacted to at least 90% of its maximum relative density is required and must be verified every 6" - 8" vertically on the build-up. Installation on loose, noncompacted fill may result in settlement/movement of the home and may invalidate the home's limited warranty.
- (c) Footer Configurations.
Attached Graphic
- (d) Footer sizing and capacities: The Footer Capacities table in subsection (a)(4) of this section represent maximum loads and spacings based on footer size and soil bearing capacity. Other footers may be used if equal or greater in bearing area than those footer sizes tabulated.
(e) Piers and pier spacings: Spacing and location of piers shall be in accordance with the tables listed in this chapter.
- (1) Spacing shall be as even as practicable avoiding obstacles that are not in control of the installer along each main I-Beam. Pier spacing may exceed tabulated values up to 30% so long as the total pier count remains the same. End piers are to be located within 24 inches of the end of the main frame.
- (2) Piers shall extend at least 6 inches from the centerline of the I-Beam or be designed to prevent dislodgment due to horizontal movement of less than 4 inches.
- (3) Load bearing supports or devices shall be registered with the Department in accordance with §80.26 of this chapter (relating to Registration of Stabilizing Components and Systems).
- (4) Sidewall openings greater than 4 feet shall have perimeter piers located under each side of the opening, i.e. patio doors, recessed porches/entries, bay windows and porch posts. Perimeter piers for openings are not required for endwalls.
(f) Pier design: Piers shall be constructed per the details in the Pier Design.
Attached Graphic
- (1) Shimming (if needed): Shims are commonly used as a means for leveling the home and filling any voids left between the bottom flange of the I-Beam and the top of the pier cap. Wedge shaped shims must be installed from both sides of the I-Beam to provide a level bearing surface. The allowable height must not exceed 1 inch. Shims shall be a minimum of 3" x 6" nominal. All adjustment shims (marriage and perimeter) must be installed in manner which prevents dislodgement.
- (2) Table for pier spacing without perimeter piers.
Attached Graphic
- (3) Table for pier spacing WITH perimeter supports and the Perimeter Pier Front and Side View.
Attached Graphic
- (g) Typical Multi-Section Pier Layout.
Attached Graphic
- (h) Typical Single Section Pier Layout.
Attached Graphic
(i) Multi-section units mating line column supports:
- (1) On multi-section units, openings larger than 4 feet must have piers installed at each end of the opening. And within 6 inches of each end.
Attached Graphic
- (2) Column loads for each section may be combined when the columns are opposite each other. The footer must be sized for the combined loading.
- (3) Additional piers are required under marriage walls (see wall between column #3 and #4 in the Marriage Line Elevation figure in paragraph (1) of this subsection. The maximum spacing is the same as the spacing at the main I-Beams, without perimeter piers, and one half the spacing of the perimeter piers, with perimeter piers installed.
- (4) See the table for the mating line column loads.
Attached Graphic
(j) For temporary blocking at a retail location. If manufacturer has instructions for temporary blocking, home should be blocked according to the manufacturer specifications. In absence of any manufacturer instructions, the State Generic should be use. Manufactured dwellings supported on their wheels and at the draw bar (hitch) shall be adequately supported under the perimeter of each floor section at 10 feet on center and under the marriage line at each column support post locations. Marriage line support post locations will be clearly marked by the manufacturer. Piers shall not be located under any window or door opening, except under jambs for openings 4 feet or greater.
- (1) Manufactured dwellings not supported on their wheels and at the draw bar shall be adequately supported under each main frame (I-beam) and under the marriage line at each column support post location. Mainframe support post shall start not more than 5 feet from the end of the home and shall not be located under any window or door opening, except under jambs for openings 4 feet or greater.
- (2) Manufactured dwellings shall be sealed at the centerlines and at all other openings to prevent exposure to the elements.
Source Note:The provisions of this §80.23 adopted to be effective January 29, 2008, 32 TexReg 8790.