ARSD 20:10:39:32
20 : 10 : 39 : 32 . Recording the cow contact test data. The qualified testing professional conducting the cow contact test shall record the location of each test point and the values measured at each test point. At each cow contact location, an open circuit voltage reading and a voltage reading with the shunt resistor placed across the input to the meter are taken. The readings are taken with not more than ten seconds between each reading. A current measurement may be taken in place of the voltage measurement. Data for these test points are recorded on the cow contact test form on file with the commission.
Source: 42 SDR 174 , effective June 21, 2016 .
General Authority: SDCL 49 - 47 - 2.
Law Implemented: SDCL 49-47-2 , 49-47-3 .