ARSD 20:10:39:17
20 : 10 : 39 : 17 . Testing sequence. The cow contact test and the 48 hour test shall be performed in all investigations, subject to the provisions of § 20:10:39:21. The cow contact test shall be performed first. The primary profile test, the secondary neutral voltage drop test, the load box test, and the signature test may be performed in any order and may be performed without first determining if the tests are required under § 20:10:39:19. The primary profile test, the secondary neutral voltage drop test, the load box test, and the signature test may be performed before the start of recording for the 48 hour test or while the 48 hour test is in progress. The 48 hour test may be interrupted to conduct the secondary neutral voltage drop test, the load box test, and the signature test, or to review and analyze the data recorded.
Source: 42 SDR 174 , effective June 21, 2016 .
General Authority: SDCL 49 - 47 - 2.
Law Implemented: SDCL 49-47-2 , 49 - 47-3 .