450-RICR-00-00-8
A. The Fire Safety Code Board of Appeal and Review hereby adopts and incorporates as the RILSC the provisions of the National Fire Protection Association (NFPA) 101, Life Safety Code, 2021 edition, with annexes, as published by the NFPA not including any further editions or amendments thereof and only to the extent that the provisions therein are not inconsistent with R.I. Gen. Laws Chapter 23-28.01, et seq. and any provisions added, amended or reserved in this Regulation.
H. The provisions of NFPA 101, 2021 edition, as amended and referenced below, and incorporated herein as the “Rhode Island Life Safety Code”, shall be preceded by the acronym “RILSC”. All of the remaining provisions of NFPA 101, 2021 edition, adopted as the “Rhode Island Life Safety Code”, but not specifically addressed below, shall likewise be identified by the acronym “RILSC” preceding it. (Accordingly, “Chapter 1” below would be identified as “RILSC 1”. Likewise, “§ 1.1.2” below would be identified as “as RILSC 1.1.2”.)
A. For purposes of this Code, the following abbreviations have the following meanings:
Chapter 1 has been adopted with the following changes:
1.1Scope
(Amd) 1.1.1Title.
The Title of this Code shall be known as the “Rhode Island Life Safety Code,” is cited as such, and shall be referred to herein as “this Code” or “the Code.”
(Add) 1.1.1.2Relationship to other fire codes.
The “Rhode Island Life Safety Code” (NFPA 101, 2021 Edition, as amended) and the “Rhode Island Fire Code” (NFPA 1, 2021 Edition, as amended) comprise the “Rhode Island Fire Safety Code” pursuant to R.I. Gen. Laws § 23-28.1-2.
The “Rhode Island Life Safety Code” is the major component of the “Rhode Island Fire Safety Code” which includes all other statutory mandates found in R.I. Gen. Laws Chapter 23-28 along with any additional Rules and Regulations adopted, by the Fire Safety Code Board of Appeal and Review, pursuant to R.I. Gen. Laws §§ 23-28.3-3 and 23-28.1-2.
(Amd) 1.4 Equivalency.
Nothing in this Code is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety over those prescribed by this code provided that any proposed equivalent systems, methods and devices are first approved by the Fire Safety Code Board of Appeal & Review.
The State Fire Marshal is the sole authority having jurisdiction for the strict enforcement of the provisions of this Code. The State Fire Marshal shall have authority to appoint and certify as many Deputy State Fire Marshals and Assistant Deputy State Fire Marshals as are deemed necessary to strictly enforce the provisions of this Code. All such Deputy State Fire Marshals and Assistant Deputy State Fire Marshals maintain their certification at the pleasure of the State Fire Marshal. Accordingly, all Deputy State Fire Marshals and Assistant Deputy State Fire Marshals shall be allowed to enforce this code as long as they maintain their certification in the above positions by the State Fire Marshal.
The Fire Safety Code Board of Appeal & Review is the sole authority having jurisdiction for administration of this Code. Accordingly, the Fire Safety Code Board of Appeal & Review is the sole authority having jurisdiction to grant variances, waivers and amendments from, or to review and accept any proposed fire safety equivalencies and alternatives to, the strict adherence to the provisions of this Code and all referenced standards herein. For purposes of uniform administration, all exceptions listed in this Code, and its referenced standards, allowing for a discretionary waiver by the authority having jurisdiction, shall be referred directly to the Fire Safety Code Board of Appeal & Review as outlined in § 1.7.1 of this Subchapter, et seq.
(Add) 1.7
When a conflict between the language of the original 2021 Edition of NFPA 101-Life Safety Code and any specific Rhode Island amendment occurs, the conflict shall initially be resolved by the Office of the State Fire Marshal.
(Amd) 2.2
NFPA 70®, National Electrical Code®, 2023 edition, as adopted, reserved and amended by the State Building Code Standards Committee as the Rhode Island Electrical Code (SBC-5), .
NFPA 72®, National Fire Alarm and Signaling Code, 2022 edition. Any conflict or citation inconsistency with the provisions of this edition and references to the 2019 edition, shall be resolved in favor of the most stringent requirement as determined by the State Fire Marshal subject to appeal to the Fire Safety Code Board of Appeal & Review.
NFPA 855, Standard for the Installation of Stationary Energy Storage Systems, 2023 Edition. Any conflict or citation inconsistency with the provisions of this edition and references to the 2020 edition, shall be resolved in favor of the most stringent requirement as determined by the State Fire Marshal subject to appeal to the Fire Safety Code Board of Appeal & Review.
(Amd) 3.3.37.3 Apartment Building.
A building or portion thereof containing four (4) or more dwelling units with independent cooking and bathroom facilities.
(Add) 3.3.175.1
Congregate Family Living Facility: A building or part thereof that contains sleeping rooms where residents share the entire house and live, cook and function together as a single housekeeping unit.
(Add) 3.4.5 Certificate of Occupancy. After the building official inspects the building or structure and, after consultation with the AHJ enforcing the provisions of this Code, finds no violations of the provisions of this Code or other laws that are enforced by the department of building safety, the building official issues an official document known as a “certificate of occupancy” that generally contains the following:
(Add) 3.4.13 Nightclub: A place of public accommodation, which in general is characterized by all of the following:
(Add) 4.6.9.3
The Authority Having Jurisdiction (AHJ) for the enforcement of this Code may approve the issuance of a temporary certificate of occupancy (TCO) by the building official provided the major life safety systems (sprinkler, fire alarm, approved egress system, etc.) are operational in the area of the building to be so occupied. The AHJ is further authorized to require any additional safeguards he or she deems necessary to ensure the life safety of the temporary occupants.
(Add) 4.6.12.2.1 Existing fire protection systems or features, or portions thereof, shall only be removed in accordance with the following procedure:
Chapter 6 has been adopted with the following changes:
1. No dwelling unit of a residential occupancy shall have its sole means of egress pass through any nonresidential occupancy in the same building unless both of the following conditions exist:
2. Dwelling units of a residential occupancy shall be permitted to be located above a nonresidential occupancy only where one of the following conditions exists:
(Amd) 6.1.8.1.5 Definition – Apartment Building. A building or portion thereof containing four (4) or more dwelling units with independent cooking and bathroom facilities.
(Add) 6.1.14.3.2.1 The minimum separate safeguards are as follows:
(Add) 6.1.14.4.7
§ 6.1.14.4 shall not be construed as to require that any or all occupancies be separated. These Sections simply establish the separation requirements necessary if a building owner chooses to have a portion of the building not comply with the most restrictive requirements of the occupancies involved. All non-separated occupancies are mixed occupancies, as defined in § 6.1.14.2.2, and must comply with the provisions of this Code covering mixed occupancies.
Chapter 7 has been adopted with the following changes:
(Amd) 7.2.2.4.5.5 New handrails shall be installed to provide a clearance of not less than one and one half inch (1 ½”) (38 mm) between the handrail and the wall to which it is fastened.
(Add) 7.2.8.9.2 Maintenance of fire escape stairs shall include:
(Add) 7.2.8.9.3 Fire escape stairs that are not properly maintained and show signs of structural instability shall be repaired prior to continued use. All repairs shall be inspected by a person or firm acceptable to the State Fire Marshal.
(Add) 7.2.9.4Maintenance
(Add) 7.2.9.4.2 Maintenance of fire escape ladders shall include:
Chapter 9 has been adopted with the following changes:
(Amd) 9.1.3.2
New generator controllers shall be monitored by the fire alarm system, where provided, or at a location approved by the AHJ, for the following conditions:
Exception: A generator remote annunciator may be installed adjacent to the fire alarm control unit or fire alarm remote annunciator with the approval of the AHJ to satisfy this requirement.
(Add) 9.1.3.3 Where a building fire alarm system is provided, existing emergency generators shall be monitored by the fire alarm system for generator running.
Exception: A generator remote annunciator may be installed adjacent to the fire alarm control unit or fire alarm remote annunciator with the approval of the AHJ to satisfy this requirement.
(Add) 9.2.3.1 Any business that is open less than six (6) months a year shall be considered a seasonal business with low-volume cooking operations and as such, shall be exempt from the semiannual maintenance requirements of 96:12.4 and shall only be required to perform said maintenance annually prior to reopening for the season.
(Add) 9.2.5 Where a building fire alarm system is provided, it shall be interconnected to the building’s heating, ventilating and air conditioning (HVAC) line voltage controls so that any individual fan supplying two thousand (2,000) ft³/min. (cfm) (56.63 m³/min.) or greater capacity of any ventilating system not used for pressurization of a fire safe area shall automatically shut down any time, other than drills or when testing, that any initiating device connected to the fire alarm system is activated as provided in § 9.6.5.2 (6).
(Add) 9.2.5.1 The requirements of 9.2.5 may be modified or omitted in areas where automatic shutdown may interfere with clean room operations, temperature controlled environments protecting sensitive equipment, or other building operations as approved by the authority having jurisdiction.
(Amd) 9.4.2.1
Except as modified herein, new elevators, escalators, dumbwaiters, and moving walks shall be in accordance with the requirements of ASME A17.1/CSA B44, Safety Code for Elevators and Escalators and the Rhode Island Elevator Safety Code, 260-RICR-30-10-1.
(Amd) 9.4.2.2
Except as modified herein, existing elevators, escalators, dumbwaiters, and moving walks shall conform to the requirements of ASME A17.3, Safety Code for Existing Elevators and Escalators and the Rhode Island Elevator Safety Code, 260-RICR-30-10-1.
(Amd) 9.4.2.3
Elevators in accordance with ASME A17.1/CSA B44.7, Performance-Based Safety Code for Elevators and Escalators, shall be deemed to comply with ASME A17.1/CSA B44, Safety Code for Elevators and Escalators, or ASME A17.3, Safety Code for Existing Elevators and Escalators and the Rhode Island Elevator Safety Code, 260-RICR-30-10-1.
(Amd) 9.4.3.2
All existing elevators shall conform to the Fire Fighters’ Emergency Operations requirements of ASME A17.3, Safety Code for Existing Elevators and Escalators and the Rhode Island Elevator Safety Code, 260-RICR-30-10-1.
(Amd) 9.4.6.1
Elevators shall be subject to periodic inspections and tests as specified in ASME A17.1/CSA B44, Safety Code for Elevators and Escalators and the Rhode Island Elevator Safety Code, 260-RICR-30-10-1.
(Amd) 9.4.6.2
All elevators equipped with fire fighters’ emergency operations in accordance with § 9.4.3 shall be subject to a monthly operation with a written record of the findings made and kept on the premises as required by ASME A17.1/CSA B44, Safety Code for Elevators and Escalators and the Rhode Island Elevator Safety Code, 260-RICR-30-10-1.
(Amd) 9.4.6.3
The elevator inspections and tests required by § 9.4.6.1 shall be performed at frequencies complying with the Rhode Island Elevator Safety Code, 260-RICR-30-10-1.
(Add) 9.6.1.1.1
The Authority having jurisdiction (AHJ), for the purpose of enforcing the Rhode Island Life Safety Code, § 9.6 shall be the State Fire Marshal or his or her designee and those parties certified by the State Fire Marshal as prescribed by R.I. Gen. Laws § 23-28.2-6 and 23-28.2-9.
(Amd) 9.6.1.3*
Where required, a fire alarm system shall be installed, tested, and maintained in accordance with the applicable requirements of this Chapter, NFPA 70, National Electrical Code, and NFPA 72, National Fire Alarm and Signaling Code. Any conflicts between the provisions of this Chapter, as amended and NFPA 72 shall be resolved in favor of the provisions of this Chapter as determined by the State Fire Marshal.
(Add) 9.6.1.4.1
All systems and components shall be approved for the purpose for which they are installed, and listed or approved by a nationally recognized testing laboratory.
(Amd) 9.6.1.5 Where a required fire alarm system is out of service for more than four (4) hours in a twenty-four (24) hour period for repair, maintenance or testing, the authority having jurisdiction shall be notified, and the building impairment procedures shall comply with NFPA 72.
(Add) 9.6.1.5.1 With the written approval of, and subject to any additional safeguards mandated by the AHJ, the fire alarm systems, or portions thereof may be temporarily disabled for events or other occasions by qualified personnel where environmental, mechanical or human factors would lead to unnecessary nuisance, accidental or intentional false alarms.
3. Areas of the building not identified in § 9.6.2.9(2), but requiring detection based on § 9.6.2.9(1), shall be permitted to be protected by automatic heat detectors or an approved, supervised automatic sprinkler system.
(Add) 9.6.2.11 Where required by Chapters 11 through 43, an automatic fire detection system for initiation of the signaling system shall be provided in accordance with all of the following:
(Add) 9.6.1.6 Whenever the terms “hardwired 120 vAC-powered” “hard-wired” or “hardwired” are used in this Code as it relates to the primary power supply for single or multiple station smoke alarms or carbon monoxide (CO) alarms, the provisions of NFPA 72 § 29.9.1 (2022) shall apply.
(Add) 9.6.1.7 Whenever the term “wireless” is used in this Code as it relates to household fire alarm systems and/or single or multiple station alarms, it shall mean low-power radio (wireless) and the provisions of NFPA 72:§ 29.10.8 (2022) shall apply.
(Add) 9.6.2.2.1
Manual fire alarm boxes shall be double-action, key locked and shall be keyed the same as the fire alarm control unit door lock. Manual fire alarm boxes shall be installed in accordance with NFPA 72.
(Add) 9.6.2.2.1.1
Existing single-action manual fire alarm boxes that are provided with listed protective covers, with or without a local signal, may be continued in use and deemed compliant with the double-action requirement of § 9.6.2.2.1.
(Add) 9.6.2.2.2
Manual fire alarm boxes, new and existing, used in systems not equipped for emergency forces notification shall be marked “In case of emergency, pull handle, then call 9-1-1”.
(Amd) 9.6.2.8 Where a sprinkler system provides automatic detection and alarm system initiation, it shall be provided with an approved alarm initiation device that operates within ninety (90) seconds when the flow of water is equal to or greater than that from a single automatic sprinkler.
(Amd) 9.6.2.9 Where a total (complete) coverage fire alarm system is required by another section of this Code, automatic detection shall be provided as follows:
(5) Spaces twenty-four inches (24”) (0.61m) or more above suspended ceilings shall be exempt from the requirements of § 9.6.2.11(3) if the building is of Type I or Type II construction and all interior surfaces of the above ceiling space have a Class A or B interior finish rating and the space is not utilized for storage.
(Add) 9.6.2.12
In locations where heat detectors and/or smoke detectors are required, the type and/or temperature rating of the heat detector or smoke detector may be modified if the type or temperature rating of the device is unsuitable due to environmental or structural conditions unique to that location or where multiple nuisance alarms have occurred, subject to the approval of the AHJ.
(Add) 9.6.2.13 Where a specific temperature rating or type of heat detector is specified elsewhere in this code, rate anticipation detectors, line-type detectors, beam detectors or other type detectors listed for the application may be installed where approved by the AHJ.
(Res) 9.6.3.2.1
(Amd) 9.6.3.2.2 Where duct-type smoke detectors are installed in HVAC systems in buildings requiring a fire alarm system, the duct-type smoke detectors shall be connected to the fire alarm control unit to signal an audible and visual supervisory signal at the fire alarm control unit and annunciator. An alarm condition shall not occur unless specifically requested and authorized by the AHJ.
(Res) 9.6.3.2.3
(Res) 9.6.3.6.3
(Res) 9.6.3.6.4
(Amd) 9.6.3.10 Automatically transmitted or approved live voice evacuation or relocation instructions shall be permitted to be used to notify occupants and shall comply with either §§ 9.6.3.10.1 or 9.6.3.10.2.
(Amd) 9.6.3.10.2* Where permitted by Chapters 11 through 43 and subject to the approval of the authority having jurisdiction, automatically transmitted or live voice announcements shall be permitted to be made via a voice communication or public address system that complies with the following:
4. Emergency announcements shall take precedence over any other use.
(Amd) RILSC 9.6.4.2 Where emergency forces notification is required by this Code and provided for in a building in a city, town, or fire district having a public emergency alarm reporting system, the protected premises fire alarm reporting system within the building shall be connected into the public emergency reporting system via a local energy master box, auxiliary transmitter, radio master box, or other approved method so that any fire alarm signal within the building will be automatically transmitted to the community’s communications center.
(Add) 9.6.4.2.1 Systems requiring emergency forces notification in buildings in a city, town, or fire district not having a public emergency alarm reporting system shall be connected to the community communications center via a remote supervising station alarm system or other method in a manner approved by the AHJ so that any fire alarm signal within the building will be automatically transmitted to the community’s communications center.
7. Operation of exterior horn/strobe notification appliances
(Add) 9.6.6.3 Where the functions identified in §§ 9.6.6.2(5), (6) or (7) are provided, they shall be actuated upon the initiation of any manual fire alarm box, automatic initiating device or extinguishing system operation installed within the building.
(Add) 9.6.6.4 A manual override for each fire safety function installed in accordance with § 9.6.5.2 shall be provided at the fire alarm control unit for maintenance, drills and testing of the fire alarm system.
(Add) 9.6.6.5 All buildings that have a fire alarm system required by this Code that requires emergency egress and relocation fire drills to be held shall have a key-operated drill switch to activate the notification appliances in the building, installed at a remote location outside of the fire alarm control unit, subject to the approval of the AHJ. The drill switch key shall not be the same as the fire alarm control unit key.
(Add) 9.6.8.2.1 A directory or zone map as required by the AHJ shall be provided for every required fire alarm system. The directory or zone map shall be provided in a location deemed acceptable by the AHJ.
(Amd) 9.6.8.3 For the purposes of alarm annunciation, each floor of the building shall be considered as not less than one (1) zone, unless otherwise permitted by §§ 9.6.8.4.4, 9.6.8.4.6 or another section of this Code.
(Res) 9.6.8.4.5
(Amd) 9.6.8.4.6 Where the building is protected by an automatic sprinkler system in accordance with § 9.7.1.1(2), the sprinkler system shall be permitted to be annunciated on the fire alarm system as a single zone.
(Add) 9.6.8.9 Where a building is protected by an automatic sprinkler system in accordance with §§ 9.7.1.1(1) or (3), any alarm originating from a sprinkler or a Class II or Class III standpipe connection shall provide two (2) separate indications on the system annunciator, one to indicate “sprinkler/standpipe” and one (1) to indicate the activated zone.
(Add) 9.6.8.10 Where an existing building that is not classified as a high-rise is protected by an existing sprinkler system in accordance with § 9.7.1.1, the sprinkler system shall be permitted to be annunciated on the fire alarm system as a single zone.
(Add) 9.6.8.11 Supervisory signals, including the operation of sprinkler control valve supervisory switches or duct type smoke detectors, shall be permitted to annunciate as a trouble signal on existing fire alarm systems.
(Add) 9.6.8.12 In complexes consisting of multiple building clusters without emergency forces notification, each building shall be clearly identified visually on site in a manner approved by the AHJ (i.e.: strobe lights, etc.).
(Add) 9.6.4.4.1 Whenever any supervisory signal or trouble signal is required to sound and be displayed at a location that is constantly attended by qualified personnel, signals that sound and are displayed in a public or common area of the building shall be deemed to be in compliance.
(Add) 9.6.4.5 All fire alarm control units connected to the local Public Emergency Alarm Reporting System shall be configured to restore the emergency forces notification circuit when an alarm signal is acknowledged and/or the notification appliance circuit(s) silenced.
(Add) 9.6.4.6 Where emergency forces notification is provided, multiple-zone signaling from the protected premises fire alarm control unit shall be provided in any jurisdiction capable of receiving multiple-zone signals and shall be provided as required by the AHJ.
(Add) 9.6.4.7 In complexes consisting of multiple building clusters, a single means of connection in accordance with § 9.6.4.2 may be used to accomplish emergency forces notification provided that each building is clearly identified visually on site in a manner approved by the AHJ (i.e.: strobe lights, etc.)
(Amd) 9.6.6.2 Where required by another section of this Code, the following functions shall be actuated:
(Add) 9.6.9.8 Low-Power Radio
All conductors shall be minimum #16 gauge and be solid copper, type “thhn”, “thwn” or “tfn” unless otherwise specified by the manufacturer. All wiring shall be run continuously from device to device. With the approval of the AHJ, junction points may be made due to construction hardships where a continuous run would be impractical.
The color code for all newly installed fire alarm system conductors shall be as follows:
Terminal cabinets shall be provided at all junction points, except for previously approved installations. Terminal cabinets shall be red with hinged locked covers. All conductor splices or terminations shall be made on screw- type terminal blocks – wire nuts, butt or crimp type connectors shall not be used. All terminals within a terminal cabinet shall be properly identified.
(Add) 9.6.11.1 A pre-acceptance test will be held with the installer and the manufacturer's technical representative present. The pretest shall be a one hundred percent (100%) test as follows:
(Add) 9.6.11.5 At the time of the final acceptance test, a Uniform Test Report (UTR) as prescribed by § 9.6.11.4 shall be completed and a sticker affixed to the fire alarm control unit.
(Add) 9.6.12 Maintenance and Testing
(Add) 9.6.12.5 In addition to the required testing requirements above, all system smoke detectors located within the protected premises shall be externally cleaned at least once every twelve (12) month period.
(c) Elevator machine rooms shall be used for no purpose other than elevator machine rooms.
(Add) 9.7.1.7 Certification of any periodic testing required by the Code shall be on the Uniform Testing Report (UTR) as prescribed in NFPA 1, §§ 1.13.1(12) & (13) and issued by the State Fire Marshal. This UTR shall be utilized by all persons and firms performing automatic sprinkler or standpipe testing and inspections pursuant to this Code and shall bear the name and license number of the licensed person performing the test.
(Add) 9.7.2.1.2.1 Whenever any supervised automatic sprinkler supervisory signal is required to sound and be displayed at a location that is constantly attended by qualified personnel or at a remotely located receiving facility, signals that sound and are displayed in a public or common area of the protected premises shall be deemed to be in compliance.
(Amd) 9.12 Where required by another section of this Code, carbon monoxide (CO) detection and warning equipment shall be provided in accordance with NFPA 72 (2022).
(Add) 9.6.12.6 All persons and firms performing any installation, servicing, maintenance and/or testing & inspections required by this Chapter shall be licensed in accordance with R.I. Gen. Laws § 5-6-2, “Electricians – Work for Which License Required.”
(Add) 9.7.1.6 Fire protection for elevator installations shall be as follows:
Chapter 11 has been adopted with the following changes:
(Add) 11.8.4.4 Emergency voice/alarm communication systems shall also be provided with standby amplifiers equal to the amount of amplification required for the complete system operation.
(Add) 11.8.4.5 Smoke detectors shall be installed in stairwells at the first floor, every third (3rd) floor thereafter and at the top of every stairwell.
(Add) 11.8.4.6 Where partial or selective evacuation is required by the AHJ, stairwell smoke detector activation shall not cause an evacuation signal to be sounded; however; emergency forces notification shall occur.
Chapter 12 has been adopted with the following changes:
3. An approved fire detection system in accordance with § 9.6.2.11.
(Res) 12.3.4.2.2
(Res) 12.3.4.2.3
(Add) 12.3.4.2.4 A manual fire alarm box shall be installed on every stage, near any fixed lighting control panel and in any projection booth.
(Add) 12.3.4.2.5 Manual fire alarm boxes, with the approval of the AHJ, may be omitted from required exits and installed in such supervised locations as bar areas, hostess stands, refreshment stands, ticket booths or other areas constantly attended by properly trained staff whenever the facility is occupied.
(Amd) 12.3.4.3 Notification. Occupant notification by both audible and visible means shall be provided automatically in accordance with § 9.6.3.
(Amd) 12.3.4.1.1 Assembly occupancies shall be provided with an approved fire alarm system in accordance with §§ 9.6.1 and 12.3.4, unless otherwise permitted by §§ 12.3.4.1.2 or 12.3.4.1.3.
(Add) 12.3.4.1.3 Places of worship with a calculated occupant load of seventy-four (74) or fewer occupants and no more than one (1) story above grade shall not be required to be provided with a fire alarm system.
(Amd) 12.3.4.2.1 Initiation of the required fire alarm system shall be all of the following means:
(Add) 12.3.4.3.9 Emergency forces notification shall be provided in accordance with where one (1) of the following conditions exists:
(Add) 12.3.4.3.10.2 In any assembly occupancy where the exemption to the requirement for automatic sprinklers is utilized, the fire alarm system shall meet the requirements for total (complete) coverage.
Exception: Places of Worship.
(Amd) 12.3.5.1
Pursuant to R.I. Gen. Laws § 23-28.6-21, nightclubs with an occupant load that exceed one hundred fifty (150), shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with NFPA 13.
(Add) 12.7.1.4
In places of assembly which have scheduled activities for recreational, educational, political, fraternal, social, or amusement purposes, the owner or management must inspect every exit from the building not more than ninety (90) minutes prior to the beginning of any event, meeting, concert, etc. If the inspection reveals blocked exits, the scheduled presentation must not begin until the exits are cleared and made easily accessible, assuring the safety and welfare of the patrons.
(Add) 12.7.3.1
The use of open flame devices or pyrotechnic devices, outlined in § 12.7.3, shall be limited to the places of assembly with occupancy loads in excess of one thousand (1,000) persons and to those places of assembly, that are theaters, with occupancy loads of greater than three hundred (300) but less than one thousand one (1,001). All such places of assembly must be fully sprinkled and further protected by a fire alarm system providing emergency forces notification.
(Amd) 12.7.6 Crowd Management
The crowd manager and crowd management supervisor shall receive appropriate training in emergency planning and basic crowd control techniques, by the State Fire Marshal, or his or her designee.
(Add) 13.1.8 Places of Worship
A Place of Worship is defined as a building or structure, or an area thereof, the occupancy of which is for the religious rites and services and communal functions of a congregation, and which shall include sanctuaries, gathering halls, meeting rooms, rooms used on a limited basis for religious education, offices and related facilities of the congregation, which may be located in the same, in connected, or in proximate structures.
In areas where there are incidental uses such as non-licensed day care or nurseries the provisions of the Rhode Island Fire Alarm Code, NFPA 72, as amended, also shall apply.
Any one (1), two (2) or three (3) family residential building that comes under the classification of a Place of Worship that is utilized as a rectory, parsonage, convent or other residence used exclusively for religious personnel, shall only be required to be protected by approved hardwired smoke alarms. In addition, approved carbon monoxide alarms shall be installed when these CO alarms would be otherwise required under the fire code provisions covering one (1), two (2) and three (3) family homes.
Any religious-related business office use of a portion of a one (1), two (2) or three (3) family residential building, or a place of worship, as outlined above, that is confined to a space of less than one thousand (1,000) square feet of that building, shall not be required to maintain a fire alarm system provided that the above required smoke alarm and/or CO detection system is operational and maintained. Larger business office space, up to the square footage threshold for fire alarm coverage as outlined in this code, may be exempted from fire alarm coverage if it is properly separated from the remainder of the residential building, by approved “acceptable separation”, as outlined in § 6.1.14.3.2.1.
Any place of worship, existing as of January 1, 2008, shall be deemed in compliance with the provisions of Chapter 13, upon meeting the following fifteen (15) requirements within the time frames provided in this Code. The owners and/or operators of any such existing Place of Worship shall not be required to comply with any additional assembly occupancy requirements. The above owners and/or operators may also seek an additional time extension from the Fire Board.
15. The use of any open flame(s) shall be in accordance with 101:13.7.3.
Any new construction, renovations, alterations, reconstruction and/or additions to an existing Place of Worship, covered by the above fifteen (15) point plan, shall comply with the applicable Fire Codes covering those activities in an existing place of assembly. Notwithstanding the above, the existing portions of a Place of Worship shall not be required to be sprinkled unless they are not separated, from any new addition proposed for assembly occupancy, by approximately one (1) hour fire rated separation. In the absence of an approximate one (1) hour fire separation between an existing and a new assembly occupancy, the merged existing and new assembly occupancies shall be calculated on the basis of fifteen (15) square feet per person to determine whether sprinklers are to be required.
(Amd) 13.3.4.1.1 Assembly occupancies shall be provided with an approved fire alarm system in accordance with §§ 9.6.1 and 13.3.4, unless otherwise permitted by §§ 13.3.4.1.2 or 13.3.4.1.5.
(Res) 13.3.4.1.4
3. An approved fire detection system in accordance with § 9.6.2.11.
(Res) 13.3.4.2.2
(Res) 13.3.4.2.3
(Add) 13.3.4.2.4 A manual fire alarm box shall be installed on every stage, near any fixed lighting control panel and in any projection booth.
(Add) 13.3.4.2.5 Manual fire alarm boxes, with the approval of the AHJ, may be omitted from required exits and installed in such supervised locations as bar areas, hostess stands, refreshment stands, ticket booths or other areas constantly attended by properly trained staff whenever the facility is occupied.
(Amd) 13.3.4.3 Notification. Occupant notification by both audible and visible means shall be provided automatically in accordance with § 9.6.3.
(Add) 13.3.4.1.5 Places of worship with a calculated occupant load of seventy-four (74) or less occupants and no more than one (1) story above grade shall not be required to be provided with a fire alarm system.
(Amd) 13.3.4.2.1 Initiation of the required fire alarm system shall be by all of the following means:
(Add) 13.3.4.3.9 Emergency forces notification shall be provided in accordance with where one (1) of the following conditions exists:
(Add) 13.3.4.4.2 In any existing place of worship where the exemption to the requirement for automatic sprinklers is utilized, the fire alarm system shall not be required to meet the requirements for total (complete) coverage.
(Amd) 13.3.5.1
Unless exempted by another provision of this Chapter, all existing places of assembly shall be completely protected by an approved, supervised automatic sprinkler system installed and maintained in accordance with § 9.7.1.1(1).
The requirements of 13.3.5.1 shall not apply to the following:
(Add) 13.3.5.7
The occupancy of any place of assembly without a required fire alarm system and/or sprinkler system, shall have its maximum occupancy adjusted by minus ten percent (10%) for the absence of a fire alarm system and minus twenty percent (20%) for the absence of a sprinkler system, when sprinklers are required by law or Regulation. Such downward adjustment in occupancy shall be cumulative and shall cease to apply when the premises are in compliance with the requirements for fire alarm systems and sprinklers, and shall not affect any other requirements of this Code, or the Fire Safety Code Board of Appeal and Review, applicable to the premises. This Section shall not be construed to act as an exemption for otherwise required fire protection systems.
(Add) 13.4.5.1 Existing high-rise buildings shall be provided with a detection, alarm and communication system in accordance with § 11.8.4 and an emergency command center complying with § 11.8.6.
(Add) 13.4.13 Nightclubs
All nightclubs, as defined in § 3.4.13, shall comply with the requirements of §§ 13.4.13.2 through 13.4.13.4 and shall be inspected annually by the AHJ.
(Add) 13.4.13.3
The responsible management of each nightclub shall provide an audible announcement of the location of emergency exits prior to each act or set.
(Add) 13.4.13.4
The responsible management of each nightclub shall have an emergency plan for the rapid evacuation of the premises approved by the State Fire Marshal. The plan shall identify the egress system of the building, explain, on a step-by-step basis, how the crowd manager on duty will complete the evacuation, and explain how the crowd manager will direct the occupants to safety in the event of one (1) or more blocked exits.
(Add) 13.7.1.4
In places of assembly which have scheduled activities for recreational, educational, political, fraternal, social, or amusement purposes, the owner or management must inspect every exit from the building not more than ninety (90) minutes prior to the beginning of any event, meeting, concert, etc. If the inspection reveals blocked exits, the scheduled presentation must not begin until the exits are cleared and made easily accessible, assuring the safety and welfare of the patrons.
(Add) 13.7.3.1
The use of open flame devices or pyrotechnic devices, outlined in § 13.7.3, shall be limited to the places of assembly with occupancy loads in excess of one thousand (1,000) persons and to those places of assembly, that are theaters, with occupancy loads of greater than three hundred (300) but less than one thousand one (1,001). All such places of assembly must be fully sprinkled and further protected by a fire alarm system providing emergency forces notification.
(Amd) 13.7.6 Crowd Management
The crowd manager and crown management supervisor shall receive appropriate training in emergency planning and basic crowd control techniques, by the State Fire Marshal, or his or her designee.
Admissions to all places of assembly shall be supervised by the responsible management or by the person or persons delegated with the responsibility by the management, and the responsible person shall not allow admissions in excess of the maximum occupancy posted by the State Fire Marshal or his or her designee.
Chapter 14 has been adopted with the following changes:
(Amd) 14.1.2.3 In cases where instruction is incidental to some other occupancy, the section of this Code governing the other occupancy shall apply. Sunday schools or church schools that are not used for daily classes throughout the week shall comply with the section of this Code dealing with places of worship.
(Amd) 14.3.4.2.1 Initiation of the required fire alarm system shall be by all of the following means:
(Add) 14.3.4.6
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
Chapter 15 has been adopted with the following changes:
(Amd) 15.1.2.3 In cases where instruction is incidental to some other occupancy, the section of this Code governing the other occupancy shall apply. Sunday schools or church schools that are not used for daily classes throughout the week shall comply with the section of this Code dealing with places of worship.
(Amd) 15.3.4.2.1 Initiation of the required fire alarm system shall be by all of the following means:
(Res) 15.3.4.2.3
(Res) 15.3.4.2.3.2
(Add) 15.3.4.6
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Add) 15.3.6 Corridors
(6) In buildings protected throughout by a total (complete) fire alarm system with emergency forces notification, self-closing devices shall not be required on normally occupied classroom doors provided that teachers and other faculty/staff are trained to close all doors in the event of an emergency.
(Amd) 15.4.3 High-Rise Buildings. High-rise buildings shall comply with § 11.8.1 and be provided with a detection, alarm and communication system in accordance with § 11.8.4 and an emergency command center complying with § 11.8.6.
(Add) 15.7.3.4Annual Inspections
All educational occupancies shall be inspected annually by the AHJ.
Chapter 16 has been adopted with the following changes:
3. An approved fire detection system in accordance with § 9.6.2.9.
(Add) 16.3.4.4.1 Emergency forces notifications shall not be required for day care occupancies with less than nineteen (19) clients, under three thousand (3,000) ft2 (278.71 m2) and located on a ground floor.
(Amd) 16.3.4.5 Detection. Where a fire alarm system is required, a total (complete) coverage fire detection system in accordance with § 9.6.2.9 shall be provided.
(Add) 16.2.2.2.3.4 It shall be recognized that, in buildings. or portions thereof, housing certain clients who exhibit behavior that is harmful to themselves or others, it might be necessary to lock egress doors to confine and protect building inhabitants.
(Add) 16.2.2.2.3.5 Buildings, or sections thereof, that primarily house clients who, in the opinion of the governing body of the facility, the governmental licensing agency, or authority having jurisdiction, are incapable of self-preservation under emergency conditions shall be permitted to have locking arrangements complying with the provisions of § 18.2.2.2.5.
(Add) 16.2.2.2.3.6 The requirements of § 16.2.2.2.3.5 shall only apply when staff is available in all secured client-occupied areas to perform certain fire safety functions as required in §§ 18.2.2.2.5 through 18.2.2.2.5.2, and 18.7.
(Amd) 16.3.4.1 General. Day-care occupancies shall be provided with a fire alarm system in accordance with § 9.6.
(Amd) 16.3.4.2 Initiation. Initiation of the required fire alarm system shall be by all of the following means:
(Add) 16.3.4.5.1 In addition to the requirements of § 9.6.2.9(2), smoke detectors shall be installed in all lounges, recreation areas and sleeping rooms within the day-care occupancy.
(Add) 16.3.4.6 Smoke and Carbon Monoxide Alarms. Every child day-care occupancy shall be provided with either hardwired or wireless smoke and carbon monoxide alarms installed in accordance with the referenced edition of NFPA 72. Local smoke alarms shall not be required in areas protected by system smoke detectors.
(Add) A.16.3.4.6 The application or use of single-station carbon monoxide alarms in sleeping areas is considered the equivalent of installations in dwelling units.
(Add) 16.3.4.7
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 16.6.3.4.6 Single-station or multiple station carbon monoxide alarms or detectors shall be provided in accordance with § 9.12 in day care homes where client sleeping occurs.
Chapter 17 has been adopted with the following changes:
3. An approved fire detection system in accordance with § 9.6.2.9.
(Amd) 17.3.4.4.1 Emergency forces notification shall be accomplished in accordance with § 9.6.4.
(Amd) 17.3.4.4.2 Emergency forces notifications shall not be required for day care occupancies with less than nineteen (19) clients, under three thousand (3,000) ft2 (278.71 m2) and located on a ground floor.
(Amd) 17.3.4.5 Detection. Where a fire alarm system is required, a total (complete) coverage fire detection system in accordance with § 9.6.2.9 shall be provided.
(Add) 17.2.2.2.3.4 It shall be recognized that, in buildings or portions thereof, housing certain clients who exhibit behavior that is harmful to themselves or others, it might be necessary to lock egress doors to confine and protect building inhabitants.
(Add) 17.2.2.2.3.5 Buildings, or sections thereof, that primarily house clients who, in the opinion of the governing body of the facility, the governmental licensing agency, or authority having jurisdiction, are incapable of self-preservation under emergency conditions shall be permitted to have locking arrangements complying with the provisions of § 19.2.2.2.5.
(Add) 17.2.2.2.3.6 The requirements of § 17.2.2.2.3.5 shall only apply when staff is available in all secured client-occupied areas to perform certain fire safety functions as required in §§ 19.2.2.2.5 through 19.2.2.2.5.2, and 19.7.
(Amd) 17.3.4.1. General. Day-care occupancies shall be provided with a fire alarm system in accordance with § 9.6.
(Amd) 17.3.4.2 Initiation. Initiation of the required fire alarm system shall be by all of the following means:
Exception: The requirements of this Section shall not apply to rooms that have previously approved hardwired smoke alarms AND system heat detectors or automatic sprinklers.
(Add) 17.3.4.6 Smoke and Carbon Monoxide Alarms. Every child day-care occupancy shall be provided with either hardwired or wireless smoke and carbon monoxide alarms installed in accordance with the referenced edition of NFPA 72. Local smoke alarms shall not be required in areas protected by system smoke detectors.
(Add) A.17.3.4.6 The application or use of single-station carbon monoxide alarms in sleeping areas is considered the equivalent of installations in dwelling units.
(Add) 17.3.4.7
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Res) 17.6.3.4.4
(Res) 17.6.3.4.5
(Add) 17.6.3.4.6. Carbon Monoxide Alarms.
Day-care homes shall be provided with either hardwired or wireless carbon monoxide alarms installed in accordance with the referenced edition of NFPA 72.
Chapter 18 has been adopted with the following changes:
(Amd) 18.3.4.5.1 General. A total (complete) coverage fire detection system in accordance with § 9.6.2.9 shall be provided.
(Res) 18.3.4.5.3
(Add) 18.3.4.6
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
Chapter 19 has been adopted with the following changes:
(Res) 19.3.4.2.3
(Amd) 19.3.4.5.1 A total (complete) coverage fire detection system in accordance with § 9.6.2.9 shall be provided, unless otherwise permitted by § 19.3.4.5.3.
(Add) 19.3.4.5.3 Health care occupancies built or converted prior to January 1, 2005 shall be permitted to have a fire detection system complying with § 9.6.2.11.
(Add) 19.3.4.6
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 19.4.3.1 All high-rise buildings containing health care occupancies shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with the RIFC, NFPA 1, as amended.
(Res) 19.4.3.2
(Res) 19.4.3.3
(Res) 19.4.3.4
(Add) 19.4.3.5 High-rise buildings shall be provided with a detection, alarm and communication system in accordance with § 11.8.4 and an emergency command center complying with § 11.8.6.
Chapter 20 has been adopted with the following changes:
(Amd) 20.3.4.1 General. Ambulatory health care facilities shall be provided with fire alarm systems in accordance with § 9.6, except as modified by §§ 20.3.4.2 through 20.3.4.5.
(Amd) 20.3.4.2 Initiation. Initiation of the required fire alarm systems shall be by manual means in accordance with § 9.6.2 and by means of any required sprinkler system waterflow alarms, detection devices or detection systems.
(Add) 20.3.4.5 Detection. A total (complete) coverage fire detection system in accordance with § 9.6.2.9 shall be provided.
(Add) 20.3.4.6
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
Chapter 21 has been adopted with the following changes:
2. (Add) 21.3.4.5.2 Ambulatory health care occupancies built or converted prior to January 1, 2005, shall be permitted to have a fire detection system complying with § 9.6.2.11.
(Add) 21.3.4.6
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 21.3.4.1 General. Ambulatory health care facilities shall be provided with fire alarm systems in accordance with § 9.6, except as modified by §§ 21.3.4.2 through 21.3.4.5.
(Amd) 21.3.4.2 Initiation. Initiation of the required fire alarm systems shall be by manual means in accordance with § 9.6.2 and by means of any required sprinkler system waterflow alarms, detection devices or detection systems.
(Add) 21.3.4.5Detection.
(Amd) 22.3.4.3.2.1. Emergency forces notification shall be accomplished in accordance with § 9.6.4.
(Res) 22.3.4.3.2.2.
(Amd) 22.3.4.4 Detection. An approved fire detection system, including a smoke detection system throughout all resident sleeping areas and adjacent day rooms, activity rooms, or contiguous common spaces, shall be in accordance with § 9.6.2.11 as modified by §§ 22.3.4.4.1 through 22.3.4.4.5.
(Add) 22.3.4.5.
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 22.4.3 High-Rise Buildings. High-rise buildings shall comply with §§ 11.8.3, 11.8.4 and 11.8.6.
(Amd) 22.4.4.9 Detection, Alarm, and Communications Systems (Nonsprinklered Buildings). A fire alarms system in accordance with §§ 22.3.4 and 9.6 shall be provided.
Chapter 23 has been adopted with the following changes:
2. Manual fire alarm boxes shall be permitted to be located in a staff location, provided that both of the following criteria are met:
(Amd) 23.3.4.2 Initiation of the required fire alarm system shall be by manual means in accordance with § 9.6.2 and by means of any required sprinkler system water flow alarms, detection devices, or detection systems, unless otherwise permitted by the following:
(Res) 23.3.4.2.2
(Amd) 23.3.4.3.2.1 Emergency forces notification shall be accomplished in accordance with § 9.6.4.
(Res) 23.3.4.3.2.2
(Amd) 23.3.4.4 Detection. An approved fire detection system, including a smoke detection system throughout all resident housing areas, shall be in accordance with § 9.6.2.11 as modified by §§ 23.3.4.4.1 through 23.3.4.4.4.
(Add) 23.3.4.5
Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Add) 23.4.3.1 Existing high-rise buildings shall comply with §§ 11.8.4 and 11.8.6.
All one (1) and two (2) family dwellings shall remain subject to, and comply with, the State Building Code SBC-2, 510-RICR-00-00-2 adopted pursuant to R.I. Gen. Laws Chapter 23-27.3 et seq.
All one (1) and two (2) family dwellings shall further remain subject to, and comply with the Rhode Island Property Maintenance Code (SBC-6), 510-RICR-00-00-6.
(Add) 24.6.2Installation of Smoke and Carbon Monoxide Alarms-New and converted buildings.
All buildings hereinafter constructed or converted for residential occupancy, including mobile and modular homes, shall be provided with smoke and carbon monoxide alarms, installed in accordance with §§ 24.3.4.1.1 and 24.3.4.2 and NFPA 72, at the direction and to the satisfaction of the AHJ.
In addition, an interconnected smoke alarm(s) shall be installed in all communicating attached garages for which a building permit was issued on or after January 1, 2019.
Compliance with the above provisions shall be considered a prerequisite to the approval, by the fire authority, of any certificate of occupancy issued by the building official pursuant to R.I. Gen. Laws § 23-27.3-120.
It shall be the responsibility of the owner to maintain in operable condition smoke and carbon monoxide alarms, installed as required pursuant to this Chapter, and the owner shall make operable, within seven (7) days after being notified by certified mail by the occupant and/or enforcement official, any inoperable alarms.
(Add) 24.6.3 Installation of Smoke and Carbon Monoxide Alarms-Existing Buildings
All occupied residential properties, including mobile homes, shall, at the responsibility of the seller before title to the property is transferred, be provided with smoke and carbon monoxide alarms, installed in accordance with this Section, at the direction and to the satisfaction of the AHJ.
The above smoke and carbon monoxide alarms may be installed as either separate or combination units approved by the AHJ. Carbon monoxide alarms required by § 24.6.3 shall be in accordance with § 24.3.4.2.
The requirements for the above smoke alarms and carbon monoxide alarms or detectors shall be as follows:
(Add) 24.6.3.1.1.1 Homes built in 1976 or prior:
(6) Carbon Monoxide Alarms or Detectors are not required to be interconnected.
(Add) 24.6.3.1.1.2 Homes built on and after January 1, 1977 through December 31, 2001:
(6) Carbon Monoxide Alarms or Detectors are not required to be interconnected.
(Add) 24.6.3.1.1.3 Homes built on and after January 1, 2002 through February 19, 2004:
(6) Carbon Monoxide Alarms or Detectors shall be required to be interconnected.
(Add) 24.6.3.1.1.4 Homes built on and after February 20, 2004 through December 31, 2012:
(6) Carbon Monoxide Alarms or Detectors shall be required to be interconnected.
(Add) 24.6.3.1.1.5 Homes built on and after January 1, 2013 through September 30, 2016:
(2) Carbon Monoxide Alarms or Detectors shall be installed in accordance with NFPA 720 (2012 Edition).
(Add) 24.6.3.1.1.6 Homes built on and after October 1, 2016, through June 30, 2021:
(2) Carbon Monoxide Alarms or Detectors shall be installed in accordance with § 24.3.4.2 and NFPA 720 (2015 Edition).
(Add) 24.6.3.1.1.7 Homes built on and after July 1, 2021, through March 1, 2026:
(2) Carbon Monoxide Alarms or Detectors shall be installed in accordance with § 24.3.4.2 and NFPA 72 (2019 Edition).
(Add) 24.6.3.1.1.8 Notwithstanding the provisions of §§ 24.6.3.1.1.1 through 24.6.3.1.1.6, newly constructed or converted bedrooms or sleeping areas shall comply with the requirements for new construction in place at the time of construction or conversion.
(Add) 24.6.3.1.1.9 For the purposes of sections 24.6.3.1.1.1 through 24.6.3.1.1.3, the term “outside sleeping areas” shall include “in the immediate vicinity of the bedrooms”.
(Add) 24.6.3.1.2
The above smoke and carbon monoxide alarms may be installed as follows:
(1) Where the above provisions require both smoke alarms and carbon monoxide alarms or detectors, combination devices shall be permitted and deemed acceptable.
(2) Where smoke alarms are required, household fire alarm systems, in accordance with NFPA 72 (2022 Edition), shall be permitted and deemed to be acceptable.
(Add) 24.6.3.1.3
The local fire authorities shall enforce the provisions of this Chapter. The State Fire Marshal’s Office may enforce the provisions of this Chapter when so requested to by the local authority or when the local authority is either unwilling or unable to fulfill its obligations under this Chapter.
The local fire authority that performs smoke and carbon monoxide alarm inspections in all residential occupancies shall, at the time of the inspection, be allowed to charge a thirty dollar ($30.00) fee for the inspection of any residential occupancy. The responsibility of this charged fee will be borne by the seller on each occurrence before title to the property is transferred. A sixty dollar ($60.00) fee will be allowed for any subsequent re-inspection of the same residential occupancy due to improper installation, wrong location, improper wiring method, or the seller’s failure to maintain a mutually agreed upon appointment with the local fire authority that performs the inspection function. The fees collected by the local fire authority shall be used for fire prevention purposes in that particular city, town, fire district, or other municipal subdivision.
(Add) 24.6.3.1.4
At the time of the transfer of title, the seller must provide the purchaser with a certificate from the fire department for the community in which the dwelling is located stating that the smoke and carbon monoxide alarms have been inspected within one hundred twenty (120) days prior to the date of sale and has been determined to be in good working order. The fire department for the community in which the dwelling is located must inspect the smoke and carbon monoxide alarms of the dwelling within ten days of a request from the owner. The inspection may be conducted by qualified personnel of the department or the State Fire Marshal’s Office. Neither the fire department nor the State Fire Marshal shall be liable for any damage caused by the subsequent malfunction of a smoke alarm or carbon monoxide alarm which it inspected.
Transfers of real property are exempt from compliance with the provisions of 24.6.2 and 24.6.3 if:
(7) The property is being acquired by the State for demolition and will not be sold or used by the State for residential purposes.
(Add) 24.6.3.1.5
It shall be the responsibility of the owner to maintain in operable condition smoke and carbon monoxide alarms, installed as required pursuant to this Chapter, and the owner shall make operable, within seven (7) days after being notified by certified mail by the occupant and/or enforcement official, any inoperable system.
If the owner fails to make the alarms operable within the required seven (7) days, the tenant may cause the alarms to be made operable if the reasonable total reasonable cost of making the repairs does not exceed the sum of fifty dollars ($50.00), and the tenant may deduct from his or her rent the actual reasonable cost of repairs not to exceed fifty dollars ($50.00).
(Add) 24.6.3.1.6
Owners of existing residential properties, previously required to install smoke alarms, shall maintain those detectors in good operating condition.
(Add) 24.6.3.1.7
(Add) 25.1 Compliance with State Building and Minimum Housing Codes.
(Add) 25.2 Installation of Smoke and Carbon Monoxide Alarms.
All three (3) family apartment buildings hereinafter constructed or converted for residential occupancy, including modular homes, shall be provided with smoke alarms, installed in accordance with § 9.6.2.10.1.
(Add) 25.2.1.1 In addition to the smoke alarms required within the dwelling unit, smoke alarms shall also be located in common areas as follows:
Exception: Common area smoke alarms shall not be required in three (3)family apartments that are protected with an approved automatic sprinkler system.
(2) Dwelling units containing fuel-burning appliances or fuel-burning fireplaces.
(Add) 25.2.1.3.1 Carbon monoxide alarms shall not be required in the following locations:
c. Within dwelling units with communicating attached garages that are mechanically vented in accordance with the Mechanical Code
(Add) 25.2.1.4
(Add) 25.2.1.2 The smoke alarms required by § 25.2.1.1 shall all be interconnected, however, shall not be interconnected with any dwelling unit smoke alarms.
(Add) 25.2.1.3 All three (3)family apartment buildings hereinafter constructed or converted for residential occupancy, including modular homes, shall be provided with carbon monoxide alarms in accordance with § 9.12.
Carbon monoxide alarms shall only be required where either of the following conditions exist:
The above smoke and carbon monoxide alarms may be installed as either separate or combination units approved by the AHJ.
(Add) 25.2.1.5
The above smoke and carbon monoxide alarms may be either hardwired one hundred twenty (120) vAC powered devices with an approved secondary (standby) power source or low-power radio (wireless) devices. Hardwired AC-powered devices utilizing wireless interconnection technology shall be permitted.
(Add) 25.2.1.6
The local fire authorities certified by the State Fire Marshal as prescribed in R.I. Gen. Laws § 23-28.2-9, in cooperation with the local building code officials, shall enforce the provisions of this Chapter. The State Fire Marshal’s Office may enforce the provisions of this Chapter when so requested to by the local authority or when the local authority is either unwilling or unable to fulfill its obligations under this Chapter.
(Add) 25.2.1.7
Compliance with the above provisions shall be considered a prerequisite to the approval, by the fire authority, of any certificate of occupancy issued by the building official pursuant to R.I. Gen. Laws § 23-27.3-120.
(Add) 25.2.1.8
It shall be the responsibility of the owner to maintain in operable condition smoke and carbon monoxide alarms, installed as required pursuant to this Chapter, and the owner shall make operable, within seven (7) days after being notified by certified mail by the occupant and/or enforcement official, any inoperable alarms.
All existing three (3) family apartment buildings used for residential occupancy, including modular homes, shall, be provided with smoke alarms, installed in accordance with § 9.6.2.10.1.
(3) In common basements
Exception: Common area smoke alarms shall not be required in three (3) family apartments that are protected with an approved automatic sprinkler system.
(Add) 25.2.2.3 The smoke alarms required by § 25.2.2.2 shall all be interconnected, however, shall not be interconnected with any dwelling unit smoke alarms.
(Add) 25.2.2.4 All existing three (3) family apartment buildings used for residential occupancy, including modular homes, shall be provided with carbon monoxide alarms in accordance with § 9.12.
Carbon monoxide alarms shall only be required where either of the following conditions exist:
(2) Dwelling units containing fuel-burning appliances or fuel-burning fireplaces.
(Add) 25.2.2.4.1 Carbon monoxide alarms shall not be required in the following locations:
c. Within dwelling units with communicating attached garages that are mechanically vented in accordance with the Mechanical Code
The local fire authorities certified by the State Fire Marshal's Office as prescribed in R.I. Gen. Laws § 23-28.2-9, in cooperation with the building code officials, shall enforce the provisions of this Chapter. The State Fire Marshal’s Office may enforce the provisions of this Chapter when so requested to by the local authority or when the local authority is either unwilling or unable to fulfill its obligations under this Chapter.
(Add) 25.2.3Power Supplies
(2) Power supplies for carbon monoxide alarms shall be in accordance with NFPA 72 (2022).
(Add) 25.2.4
(Add) 25.2.2.1 The provisions of § 9.6.2.10.3 shall not apply.
(Add) 25.2.2.2 In addition to the smoke alarms required within the dwelling unit, smoke alarms shall also be located in common areas as follows:
(Add) 25.2.4.1
(Add) 25.2.4.2
Transfers of real property are exempt from compliance with the provisions of §§ 25.2.2 through 25.2.4.5 if:
(Add) RILSC 25.2.4.3
(Add) RILSC 25.2.4.4
(Add) RILSC 25.2.4.5
(Add) RILSC 25.2.4.6
(Amd) 26.1.1.1
The requirements of this Chapter shall apply to buildings that provide sleeping accommodations for sixteen (16) or fewer persons on either a transient or permanent basis, with or without meals, but without separate cooking facilities for individual occupants, except as provided in Chapter 24 and/or as modified by §§ 26.1.1.1.1 through 26.1.1.1.10 (Bed and Breakfast Homes, Congregate Family Living Facilities, Seasonal Camp Cabins and Short Term Rental Units as outlined below.
A “Bed and Breakfast Home” is defined as an owner and/or innkeeper occupied building that provides sleeping accommodations for up to sixteen (16) guests. Every “Bed and Breakfast Home” must further have originated as a private home and must have at least three hundred (300) square feet of common space (i.e. dining room, living room, etc.) for guest use, and must further provide breakfast. Finally, the owner and/or innkeeper must occupy the building twenty-four (24) hours a day, seven (7) days a week, while guests are utilizing the facility. The owner and/or innkeeper of the Bed and Breakfast Home shall have a plan of action, approved by the local official, to assure the safety of the guests in the event the owner or innkeeper is required to temporarily leave the facility unsupervised for limited periods during the day.
A “No Smoking” policy, throughout the building, shall be strictly enforced.
With the exception of fireplaces and/or wood stoves, approved by local fire department and/or the local mechanical inspector, there shall be no open flame in the bedrooms of these facilities. Specifically, candles, incense or similar materials shall not be allowed in the bedrooms. All approved fireplaces and/or wood stoves shall further be provided with approved metal screens or glass doors. Any fireplace or wood stove located in the common areas shall also be approved by local fire department and/or the local mechanical inspector with the above safeguards.
All “Bed and Breakfast Homes” require hardwired, interconnected smoke and carbon monoxide alarms installed in accordance with the Regulations and standards of Chapter 24. There shall be approved detection in each sleeping room.
All “Bed and Breakfast Homes” with a capacity of between four (4) and six (6) guests shall meet the following requirements for this occupancy:
All “Bed and Breakfast Homes” with a capacity of between seven (7) and sixteen (16) guests shall meet the following requirements for this occupancy:
(Add) 26.1.1.1.7
Any building complying with the above “Bed and Breakfast Home” guidelines, with a capacity in excess of sixteen (16) guests, shall be required comply with the requirements for a “Hotel and Dormitory” occupancy as outlined in the provisions of Chapters 28 or 29, as applicable (new or existing), of the Rhode Island Life Safety Code.
(Add) 26.1.1.1.8
Congregate Family Living Facility is defined as a building or part thereof that contains sleeping rooms where residents share the entire structure and live, cook and function together as a single housekeeping unit. Every “Congregate Family Living Facility” must further have originated as a private residence, shall be limited to no more than two (2) stories in height and shall not exceed three thousand five hundred (3,500) gross square feet.
All “Congregate Family Living Facilities” with a capacity of between four (4) and six (6) residents shall meet the following requirements for this occupancy:
All “Congregate Family Living Facilities” with a capacity of between seven (7) and sixteen (16) residents shall meet the following requirements for this occupancy:
(Add) 26.1.1.1.9 For the purposes of this Chapter, a "seasonal camp cabin" shall mean a structure for sleeping accommodations which meets all of the following criteria:
(11) has approved smoke alarms installed in accordance with NFPA 72 Chapter 29 that are interconnected such that the activation of one alarm will activate all of the alarms in the cabin. Only devices equipped with power supplies conforming to 72:29.9.1(1), (2) or (3) shall be permitted.
a. Note: NFPA 72 section A.29.1.2 provides that the requirements of Chapter 29 are intended to apply to installations in the following new and existing locations: … (2) Sleeping rooms of lodging and rooming houses….
(Add) 26.1.1.1.9.1 Any existing structure that is altered, enlarged or otherwise improved shall not be deemed to be a seasonal camp cabin (and shall not be subject to the exception set forth in 26.1.1.1.9.2) unless such structure, as so altered, enlarged or otherwise improved, satisfies all of the criteria set forth in this paragraph.
(Add) 26.1.1.1.9.2 A seasonal camp cabin (as that term is defined above) shall be exempt from all other requirements of Chapter 26.
(Add) 26.1.1.1.10 For the purposes of this Chapter, a "short-term rental unit" shall mean an existing dwelling unit that contains sleeping rooms where residents share the entire dwelling under a single rental agreement. A short-term rental must further have originated as a private one- or two-family dwelling unit and shall be limited to no more than three (3) stories in height and shall not exceed three thousand six hundred (3,600) gross square feet square feet of livable area. For purposes of calculating height and livable square footage under this paragraph, each dwelling unit shall be treated as its own short-term rental. A short-term rental shall be for a period of time not exceeding thirty (30) consecutive days.
(Add) 26.1.1.1.10.1 All “short-term rentals” shall meet the following requirements:
(Amd) 26.3.4.1.1
Lodging and rooming houses shall be provided with a fire alarm system in accordance with § 9.6.
(Res) 26.3.4.1.2
(Amd) 26.3.4.2 Initiation. Initiation of the required fire alarm system shall be by manual means in accordance with § 9.6.2, a fire detection system required by § 23.3.4.4, and by alarm initiation in accordance with § 9.6.2.1(3) in buildings protected throughout by an approved automatic sprinkler system in accordance with § 26.3.6.
(Amd) 26.3.4.4 Detection. Where a fire alarm system is required, a system in accordance with § 9.6.2.11 shall be provided.
(Amd) 26.3.4.5.1 Approved single-station smoke alarms shall be installed in accordance with § 9.6.2.10 in every sleeping room.
(Res) 26.3.4.5.3
(Amd) 26.3.4.6.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with §§ 9.12 and 26.3.4.6 shall be provided in lodging or rooming houses where either of the following conditions exists:
2. Lodging or rooming houses containing fuel-burning appliances or fuel-burning fireplaces.
(Add) 26.3.4.7 Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 26.3.6.1
All new lodging or rooming houses shall be protected throughout by an approved automatic sprinkler system in accordance with § 26.3.6.2.
(Add) 26.3.6.1.1
Every existing lodging or rooming house built, or converted to this occupancy, on or after June 29, 1990, shall be protected throughout by an approved automatic sprinkler system in accordance with § 26.3.6.2.
(Add) 26.3.6.3
Portable fire extinguishers shall be provided in accordance with § 9.9 of this Code.
(Add) 26.5.2.3
Any furnace or boiler in the building shall be equipped with an approved remote shutoff switch approved by the AHJ.
(Add) 27.1 General Requirements.
(Add) 27.1.1 Application.
The requirements of this Chapter shall apply to buildings or structures that provide temporary emergency sleeping space to address an unexpected occurrence that requires immediate action to protect the public for sixteen (16) or fewer persons unless a greater number of occupants is specifically approved by the Fire Safety Code Board of Appeal & Review.
Places of worship, maintaining this temporary occupancy in accordance with the provisions of this Chapter, shall not lose their exception from the requirements of §§ 13.3.5.1 and 13.3.5.1.1 as outlined in § 13.3.5.2.1(4) of this Code.
For buildings with larger occupancies, the requirements of Chapters 28 and 29 are applicable. The owners of such facilities may seek interim relief from specific requirements from the Fire Safety Code Board of Appeal & Review.
(Add) 27.2 Means of Escape Requirements
There shall be at least two (2) clearly defined means of escape to grade from the space used as an emergency shelter.
The means of escape, stairways and doors shall comply with the provisions of §§ 26.2.1.1 through 26.2.3 of this Code.
(Add) 27.3 Protection.
(Add) 27.3.1 Smoke and Carbon Monoxide Detection
(Add) 27.3.2 Supervision
At least one (1) responsible adult, approved by the AHJ and not a resident of the emergency shelter occupancy, shall maintain a fire watch during all hours of occupancy of the emergency shelter facility.
The responsible adult(s) must be trained in fire prevention techniques, fire department notification, evacuation procedures and fire extinguisher operation by the AHJ prior to being approved to oversee the fire watch.
The owner or management of the shelter shall provide the AHJ with a schedule listing the names of the responsible adults conducting the fire watch and the times to which they have been assigned this duty.
(Add) 27.3.3 Protection from Hazards.
No smoking shall be allowed in any building utilized as an emergency shelter facility during any and all periods of this occupancy.
(Add) 27.3.4 Fire Extinguishers.
Chapter 28 has been adopted with the following changes:
(Amd) 28.3.4.5 Detection. A fire detection system in accordance with § 9.6.2.11 shall be provided.
(Add) 28.3.4.8 Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 28.3.5.1.
All new hotel and/or dormitory occupancies shall be protected throughout by approved automatic sprinkler systems in accordance with § 28.3.5.3.
(Amd) 28.3.5.2.
Every hotel and/or dormitory occupancy, every addition hereafter made to a hotel and/or dormitory, and every building hereafter converted for the purposes of a hotel and/or dormitory shall be completely protected by an approved system of automatic sprinklers installed and maintained in accordance with § 28.3.5.3.
(Res) 28.3.5.8
(Add) 28.3.5.9 Portable fire extinguishers shall be provided in all new hotel occupancies in accordance with § 9.9 of this Code.
(Add) 28.5.2.3 Any furnace or boiler in the building shall be equipped with an approved remote shutoff switch approved by the AHJ.
Chapter 29 has been adopted with the following changes:
(4) Required automatic detection system other than sleeping room smoke alarms
(Amd) 29.3.4.3.3 Guest rooms and guest suites specifically required and equipped to accommodate hearing impaired individuals shall be provided with a visible notification appliance.
(Amd) 29.3.4.3.4 In areas subject to occupancy, other than guest rooms and guest suites, visible notification appliances shall be provided.
(Amd) 29.3.4.3.6 Emergency forces notification shall be accomplished in accordance with § 9.6.4.
(Res) 29.3.4.3.7
(Amd) 29.3.4.4 Detection. Where a fire alarm system is required, a fire detection system in accordance with § 9.6.2.11 shall be provided.
(Amd) 29.3.4.1 General. A fire alarm system in accordance with § 9.6, except as modified by §§ 29.3.4.2 through 29.3.4.5, shall be provided.
(Amd) 29.3.4.2 Initiation. The required fire alarm system shall be initiated by each of the following:
(Add) 29.3.4.4.1 A combination rate of rise and one hundred thirty-five degree Fahrenheit (135° F) to one hundred forty degree Fahrenheit (140° F) fixed temperature heat detector shall be installed in every sleeping room, other than sleeping rooms equipped with an approved, supervised automatic sprinkler system in accordance with § 28.3.5.3.
(Add) 29.3.4.6 Carbon Monoxide Alarms and Carbon Monoxide Detection Systems.
(Add) 29.3.4.6.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with §§ 9.12 and 29.3.4.6 shall be provided in hotels and dormitories where either of the following conditions exists:
(Add) 29.3.4.6.2 Where required by § 29.3.4.6.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations:
(Add) 29.3.4.6.3 Carbon monoxide alarms and carbon monoxide detectors as specified in § 29.3.4.6.1(1) shall not be required in the following locations:
(Add) 29.3.4.6.5 Carbon monoxide alarms or carbon monoxide detectors shall be installed in accordance with the manufacturer’s published instructions in the locations specified as follows:
2. Centrally located within occupiable spaces adjacent to a communicating attached garage
(Add) 29.3.4.7 Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 29.3.5.2.
Every existing hotel and/or dormitory occupancy built, or converted to this occupancy, on or after June 29, 1990, and all existing hotels and/or dormitories of construction types III, IV and V, as outlined in NFPA 220, which have sleeping accommodations for guests or employees above the third story in height, shall be protected throughout by an approved automatic sprinkler system in accordance with § 29.3.5.3.
(Amd) 29.3.5.8 Portable fire extinguishers shall be provided in all existing hotel occupancies in accordance with § 9.9 of this Code.
(Amd) 29.4.1.1 High-rise buildings shall comply with §§ 29.3.5.1, 11.8.4 and 11.8.6.
(Add) 29.5.2.3
Any furnace or boiler in the building shall be equipped with an approved remote shutoff switch approved by the AHJ.
Chapter 30 has been adopted with the following changes:
(Amd) 30.3.4.1.1 General. Every apartment building, other than those meeting § 30.3.4.1.2, shall be provided with a fire alarm system in accordance with amended § 9.6 of this Code, except as modified by §§ 30.3.4.2 through 30.3.4.5
(Amd) 30.3.4.1.2 A fire alarm system shall not be required in buildings where each dwelling unit is completely separated from other contiguous dwelling units by fire barriers (see § 8.3) having a fire resistance rating of not less than one (1) hour, and where each dwelling unit has either its own independent exit or its own independent stairway or ramp discharging at grade. However, such exempted buildings shall fully comply with the provisions for smoke and carbon monoxide alarms in accordance with §§ 30.3.4.5 and 30.3.4.6.
(Amd) 30.3.4.2.1 Initiation of the required fire alarm system shall be by all of the following means:
(Res) 30.3.4.3.4
(Add) 30.3.4.3.5.1 Emergency forces notification shall not be required for apartment occupancies containing less than twelve (12) dwelling units between fire barriers (see § 8.3). The above fire barriers shall have a fire resistance rating of not less than two (2) hours.
(Amd) 30.3.4.4 Detection. Where a fire alarm system is required, a fire detection system in accordance with § 9.6.2.11 shall be provided.
(Add) 30.3.4.7 Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Add) 30.3.5.13 Portable fire extinguishers shall be provided in all new apartment occupancies in accordance with § 9.9 of this Code.
(Add) 30.3.5.13.1 As an alternative to the location requirements for portable fire extinguishers outlined in § 9.9 of this Code, the owner or management of a new apartment building may provide each apartment unit with an approved fire extinguisher installed at the direction and to the satisfaction of the AHJ.
(Add) 30.5.2.3 Any furnace or boiler in the building shall be equipped with an approved remote shutoff switch approved by the AHJ.
Chapter 31 has been adopted with the following changes:
(Amd) 31.1.1.1 The requirements of this Chapter shall apply to existing buildings or portions thereof currently occupied as apartment occupancies. In addition, the building shall meet the requirements of one (1) of the following options:
(Add) 31.1.1.5 Approved apartment buildings.
Any existing apartment building, that was originally converted to this occupancy from an existing one (1), two (2), or three (3) family dwelling, shall be deemed in full compliance with the provisions of this Chapter 31, upon meeting the following fifteen (15) requirements on or before January 1, 2013:
15. Every existing apartment building, containing more than six (6) living units between approved fire barriers (see § 8.3) having a fire resistance rating of two (2) hours, built or converted to this occupancy, on or after June 29, 1990 shall be provided with sprinkler coverage, at the direction and to the satisfaction of the AHJ, in accordance with the standards outlined in the referenced editions of NFPA 13 or NFPA 13R where applicable.
(Amd) 31.3.4.2.1 Initiation of the required fire alarm system shall be by all of the following means:
(Res) 31.3.4.3.4
(Add) 31.3.4.3.5.1 Emergency forces notification shall be not required for apartment occupancies containing less than twelve (12) dwelling units between fire barriers (see § 8.3). The above fire barriers shall have a fire resistance rating of not less than two (2) hours.
(Amd) 31.3.4.4.1 Where a fire alarm system is required, a fire detection system in accordance with § 9.6.2.11 shall be provided.
(Res) 31.3.4.4.2
(Amd) 31.3.4.5.1* Smoke alarms shall be installed in accordance with § 9.6.2.10 outside every sleeping area in the immediate vicinity of the bedrooms and on all levels of the dwelling unit, including basements.
(Add) 31.3.4.6.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with §§ 9.12 and 31.3.4.6 shall be provided apartment buildings where either of the following conditions exists:
(Add) 31.3.4.6.2 Where required by § 31.3.4.6.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations:
(Add) 31.3.4.6.3 Carbon monoxide alarms and carbon monoxide detectors as specified in § 31.3.4.6.1(1) shall not be required in the following locations:
(Add) 31.3.4.6.5 Carbon monoxide alarms or carbon monoxide detectors shall be installed in accordance with the manufacturer’s published instructions in the locations specified as follows:
2. Centrally located within occupiable spaces adjacent to a communicating attached garage
(Add) 31.3.4.7 Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 31.3.5.1
Every existing apartment building, containing more than six (6) living units between approved fire barriers (see § 8.3) having a fire resistance rating of not less than two (2) hours, built, or converted to this occupancy, on or after June 29, 1990 shall be protected throughout by an approved automatic sprinkler system in accordance with § 31.3.5.2.
(Amd) 31.3.5.9.3
The workmanship and the materials of the sprinkler installation specified in § 31.3.5.9 shall meet the requirements of § 9.7.
(Amd) 31.3.5.13 Portable fire extinguishers shall be provided in all existing apartment occupancies in accordance with § 9.9 of this Code.
(Amd) 31.3.5.13.1 As an alternative to the location requirements for portable fire extinguishers outlined in § 9.9 of this Code, the owner or management of an existing apartment building may provide each apartment unit with an approved fire extinguisher installed at the direction and to the satisfaction of the AHJ.
(Amd) 31.4.1.1 High-rise buildings shall comply with §§ 31.2.11.1 and 31.3.5.11 and §§ 11.8.4. and 11.8.6.
Chapter 32 has been adopted with the following changes:
(Amd) 32.2.3.4.1 General. Every residential board and care occupancy shall be provided with a fire alarm system in accordance with amended § 9.6 of this Code.
(Add) 32.2.3.4.1.1 Initiation of the required fire alarm system shall be by all of the following means:
3. An approved fire detection system in accordance with § 9.6.2.11.
(Add) 32.2.3.4.1.2 Detection. A fire detection system in accordance with § 9.6.2.11 shall be provided.
(Add) 32.2.3.4.6 Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 32.2.3.5.1 All facilities shall be protected throughout by an approved, automatic sprinkler system installed in accordance with § 32.2.3.5.3 using quick response or residential sprinklers.
(Add) 32.2.5.2.4 Any furnace or boiler in the building shall be equipped with an approved remote shutoff switch approved by the AHJ.
(Amd) 32.3.3.4.8Detection.
(Amd) 32.3.3.4.8.1 A fire detection system in accordance with § 9.6.2.11 shall be provided.
(Add) 32.3.3.4.10 Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
Chapter 33 has been adopted with the following changes:
(Amd) 33.2.3.4.1 General. Every residential board and care occupancy shall be provided with a fire alarm system in accordance with amended § 9.6 of this Code.
(Amd) 33.2.3.4.1.1 Initiation of the required fire alarm system shall be by all of the following means:
(Res) 33.2.3.4.1.2
(Add) 33.2.3.4.2.1 Detection. A fire detection system in accordance with § 9.6.2.11 shall be provided.
(Add) 33.2.3.4.5Carbon Monoxide Alarms and Carbon Monoxide Detection Systems.
(Add) 33.2.3.4.5.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with §§ 9.12 and 33.2.3.4.5.2 shall be provided residential board and care occupancies where either of the following conditions exists:
(Add) 33.2.3.4.5.2 Where required by § 33.2.3.4.5.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations:
(Add) 33.2.3.4.5.3 Carbon monoxide alarms and carbon monoxide detectors as specified in § 32.2.3.4.5.1(1) shall not be required in the following locations:
(Add) 33.2.3.4.5.5 Carbon monoxide alarms or carbon monoxide detectors shall be installed in accordance with the manufacturer’s published instructions in the locations specified as follows:
2. Centrally located within occupiable spaces adjacent to a communicating attached garage
(Add) 33.2.3.4.6 Any conflict between the provisions of this Section and the provisions of amended § 9.6 of this shall be resolved in favor of compliance with the most reasonable combined requirements as determined by the State Fire Marshal’s Office.
(Amd) 33.2.3.5.1 All facilities shall be protected throughout by an approved, automatic sprinkler system installed in accordance with § 33.2.3.5.3 using quick response or residential sprinklers.
(Add) 33.2.5.2.4 Any furnace or boiler in the building shall be equipped with an approved remote shutoff switch approved by the AHJ.
(Amd) 33.3.3.4.2 Initiation. The required fire alarm system shall be initiated by each of the following means:
4. Required detection system, other than sleeping room smoke alarms
(Amd) 33.3.3.4.6.1 Emergency forces notification shall be accomplished in accordance with § 9.6.4.
(Amd) 33.3.3.4.8.1 A fire detection system in accordance with § 9.6.2.11 shall be provided.
(Res) 33.3.3.4.8.2
(Add) 33.3.3.4.9Carbon Monoxide Alarms and Carbon Monoxide Detection Systems.
(Add) 33.3.3.4.9.1 Carbon monoxide alarms or carbon monoxide detectors in accordance with §§ 9.12 and 33.3.3.4.9.2 shall be provided residential board and care occupancies where either of the following conditions exists:
(Add) 33.3.3.4.9.2 Where required by § 33.3.3.4.9.1, carbon monoxide alarms or carbon monoxide detectors shall be installed in the following locations:
(Add) 33.3.3.4.9.3 Carbon monoxide alarms and carbon monoxide detectors as specified in § 33.3.3.4.9.1(1) shall not be required in the following locations:
(Add) 33.3.3.4.9.5 Carbon monoxide alarms or carbon monoxide detectors shall be installed in accordance with the manufacturer’s published instructions in the locations specified as follows:
3. Centrally located within occupiable spaces adjacent to a communicating attached garage
(Add) 33.3.3.5.1 All facilities shall be protected throughout by an approved, supervised automatic sprinkler system installed in accordance with § 9.7, as modified by §§ 33.3.3.5.1.1 and 33.3.3.5.1.2.
(Amd) 36.3.4.1 General
All Class A mercantile occupancies, all Class B mercantile occupancies occupying more than three thousand (3,000) square feet per floor for sales purposes, and all mercantile occupancies requiring sprinkler coverage, under this Code or the State Building Code, shall be provided with a fire alarm system in accordance with § 9.6
(Amd) 36.3.4.2 Initiation
Initiation of the required fire alarm system shall be by all of the following means:
(Amd) 36.3.4.3.1 Occupant Notification
The required fire alarm system, once initiated, shall perform one of the following functions:
(Amd) 36.3.4.3.2 Emergency Forces Notification
Emergency forces notification shall be provided for all Class A mercantile occupancies and all Class B mercantile exceeding twelve thousand (12,000) gross square feet and shall include notifying both of the following:
(Add) 36.3.4.4.1 Where a fire alarm system is required, a fire detection system in accordance with § 9.6.2.11 shall be provided.
(Amd) 36.3.5.2 Automatic sprinkler systems, where required by either this Code or the Rhode Island Building Code, in either Class A or Class B mercantile occupancies shall be supervised in accordance with § 9.7.2.
(Amd) 36.4.4.7.2 Initiation
Initiation of the required fire alarm system shall be by all of the following means:
(Amd) 36.4.4.7.3.1 Occupant Notification
The required fire alarm system, once initiated, shall perform one of the following functions:
(Amd) 36.4.5.4.2 Initiation
Initiation of the required fire alarm system shall be by all of the following means:
(Amd) 36.4.5.4.3 Occupant Notification
The required fire alarm system, once initiated, shall activate an alarm in accordance with § 9.6.3 throughout the mercantile occupancy, and positive alarm sequence in accordance with § 9.6.3.4 shall be permitted.
(Amd) 37.3.4.1 General
All Class A mercantile occupancies, all Class B mercantile occupancies occupying more than three thousand (3,000) square feet per floor for sales purposes, and all mercantile occupancies requiring sprinkler coverage, under this Code or the State Building Code, shall be provided with a fire alarm system in accordance with § 9.6.
(Amd) 37.3.4.2 Initiation
Initiation of the required fire alarm system shall be by all of the following means:
(Amd) 37.3.4.3.1 Occupant Notification
The required fire alarm system, once initiated, shall perform one (1) of the following functions:
1. It shall activate an alarm in accordance with § 9.6.3 throughout the mercantile occupancy, and both of the following also shall apply:
(Amd) 37.3.4.3.2 Emergency Forces Notification
Emergency forces notification shall be provided for all Class A mercantile occupancies and all Class B mercantile exceeding twelve thousand (12,000) gross square feet and shall include notifying both of the following:
(Amd) 37.3.5.1 Extinguishing Requirements
4. Throughout multiple occupancies protected as mixed occupancies in accordance with § 6.1.14 where the conditions of §§ 37.3.5.1(1), (2), or (3) apply to the mercantile occupancy.
(Amd) 37.3.5.2 The provisions of § 37.3.5.1(2) shall not apply to existing mercantile occupancies with a total gross area less than twelve thousand (12,000) square feet (1115 m2).
Mercantile occupancies shall be protected by an approved automatic sprinkler system in accordance with § 9.7.1.1(1) in any of the following locations:
(Add) 37.3.5.4
Automatic sprinkler systems, where required by either this Code or the Rhode Island Building Code, in either Class A or Class B mercantile occupancies, shall be supervised in accordance with § 9.7.2.
(Amd) 37.4.2 High-Rise Buildings. High-rise buildings shall comply with §§ 11.8.4 and 11.8.6.
(Amd) 37.4.4.7.2 Initiation
Initiation of the required fire alarm system shall be by all of the following means:
(Amd) 37.4.4.7.3.1 Occupant Notification
The required fire alarm system, once initiated, shall perform one (1) of the following functions:
(Amd) 37.4.5.4.2 Initiation.
Initiation of the required fire alarm system shall be by all of the following means:
(Amd) 37.4.5.4.3 Occupant Notification
The required fire alarm system, once initiated, shall perform one (1) of the following functions:
(Amd) 38.3.4.1 General
4. All business occupancies in which sprinkler coverage is required by either this Code or the Rhode Island Building Code.
(Amd) 38.3.4.2 Initiation. Initiation of the required fire alarm system shall be by all of the following means:
A fire alarm system in accordance with § 9.6 shall be provided in all business occupancies where any one (1) of the following conditions exists:
(Amd) 38.3.4.3 Occupant Notification
The required fire alarm system, once initiated, shall activate a general alarm in accordance with § 9.6.3 throughout the building, and positive alarm sequence in accordance with § 9.6.3.4 shall be permitted.
(Add) 38.3.5.1
All new business occupancies shall be protected by an approved automatic sprinkler system in accordance with § 9.7.1.1(1) in any of the following locations:
(Add) 38.3.5.2
Automatic sprinkler systems, where required by either this Code or the Rhode Island Building Code, in new business occupancies shall be supervised in accordance with § 9.7.2.
(Amd) 39.3.4.1 General
4. All business occupancies in which sprinkler coverage is required by either this Code of the Rhode Island Building Code.
(Amd) 39.3.4.2 Initiation. Initiation of the required fire alarm system shall be by all of the following means:
A fire alarm system in accordance with § 9.6 shall be provided in all business occupancies where any one of the following conditions exists:
(Amd) 39.3.4.3 Occupant Notification
The required fire alarm system, once initiated, shall activate a general alarm in accordance with § 9.6.3 throughout the building, and positive alarm sequence in accordance with § 9.6.3.4 shall be permitted.
(Amd) 39.3.4.4 Emergency Forces Notification
Where a fire alarm is required by this Chapter, emergency forces notification shall be provided and shall include notifying both of the following:
(Add) 39.3.5.1
All existing business occupancies shall be protected by an approved automatic sprinkler system in accordance with § 9.7.1.1(1) in any of the following locations:
(Add) 39.3.5.2
The provisions of § 39.3.5.1 shall not apply to existing business occupancies with a total gross area less than twelve thousand (12,000) square feet (1115 m2).
(Add) 39.3.5.3
Automatic sprinkler systems, where required by either this Code or the Rhode Island Building Code, in existing business occupancies shall be supervised in accordance with § 9.7.2.
(Amd) 40.3.4.1 General
A fire alarm system in accordance with § 9.6 shall be provided in all industrial occupancies where any one (1) of the following conditions exists:
(Amd) 40.3.4.2 Initiation.
Initiation of the required fire alarm system shall be by all of the following means:
(Amd) 40.3.4.3.1 Occupant Notification
The required fire alarm system, once initiated, shall activate a general alarm in accordance with § 9.6.3 throughout the building,
(Add) 40.3.4.3.5 Emergency Forces Notification
In buildings where a fire alarm is required, emergency forces notification shall be provided in buildings greater than thirty thousand (30,000) gross square feet in area and shall include both of the following:
(Amd) 42.3.4.1.1
Low hazard storage occupancies, and the specific non-residential farm buildings listed below, shall not be required to have a fire alarm system:
(Amd) 42.3.4.1.2
Storage occupancies with ordinary or high hazard contents not exceeding an aggregate floor area of ten thousand (10,000) square feet (930 m2) shall not be required to have a fire alarm system.
(Res) 42.3.4.1.3
(Amd) 42.3.4.2 Initiation. Initiation of the required fire alarm system shall be by all of the following means:
(Amd) 42.3.4.3 Occupant Notification
The required fire alarm system shall meet one (1) of the following criteria:
(Add) 42.3.4.4 Emergency Forces Notification
Where a fire alarm is required, emergency forces notification shall be provided in buildings greater than thirty thousand (30,000) gross square feet in area and shall include both of the following:
(Add) 44.1
In any building where a fire alarm system is exempted due to the minimum occupant load provisions or the minimum square footage provisions of Chapters 12 through 43, a fire alarm system as prescribed in § 9.6 may be required by the State Fire Marshal where it is proven that life safety of the occupants is compromised due to the hazard of contents, proximity of exposures, limitations to fire department vehicle access or other such hazardous conditions.
Annex A has been adopted with no changes subject to those indicated within the body of the code sections above [16.3.4.6 and 17.3.4.6].
Annex B has been adopted with no changes.
Annex C has been adopted with no changes.
Annex D has been adopted with no changes.