250-RICR-150-10-6
C. The improper location, design, construction, operation and maintenance of OWTSs may have the following harmful effects:
G. Cesspools are not an approved method of wastewater disposal under these Rules, and all existing cesspools are considered to be substandard.
A. As used in these Rules, the following terms shall, where the context permits, be construed as follows:
10. “Bedroom” means any room in a residential structure which is greater than seventy (70) square feet in area, which is susceptible to present or future use as a private sleeping area and which satisfies all of the following requirements:
30. “Failed OWTS” means any OWTS that does not adequately treat and disperse wastewater so as to create a public or private nuisance or threat to public health or environmental quality, as evidenced by, but not limited to, one (1) or more of the following conditions:
38. “Freshwater wetland” means, consistent with R.I. Gen. Laws § 2-1-20(8), except as specified in R.I. Gen. Laws § 2-1-22(k), and includes, but is not limited to:
45. “Large onsite wastewater treatment system” means an OWTS that meets any of the following:
49. "LPP" means low pressure pipe:
82. “Transfer” means a transfer of real property except between the following relationships:
D. No person shall utilize an OWTS permitted under these Rules:
A. Class I Designer's License – A Class I License authorizes the design of a repair to an OWTS, or any component thereof, provided that the repaired OWTS meets one (1) of the criteria below:
B. Class II Designer's License – A Class II License authorizes the design of the following:
1. The design of an OWTS repair or OWTS for an alteration to a structure as defined in § 6.18 of this Part, provided that the OWTS meets one (1) of the criteria below:
2. The design of an OWTS for new building construction as defined in § 6.18 of this Part, provided that the OWTS meets one (1) of the criteria in §§ 6.10(B)(1)(a) through (d) of this Part and the OWTS is on a lot that does not require a variance from any of the following provisions of the Rules:
A. Class I, II, or IV License
2. Minimum Qualifications – In order to qualify for an examination, the applicant must demonstrate to the Department with appropriate documentation that the minimum qualifications below are met for the respective examination:
c. Class IV
(1) The minimum qualifications for the Class IV exam shall be satisfied by meeting any one (1) of the following:
3. Examination Descriptions
a. The examination for a Class I Designer's License shall be a written examination that, at minimum, addresses the following:
b. The examination for a Class II Designer's License shall, at minimum, address the following:
c. The examination for a Class IV License shall have a written and field component, each of which shall be graded separately. The written and field examinations for Class IV do not have to be passed concurrently. However, if more than three (3) years elapse after the applicant passes one (1) of the components of the examination, the applicant must retake that portion of the examination originally passed more than three (3) years earlier. The Class IV License examination shall at minimum address the following:
B. Class III License
2. A Class III designers license shall be issued provided that:
B. Renewal Prior to Expiration – A license issued pursuant to this Rule may be renewed provided that:
B. Denial, Suspension, or Revocation of License – The Director may deny, suspend or revoke a license if the individual has failed to comply with the requirements in these Rules or where the individual:
D. Denial of License Renewal – The Director may deny the renewal of a license if the individual has failed to comply with the requirements in these Rules or where the individual:
E. Review Panel – The Director shall appoint a Review Panel which shall consist of five (5) members, at least three (3) of whom shall be licensed under this Rule and not be employed by the Director. Members of the Review Panel shall be appointed for a two (2) to five (5) year term. The Director may appoint new members to serve out the remaining time of those members who leave the Review Panel before the end of their term. The Director may also limit the number of terms an individual can serve. The Review Panel shall conduct regular meetings as needed, but shall meet not less than once every six (6) months. The Review Panel shall have the authority to:
G. Complaint Review – The procedure for Departmental review of complaints regarding Licensed Designers or Soil Evaluators is described below. At any time during the review of the complaint, the Director may request an informal meeting with the licensee to discuss the complaint.
B. Obtaining an Installer’s License
C. Expiration, Renewal, and Reinstatement of Installer’s Licenses
D. Denial, Suspension and Revocation of Installer’s Licenses
1. The Director may deny, suspend or revoke an Installer’s License if the individual has failed to comply with the requirements in these Rules or where the individual:
E. Connection to a Public Wastewater System – An OWTS application shall not be approved if such OWTS is proposed to serve a premises for which a public wastewater system is reasonably accessible as determined by the Director, and for which permission to enter the public wastewater system can be obtained from the authority having jurisdiction. The Director shall require the owner or occupant to connect the structure to a public wastewater system within a specified period of time if the following occur:
B. Validity of Field Data – Field data shall be considered valid for a period of five (5) years from the time of initial certification by the Department or five (5) years from the date of initial approval of any OWTS application, design, or subdivision suitability where the data were used, whichever occurred most recently. Field data older than five (5) years may be used provided that §§ 6.16(B)(1) through (3) of this Part are met. Field data cannot be renewed independent of an OWTS application or subdivision site suitability certification application.
C. Soil Evaluation Requirements – The soil evaluation shall be prepared on forms approved by the Director. The soil evaluation shall contain a site sketch and the information in §§ 6.16(C)(1) through (6) of this Part. The information in §§ 6.16(C)(1) and (2) of this Part shall be completed by a Soil Evaluator, and may be required to be witnessed by the Director in accordance with § 6.16(E) of this Part. The information in items §§ 6.16(C)(3) through (6) of this Part shall be determined by a Class II or III Licensed Designer or a Soil Evaluator. The test holes excavated for the soil evaluation shall be within the area of the proposed leachfield as described in § 6.16(I) of this Part.
E. Soil Evaluation Witnessed by the Department
3. The Soil Evaluator shall complete the soil evaluation form prior to the arrival of the Director onsite for the scheduled appointment with the Department. While in the field, the Director shall determine which of the following apply:
c. The Director does not concur with the soil evaluation. If soil conditions are in dispute, the Department, upon request of the Soil Evaluator, shall provide an additional field review in an effort to resolve the dispute.
F. Soil Evaluation Not Witnessed by the Department – If the Director determines that the Department need not witness the soil evaluation, the Licensed Designer or Soil Evaluator shall notify the Department during normal business hours by telephone of the date and time of the soil evaluation at least twenty-four (24) hours prior to conducting the soil evaluation. The Department, at its discretion, may make unannounced inspections of any soil evaluation. The soil evaluation form shall be submitted to the Director prior to the submission of the application for an OWTS permit and within ninety (90) days of the day the soil evaluation was conducted.
2. After review of the soil evaluation, the Director shall either:
I. Test Hole Requirements
J. Soil Class – The information collected from the test hole shall be used to assign the soil to one (1) of the soil classes below, except for Class G soils in which case the soil class for the substratum shall also be indicated.
L. Soil Category
| Soil Category | Loading Rate (gals/sq ft/day)Pursuant to § 6.33(B) of this PartStarred items (*) are for soils with coarse fragment modifiers | Soil Texture | Soil Structure | Soil Consistence | Typical Soil Class | |
| Consistence In-Hand Using Soil Clods | Excavation Difficulty | |||||
| 1 | .70 | cos, s, lcos, ls, cosl, fs | structureless- single grain subangular blocky | loose friable | N/A | Outwash (Class C), ice contact (Class D) and coarse ablation till (Class B) deposits |
| .61* | ||||||
| 2 | .61 | vfs, lvfs | structureless- single grain | Loose | N/A | Outwash (Class C) and ice contact (Class D) deposits |
| 3 | .70 | ls, sl, l | granular, subangular blocky | very friable to friable | low | Lodgement Till (Class A), Ablation Till (Class B), Outwash (Class C), or Ice Contact (Class D) |
| 4 | .61 | lfs, lvfs, fsl, vfs | granular, subangular blocky | very friable to friable | low | Lodgement Till (Class A), Ablation Till (Class B), Outwash (Class C), or Ice Contact (Class D) |
| .70* | ||||||
| 5 | .52 | sil, si, vfsl | subangular blocky | very friable to friable | low | Typically Eolian deposits (Class G) |
| 6 | .61 | lcos, cosl, lfs, ls, sl, l | structureless massive | very friable to friable | low | Ablation till (Class B) |
| .70* | ||||||
| 7 | .52 | fsl, vfsl, sil, si, vfs | structureless- massive | very friable to friable | low to moderate | Ablation till (Class B) |
| .61* | ||||||
| 8 | .46 | all textures | structureless-massive | firm to very firm | moderate | Lodgement till (Class A) |
| .48* | ||||||
| 9 | .40 | all textures | platy, structureless- massive | firm to very firm | high | Lodgement till (Class A) |
| .43* | ||||||
| 10 | Not Allowed (Impervious) | all textures | platy, structureless- massive | extremely firm | very high to extremely high | Lodgement till (Class A) |
M. Determination of Seasonal High Groundwater Table
1. The Soil Evaluator shall use the depth to, type, location and abundance of hydromorphic features and other characteristics to determine the depth to the seasonal high groundwater table. The depth to the seasonal high groundwater table shall be measured from the original ground surface. The criteria to use in evaluating hydromorphic features include, but are not limited to, the following:
4. Wet Season Determinations – Determination of the seasonal high groundwater table during the wet season shall be made by a Class II or III Licensed Designer, or a Soil Evaluator January 1 through April 1.
B. Determination of Depth to Bedrock
1. Bedrock test holes, conducted in accordance with § 6.17(B)(2) of this Part, shall be required when any of the following occur:
2. Bedrock test holes
a. Bedrock test holes shall be excavated to a depth of ten feet (10’) in the center and four (4) corners of the proposed leachfield. Additional test holes or probe tests shall be required within twenty-five feet (25’) of the proposed leachfield, the number and location depending on the site. Bedrock depth shall be determined on all sides of the proposed leachfield. In order for DEM approval, testing must demonstrate that:
D. OWTS Suitability Determination – An OWTS Suitability Determination is a determination as to whether or not an existing OWTS is suitable for a proposed building construction, renovation or change of use so as to protect public health and the environment. For OWTS with no available records, a Class II or Class III Licensed Designer may prepare an engineering analysis that must show the OWTS complies with current Rules. An OWTS Suitability Determination Application may be submitted to the Department in order to determine the applicability of this Rule. OWTS suitability is determined by the following:
1. Excluding holding tanks, for OWTSs where all components have been installed with State approval on or after April 9, 1968:
a. The OWTS is suitable and no application to the Department is necessary for any building construction, renovation or change in use, that, for residential uses, does not result in an increase in the number of bedrooms in a residential structure beyond the number in the original State approval; or, for all other uses, an increase in the wastewater flow greater than the OWTS approved design flow for any OWTS. However, the OWTS is unsuitable and an OWTS Application for New Building Construction or an OWTS Application for Alteration to a Structure, whichever is applicable, must be submitted when any of the following in §§ 6.18(D)(1)(a)((1)) through ((3)) of this Part apply, even if there is no increase in number of bedrooms or increase in flow:
b. The OWTS is unsuitable if the OWTS is located within the Salt Pond or Narrow River Critical Resource Areas, includes any existing components permitted and installed prior to February 6, 2002, and does not utilize nitrogen reducing technology in accordance with § 6.43(B) of this Part at the time of application and the applicant proposes building construction or renovation meeting any of the conditions listed below in §§ 6.18(D)(1)(b)((1)) and ((2)) of this Part. In-kind (i.e. same number of bedrooms) replacement of mobile homes in a licensed mobile and manufactured home park is exempt from § 6.18(D)(1)(b) of this Part.
2. For OWTSs where any existing components have been installed without State approval, holding tanks, cesspools, and OWTSs installed prior to April 9, 1968: Whenever a person proposes any building construction, renovation, or change of use (as defined in § 6.8 of this Part) of a structure served by such an OWTS, the OWTS is unsuitable and shall be upgraded to the standards herein. An OWTS Application for New Building Construction or an OWTS Application for Alteration to a Structure shall be required in accordance with §§ 6.18(E) or (F) of this Part, respectively, whichever is applicable. For the purposes of this Rule, the terms "building construction” and “building renovation" shall be defined as any addition, replacement, demolition and reconstruction, or modification of a structure on the subject property which:
3. Imminent Sewer Exemption – An owner subject to the requirements of §§ 6.18(D)(1)(a)((1)) through ((3)), § 6.18(D)(1)(b), § 6.18(D)(1)(c), or § 6.18(D)(2) of this Part whose property is proposed to be served by a public wastewater system in the future shall be exempt from those requirements, provided an OWTS Suitability Determination Form is submitted to the local building official demonstrating that all of the conditions in §§ 6.18(D)(3)(a) and (b) of this Part are met. A copy of the completed form shall be provided to the Department. In order to claim exemption, the owner must:
b. Certify that:
E. OWTS Application for New Building Construction – All OWTS Applications for New Building Construction shall be made in conformance with all requirements under these Rules. Applications not in conformance with these Rules may be approved only through the variance procedures set forth in § 6.51 of this Part.
1. An OWTS Application for New Building Construction shall be made whenever an applicant proposes to:
F. OWTS Application for Alteration to a Structure
1. An OWTS Application for Alteration to a Structure shall be made whenever an applicant proposes any physical alteration to a structure that meets any of the following:
G. OWTS Application for Repair – An application for a repair of any OWTS, or any component thereof, shall be made when an OWTS or component has failed, as defined by § 6.8 of this Part. An application for repair shall not propose any change of use, building renovation pursuant to §§ 6.18(D)(2)(a) through (d) of this Part, or any increased flow to the OWTS. The Department may allow an OWTS Application for Repair to be submitted when, after the effective date of these Rules, a fire or other catastrophic occurrence necessitates that a structure served by an OWTS be replaced. The applicant may also submit an OWTS Application for Repair when the property owner desires to upgrade or modernize the OWTS (e.g., replacement of cesspool).
4. Exemptions for OWTS Application for Repair – Under the limited circumstances in §§ 6.18(G)(4)(a) through (e) of this Part, an OWTS Application for Repair will not be necessary prior to repairing the OWTS. Any repair or installation work done in accordance with §§ 6.18(G)(4)(a) through (e) of this Part that is found not to be in compliance with these Rules, will have to be corrected and will be considered a violation of these Rules.
c. Access Openings – The following work on access openings does not require prior authorization of the Department or notification to the Department once the work is completed:
B. Plan – All applications for New Building Construction, Alterations to a Structure, or redesigns of previously approved applications for New Building Construction or Alterations to a Structure, except those submitted under § 6.20(A)(1)(c) of this Part, shall be accompanied by four (4) sets of plans that include a plan view of the entire property drawn to scale, a plan view of the pertinent portion of the property at a minimum scale of one inch (1”) equals forty feet (40’), a profile of the system from the building foundation to the limits of the leachfield with invert elevations shown, and a cross-section of the leachfield. The plans shall include the items below. The Director reserves the right to require any additional information that is deemed necessary. For applications submitted under § 6.20(A)(1)(c) of this Part, six (6) sets of plans must be included.
10. Wells:
C. Additional Information – Other information to be provided by the applicant shall include, but not be limited to, the items listed below:
E. Application for Transfer – Applications for transfer of an approved OWTS application shall include the items listed below.
A. Applications Involving the DEM Freshwater Wetlands Program
1. All applications pursuant to these Rules associated with a construction project which may affect a freshwater wetlands jurisdictional area defined pursuant to Subchapter 15 Part 3 of this Chapter, Rules and Regulations Governing the Administration and Enforcement of the Freshwater Wetlands Act and regulated by the Department shall be submitted in accordance with §§ 6.20(A)(1)(a), (b), or (c) of this Part:
B. Applications Involving the Rhode Island Coastal Resources Management Council
A. Administrative
3. Subdivisions of five (5) lots or less that have frontage on an existing road have the option to apply for a Subdivision Site Suitability Certification pursuant to § 6.21(B) of this Part or submit OWTS applications for individual lots in accordance with § 6.18 of this Part. If applications for individual lots are submitted, the submittal shall be in accordance with the following:
B. Subdivision Site Suitability Certification – Application for Subdivision Site Suitability Certification shall be prepared by a Class II or Class III Licensed Designer, as appropriate, on forms approved by the Director and shall include the information in §§ 6.21(B)(1) through (5) of this Part and any other information the Director may require. The application for Subdivision Site Suitability Certification will be reviewed for all information necessary to determine the suitability of a parcel of land to be divided as shown on the application.
3. Topographic Map
a. The topographic map shall show ground elevations on the tract as follows:
c. The topographic map shall show the following for the entire area of the subdivision:
4. For lands immediately adjacent to the subdivision, the items below shall be shown, designated or reported. Distances below shall be determined from the subdivision property boundary.
C. Expiration of Subdivision Site Suitability Certification
1. Except for permits eligible for tolling pursuant to R.I. Gen. Laws § 42-17.1-2.5 as provided in § 6.21(C)(2) of this Part, a Subdivision Site Suitability Certification shall expire five (5) years from the date of issuance unless the subdivision has been platted or recorded as evidenced by the submission of a copy of the recorded subdivision plat map. After expiration, certification may be obtained only by reapplying under the Rules in effect at the time of re-application. Once a subdivision has been platted or recorded, no further certification shall be required and all lots may proceed with the application process for their OWTS in accordance with these Rules.
A. Determination of Wastewater Flow
2. For establishments not listed in § 6.22(B) of this Part, the maximum daily flow shall be determined by either of the following:
B. Wastewater Design Flows
| TYPE OF USE | UNIT | GALLONS PER DAY |
| RESIDENTIAL[Minimum design flow for residential use shall be three hundred forty-five (345) gallons per day (three (3) bedrooms), unless otherwise permitted in accordance with § 6.22(D) of this Part.] | ||
| Single family residence | per bedroom (2 persons per bedroom) | 115 |
| Multiple family residence | per bedroom (2 persons per bedroom) | 115 |
| INSTITUTIONAL | ||
| Assisted living facility | per bedroom (2 persons per bedroom) | 115 |
| Church | per seat | 1 |
| Church hall (fellowship hall) | per seat | 5 |
| Hospital | per bed | 150 |
| Library | per visitor | 5 |
| Nursing home/rest home | per bed | 125 |
| Group home | per bed | 200 |
| Correctional, rehabilitation facility | per bed | 100 |
| Gymnasium | per seat | 3 |
| Gymnasium | per participant | 15 |
| Highway rest stop | per person | 5 |
| Public park with toilets | per person | 5 |
| add for showers | per person | 10 |
| CAMPS AND CAMPGROUNDS | ||
| Day camp | per person | 15 |
| add for mess hall | per person/meal | 3 |
| Camp – overnight | per person | 25 |
| add for mess hall | per person/meal | 3 |
| Campground with washroom and toilets | per site | 50 |
| Recreational vehicle park with water service | per site | 100 |
| Add for central dining facilities | per seat | 35 |
| Recreational vehicle park without water service | per site | 50 |
| Add for central dining facilities | per seat | 35 |
| Add for central washroom and toilet facilities | per site | 50 |
| SCHOOLS | ||
| School | per person | 10 |
| add for cafeteria | per person | 5 |
| add for gymnasium and showers | per person | 10 |
| Boarding school, college | per person | 50 |
| Day care center | per person | 10 |
| RESTAURANTS[Minimum design flow for restaurants shall be 500 gallons per day.] | ||
| Restaurant | per seat | 40 |
| Restaurant – with single-service articles | ||
| with public restrooms | per seat | 25 |
| without public restrooms | per seat | 20 |
| add for drive-up window | 500 | |
| Lounge, bar (no food service at that seat) | per seat | 10 |
| Banquet hall | per seat | 5 |
| Ice cream parlor, take out service only | per store | 500 |
| COMMERCIAL[Minimum design flow for commercial use shall be 100 gallons per day] | ||
| Auto service station | per pump | 25 |
| per repair bay | 100 | |
| Barber shop/Beauty salon | per chair | 50 |
| add for sink | per hair care sink | 200 |
| Bed & Breakfast | per bedroom | 110 |
| Bowling alley | per alley | 100 |
| Catering kitchen, no food service on-site | per meal prepared | 3 |
| Country club | ||
| dining room | per seat | 40 |
| snack bar/lounge | per seat | 20 |
| lockers and showers | per locker | 20 |
| Doctors /Chiropractor/ Therapist office | per doctor/chiropractor/therapist | 250 |
| Dog/Pet grooming | per station | 500 |
| Dentist office | per chair | 200 |
| Drive-in theater | per vehicle stall | 5 |
| Factory/Industrial plant | per person | 15 |
| add for cafeteria | per person | 5 |
| Food store < 5,000 square feet (See Note 1) | per store | 350 |
| add for deli flow | per store | 100 |
| add for bakery flow | per store | 100 |
| add for meat dept. flow | per store | 150 |
| add for fish market flow | per store | 150 |
| add for public restrooms | per store | 200 |
| Food store > 5,000 square feet (See Note 1) | per store | 700 |
| add | per square foot > 5,000 sq ft | 0.05 |
| add for deli flow | per store | 200 |
| add for bakery flow | per store | 200 |
| add for meat dept. flow | per store | 300 |
| add for fish market flow | per store | 300 |
| add for public restrooms | per store | 400 |
| Funeral home | per parlor | 500 |
| Hotel, motel | per unit | 100 |
| With efficiency units | per unit | 150 |
| Health club | per participant | 15 |
| Kennel | per kennel | 10 |
| Marina (shore-side facilities) | per slip | 10 |
| add for showers | per slip | 10 |
| Mobile home park/Manufactured home park | per site | 230 |
| Office building | per employee | 15 |
| Retail store | per employee | 15 |
| Rooming house/Boarding house | per bedroom | 80 |
| Self-Service Laundry (See Note 2) | per machine | 500 |
| Shopping center/Strip mall/Multi-use retailCalculate on the largest of either:a) The total flow for the uses within as determined from this table, orb) Per square foot | per square foot | 0.1 |
| Skating rink | per seat | 3 |
| Swimming pool | per person | 15 |
| Tennis court – outdoor | per court | 100 |
| Tennis court – indoor | per court | 400 |
| Theater, auditorium | per seat | 3 |
| Veterinary office | per veterinarian | 200 |
| Notes:(1)The design flow for a stand alone deli, bakery, meat store or fish market will be three hundred fifty (350) gallons per day if the facility is less than five thousand (5,000) square feet or seven hundred (700) gallons per day if the facility is five thousand (5,000) square feet or more.(2) Self-Service laundry OWTS designs must include pretreatment to remove lint from the wastewater. |
C. Determining the Number of Bedrooms in a Single Family Residential Dwelling – For purposes of aiding the planning, designing, building, renovation, remodeling or expansion of residential dwellings, the following guidelines shall be used in determining the number of bedrooms. These guidelines are presented in acknowledgement that, in many cases, houses contain rooms meeting the strict definition of bedroom as defined in these Rules, but which are not intended to be nor will be used as bedrooms.
D. Determination of Number of Bedrooms
| Total Number of Rooms | Assumed Number of Bedrooms |
| 5 or less | 2 |
| 6-7 | 3 |
| 8-10 | 4 |
| 11-12 | 5 |
| 13 or more | 6 |
B. Minimum Setback Distances – General
| Building Sewer, Grease Tank, Distribution Box, Pump Tank, Septic Tank, Septic Tank Effluent Pipe (ft) (Note 12) | Leachfield (ft) (Note 12) | ||
| Well Serving Non-potable Uses (Note 13) | 25 | 50 | ||
| Water Supply Line | 10 (Note 1) | 25 | ||
| Property Line | 10 (Note 2) | Design Flow (gpd) | (ft) | |
| 0 – 2000 | 10 | |||
| >2000 – 5000 (Note 3) | 50 | |||
| > 5000(Note 4) | min. 50 (Note 5) | |||
| Foundation | 5 (Not applicable to building sewer) | 25 (Note 6) | ||
| Subsurface drains, foundation drains, or storm drains (see also §§ 6.23(C) and (D) of this Part): – Upgradient and side gradient of the OWTS: – Downgradient of the OWTS: | 15 (Note 7) 25 (Note 7) | 25 (Note 8) 50 (Note 9) | ||
| Edge of any land at a level lower than the invert of the distribution line | 10 | 10 | ||
| Stormwater Infiltration System | 25 (Note 10) | 25 (Note 10) | ||
| Swimming Pools:In-ground: Above ground: | 10 10 | 25 10 | ||
| Design Flow <5000 gpd | Design Flow = 5000 gpd (Note 4) | Design Flow < 5000 gpd | Design Flow = 5000 gpd (Note 4) | |
| Coastal Shoreline Feature (Note 11) not in a Critical Resource Area, Flowing Water (Rivers and Streams), Open Bodies of Water (Lakes and Ponds), Other Watercourses Not Mentioned Above, and Any Stormwater Management Structure That Potentially Intercepts Groundwater | 25 | 50 | 50 | 100 |
| Notes: The reductions in setback distances allowed below in Notes (1) through (13) will not be granted if the setback distances in § 6.23(B) of this Part can be met. A variance request pursuant to § 6.51 of this Part shall not be required for the reductions indicated below.(1) The distance between the building sewer or septic tank effluent pipe and a water supply line may be reduced and the lines may cross provided that either the building sewer or septic tank effluent pipe or water supply line is sleeved whenever the lines are within ten feet (10’) of each other. The sleeve shall be seamless or schedule 40 PVC or equivalent with watertight joints and it shall have a watertight seal that is fastened to the pipes with a stainless steel retractable clamp. Whenever possible, the building sewer and septic tank effluent pipe should be laid below water supply lines at crossings. Pressurized building sewers or pressurized septic tank effluent pipes shall be laid below water supply lines at crossings. If the setbacks to a water supply line for a public water system cannot be met, the applicant must obtain, and submit to the Department, written permission from the water supplier.(2) Not applicable to building sewer and septic tank effluent pipe. Setback distance of ten feet (10’) applies for all OWTS components not specifically listed.(3) Any single leachfield designed to treat more than two thousand (2,000) but less than five thousand (5,000) gallons per day.(4) As defined in § 6.39(A)(1) of this Part.(5) Distance shown is the minimum for upgradient and side gradient directions. Downgradient separation distance will be based on nitrate modeling undertaken pursuant to § 6.39 of this Part and shall be a minimum of fifty feet (50’).(6) Distance may be reduced to fifteen feet (15’) with no foundation drain. Full foundation details must be shown on the plan. Distance may be reduced to eight feet (8’) where a foundation slab elevation, pile foundation, or the basement floor elevation is higher than the invert of the distribution lines in the leachfield.(7) The distance between the building sewer or septic tank effluent pipe and a drain may be reduced and the building sewer or effluent pipe may cross the drain provided that the building sewer or septic tank effluent pipe is sleeved whenever they are within twenty-five feet (25’) of the drain. The sleeve shall be seamless or schedule 40 PVC or equivalent with watertight joints, and it shall have a watertight seal that is fastened to the pipes with a stainless steel retractable clamp.(8) If the slope of the original land surface over the area of the leachfield and fifty feet (50’) in all directions from the edge of the leachfield is less than three percent (3%), the minimum setback distance between the leachfield and the drain must be fifty feet (50’) in all directions. If the applicant conducts a groundwater flow study that conclusively demonstrates the drain is upgradient of the leachfield, the Director may allow a twenty-five foot (25’) separation distance on the upgradient and side gradient side.(9) If a drain is watertight and bedded in sand or bank run gravel, or laid at an elevation above the seasonal high groundwater table, this setback distance may be reduced to twenty-five feet (25’). Applications shall include a detail drawing of the drain pipe joints and bedding material.(10) On a residential property with both an OWTS and a stormwater infiltration system, the distance between any OWTS component and the stormwater infiltration system may be reduced to fifteen feet (15’) if the stormwater infiltration system has been designed in accordance with the Rhode Island Stormwater Design and Installation Standards Manual.(11) The minimum setback distance from the inland edge of the coastal shoreline feature of the ocean or Narragansett Bay is either fifty feet (50’) or twenty-five feet (25’) plus the CRMC calculated shoreline change setback pursuant to § 1.9 of 650-RICR-20-00-1, Red Book, whichever is greater. Shoreline change rates and maps are available on CRMC’s web site. This setback distance is doubled for OWTSs with design flow greater than five thousand (5,000) gallons per day.(12) The distance between the septic tank and the edge of the leachfield shall be a minimum of ten feet (10’).(13) The minimum setback from a geothermal well and its associated piping shall be twenty-five feet (25’). |
C. Minimum Setback Distances from Drinking Water Supply Watershed Critical Resource Area Features (distances in feet from all OWTS components). See also § 6.60 of this Part, Figure 2. If it is shown to the Department’s satisfaction by clear and convincing evidence that the feature of concern in this table is upgradient (for both groundwater and surface water flow) of the OWTS, the minimum setback distance will be determined from § 6.23(B) of this Part. Subsurface drains to lower the seasonal high groundwater table are not permitted in accordance with § 6.44(B) of this Part.
| Feature | OWTS Design Flow 5000 gpd | OWTS Design Flow 5000 gpd (Note 1) |
| Impoundment with Intake for Drinking Water Supply and Adjacent Freshwater Wetlands (Note 2) | 200 | 400 |
| Subsurface Drains and Foundation Drains that Discharge Directly to the Impoundment | 200 | 400 |
| Subsurface Drains and Foundation Drains that Discharge to a Drainage Swale that Subsequently Discharges to the Impoundment: Paved Swale Unpaved Swale < 200 feet long Unpaved Swale =200 feet long | 200 200 100 | 400 400 200 |
| Tributaries, Tributary Freshwater Wetlands, Swales, and Storm Drains that Discharge Directly to the Impoundment | 100 (Note 3) | 200 (Note 3) |
| Subsurface Drains, Foundation Drains, and Storm Drains that Discharge to Tributaries and Tributary Freshwater Wetlands | 100 (Note 3) | 200 (Note 3) |
| Any other Watercourse in the Drinking Water Supply Watershed (Not Connected to the Impoundment) or Areas Subject to Storm Flowage | 50 | 100 |
| Notes: The reductions in setback distances allowed below in Note (3) will not be granted if the setback distances in § 6.23(C) of this Part can be met. A variance request pursuant to § 6.51 of this Part shall not be required for the reductions indicated below.(1) As defined in § 6.39(A)(1) of this Part.(2) Distances measured from the yearly high water mark.(3) The distance between the building sewer or septic tank effluent pipe and a drain may be reduced and the building sewer or effluent pipe may cross the drain provided that the building sewer or septic tank effluent pipe is sleeved whenever they are within twenty-five feet (25’) of the drain. The sleeve shall be seamless or schedule 40 PVC or equivalent with watertight joints, and it shall have a watertight seal that is fastened to the pipes with a stainless steel retractable clamp. |
D. Minimum Setback Distances from Features in the Salt Pond and Narrow River Critical Resource Area (distances in feet from all OWTS components). See also § 6.61 of this Part, Figure 3. If it is shown to the Department’s satisfaction by clear and convincing evidence that the feature of concern in this table is upgradient (for both groundwater and surface water flow) of the OWTS, the minimum setback distance will be determined from § 6.23(B) of this Part. Applications for an OWTS permit that are approved by DEM are subject to the requirements of CRMC.
| Feature | OWTS Design Flow 5000 gpd | OWTS Design Flow 5000 gpd (Note 1) |
| Salt Pond/Narrow River Coastal Shoreline Features, excluding the ocean | 200 | 400 |
| Subsurface Drains and Foundation Drains that Discharge Directly to the Salt Pond/Narrow River | 200 | 400 |
| Subsurface Drains and Foundation Drains that Discharge to an open Drainage Swale that Subsequently Discharges to the Salt Pond/Narrow River:Paved Swale Unpaved Swale < 200 feet long Unpaved Swale = 200 feet long | 200 200 150 | 400 400 300 |
| Tributaries, Tributary Freshwater Wetlands, Swales, and Storm Drains that Discharge Directly to the Salt Pond/Narrow River | 150 (Note 2) | 300 (Note 2) |
| Subsurface Drains, Foundation Drains, and Storm Drains that Discharge to Tributaries and Tributary Freshwater Wetlands | 150 | 300 |
| Any Other Watercourse in Salt Pond/Narrow River Critical Resource Area (Not Connected to Salt Pond/Narrow River), Areas Subject to Storm Flowage, or the inland edge of the coastal shoreline feature of the ocean. (Note 3) | 50 | 100 |
| Notes: The reductions in setback distances allowed below in Note (2) will not be granted if the setback distances in § 6.23(D) of this Part can be met. A variance request pursuant to § 6.51 of this Part shall not be required for the reductions indicated below.(1) As defined in § 6.39(A)(1) of this Part.(2) The distance between the building sewer or septic tank effluent pipe and a drain may be reduced and the building sewer or effluent pipe may cross the drain provided that the building sewer or septic tank effluent pipe is sleeved whenever they are within twenty-five feet (25’) of the drain. The sleeve shall be seamless or schedule 40 PVC or equivalent with watertight joints, and it shall have a watertight seal that is fastened to the pipes with a stainless steel retractable clamp.(3) The minimum setback distance from the inland edge of the coastal shoreline feature of the ocean is either fifty feet (50’) or twenty-five feet (25’) plus the CRMC calculated shoreline change setback pursuant to § 1.9 of 650-RICR-20-00-1, Red Book, whichever is greater. Shoreline change rates and maps are available on CRMC’s web site. This minimum setback distance is doubled for OWTSs with design flow greater than five thousand (5,000) gallons per day. |
E. Minimum Setback Distances from Drinking Water Wells
| OWTS Design Flow (gpd) | Distance in Feet from Leachfield/Septic Tank Effluent Pipe, Tanks/Building Sewer (Notes 1 and 5) | Distance in Feet from All OWTS Components (Notes 1 and 5) | |
| Private Drinking Water Well (Note 2) | Public Well – Drilled (rock), Driven, or Dug | Public Well – Gravel Packed, Gravel Developed | |
| < 1,000 | 100/75/50 (Notes 3 and 4) | 200 | 400 |
| 1,000 – <2,000 | 150/75/50 | 200 | 400 |
| 2,000 – <5,000 | 200/75/50 | 200 | 400 |
| 5,000 – <10,000 | 300/75/50 | 300 | 400 |
| = 10,000 | 400/75/50 | 400 | 400 |
| Notes: The reductions in setback distances allowed below in Notes (2) and (3) will not be granted if the setback distances in § 6.23(E) of this Part can be met. A variance request pursuant to § 6.51 of this Part shall not be required for the reductions indicated below.(1) Large Systems – These distances are minimum distances for large systems as defined in § 6.39(A)(1) of this Part. Greater distances may be required based on the Impact Analysis in § 6.39(C) of this Part.(2) Distance from the building sewer may be reduced when the building sewer is constructed of Schedule 40 PVC or equivalent.(3) The minimum setback distances to wells on the subject property may be reduced to 80/60/40 (leachfield/tank/building sewer) feet for residential OWTSs on lots ten-thousand (10,000) square feet and larger under the following conditions:(A) The design flow is less than five hundred (500) gallons per day;(B) The OWTS utilizes a Department-approved nitrogen reducing technology;(C) The OWTS discharges to a pressurized shallow narrow drainfield designed in accordance with § 6.37(D) of this Part ; and(D) The OWTS separation distance between the infiltration surface and groundwater is three feet (3’) or greater.(4) The minimum setback distances shall be increased to 150/75/50 (leachfield/tank/building sewer) for OWTSs with a design flow of less than one thousand (1,000) gallons per day if the OWTS is designed for Category 1 soils per § 6.33 of this Part. For such OWTSs utilizing a Department approved nitrogen reducing technology discharging to a bottomless sand filter or pressurized shallow narrow drainfield constructed in accordance with § 6.37(D) of this Part, the minimum setback distances may be 100/75/50 (leachfield/tank/building sewer).(5) In addition to the required setbacks between wells and the proposed OWTS, well setbacks shall also apply between any existing well serving the building for which the OWTS is proposed and any other existing OWTS. Such existing OWTS may require upgrade to meet these Rules. |
C. Monitoring – The effectiveness of subsurface drains used to lower the groundwater table must be demonstrated through one (1) complete wet season, January 1 through April 15, before consideration can be given to an application for an OWTS permit. The Department may allow lesser periods of monitoring if site conditions and wet season conditions warrant.
E. Horizontal Alignment
F. Vertical Alignment
B. Required Use – Grease tanks shall be installed in accordance with the following:
E. Inlet and Outlet – The inlet and outlet shall be as required for septic tanks in § 6.27(F) of this Part. Grease tanks shall be provided with inlet tees and outlet tees. Baffles may be provided as necessary in conjunction with tees to maximize the separation of grease from the wastewater.
B. Septic Tank Capacity
C. Construction and Materials – Septic tanks shall be watertight. They shall be constructed of sound and durable materials not subject to excessive corrosion, decay or frost damage or to cracking or buckling due to settlement or soil pressures. Septic tanks shall be constructed of precast reinforced concrete, fiberglass, polyethylene or other material approved by the Director. In addition to the construction and material standards in §§ 6.27(C)(1) through (3) of this Part, all septic tanks shall meet the physical design standards in the remainder of § 6.27 of this Part.
3. Each septic tank shall be clearly and permanently marked at the inlet end of the tank with:
E. Compartments – All septic tanks shall have two (2) compartments with adequate connection at mid-depth, and all tanks shall meet the following requirements:
F. Inlet and Outlet
G. Inlet and Outlet Tees – Septic tanks shall be provided with an inlet sanitary tee and outlet tees or other non-corroding equivalent device approved by the Director. The inlet and outlet tees shall be minimum SDR 35 PVC solvent welded. The tops of the tees shall extend a minimum of six inches (6”) above the flow line, and shall be left open to provide ventilation. There shall be an air space of at least three inches (3”) between the tops of the tees and the top interior of the tank.
H. Access Openings – A minimum twenty inch (20”) inside diameter access opening shall be located over both the inlet tee and outlet tee. All septic tank openings shall meet the following requirements:
2. Lids on the top of the septic tank (§ 6.64 of this Part, Figure 6) should remain in place where practical. Lids for the openings at finished grade shall prevent unauthorized entry by meeting either of the following:
J. Installation – All septic tanks shall be installed in accordance with the manufacturer’s minimum requirements. In addition, all septic tanks must meet the installation requirements specified in the remainder of these Rules.
K. Septic Tanks in Series – Septic tanks placed in series are allowed provided they meet the following requirements:
L. Performance Testing – All septic tanks and their risers must be certified watertight by the manufacturer or by onsite testing. Onsite testing for septic tank leakage shall be conducted for tanks assembled at the installation site. The Director may require onsite testing on a case-by-case basis. The testing shall be conducted using either:
A. Use
B. Construction – Each holding tank shall:
C. Construction – Each pump tank shall:
A. Required Use – Pumps are required for OWTSs that meet any of the following conditions:
B. Dual Alternating Pumps
1. When a pump is required, dual alternating pumps are required for the following (otherwise a single pump is sufficient):
D. Outlets
E. Distribution Pipes into the Distribution Box
B. Minimum Leaching Area – The minimum leachfield area necessary for dispersal trench and concrete chamber leachfields shall be determined by dividing the maximum daily wastewater flow (design flow) for the facility, as determined from § 6.22 of this Part, by the loading rate established in § 6.33(C) of this Part. Use the lowest loading rate obtained in the manner described below:
C. Loading Rates Determined by Soil Category
| Soil Category | Loading Rate (gals/sq ft/day) |
| 1 (Note 1) | .70 |
| 1m (Note 2) | .61 |
| 2 | .61 |
| 3 | .70 |
| 4 | .61 |
| 4m | .70 |
| 5 | .52 |
| 6 | .61 |
| 6m | .70 |
| 7 | .52 |
| 7m | .61 |
| 8 | .46 |
| 8m | .48 |
| 9 | .40 |
| 9m | .43 |
| 10 | Not Allowed (Impervious) |
| Notes:(1) For OWTS Applications for Repair, a loading rate of .93 may be used for Soil Category 1.(2) “m” Means soil has gravelly or channery coarse fragment modifiers. |
M. Gravel
1. The gravel base material and, where applicable, the gravel between the trenches shall consist of clean sand and gravel free of organic matter and foreign substances. The gravel shall not contain any material larger than three inches (3”) and up to ten percent (10%) may be sized between three quarters of an inch (¾”) and three inches (3”). Gravel shall meet the following criteria:
| Sieve Size | Percent Passing |
| 3/4” | 90% - 100% |
| #4 | 55% - 100% |
| #10 | 40% - 100% |
| #40 | 10% - 50% |
| #100 | 0% - 20% |
| #200 | 0% - 5% |
T. Leachfield Protection
A. Effective Leaching Area – The effective leaching area shall be determined by the depth of stone meeting the requirements of § 6.33(K) of this Part that is placed below the distribution line in the trench and the width of the trench. The effective leaching area of dispersal trenches containing one half of a foot (½’) of stone below the pipe invert shall be the total bottom area. Credit will be allowed for added sidewall absorption area gained by increasing the depth of stone in the trenches. Such credit shall be determined in accordance with § 6.34(B) of this Part which gives the square footage allowed per lineal foot of trench as the depth of stone increases. The maximum depth of stone allowed is one and one half feet (1 ½’). The bottom of the dispersal trench shall have a maximum width of three feet (3’). The maximum depth of stone below the pipe invert shall be one half of a foot (½’) when either of the following occur:
B. Effective Leaching Area
| Depth of Stone Below Invert (Feet) | Area Allowed per Linear Foot of Trench (Sq. ft/ft) | ||
| 24” Wide Trench | 30” Wide Trench | 36” Wide Trench | |
| 0.5 | 2.0 | 2.5 | 3.0 |
| 1.0 | 2.7 | 3.2 | 3.7 |
| 1.5 | 3.2 | 3.7 | 4.2 |
C. Distribution Lines
3. The maximum length of a dispersal trench shall be as follows:
E. Leachfield Construction Where the Invert of the Distribution Lines is Below Original Grade (See § 6.65 of this Part, Figure 7).
F. Leachfield Construction Where the Invert of the Distribution Lines is Above Original Grade. (See § 6.66 of this Part, Figure 8)
G. Leachfield Construction on Sloping Sites – Where the dispersal trenches are to be constructed such that the invert of the distribution lines in the trenches will not all be at the same elevation, the invert of the distribution lines shall be below the original grade, the distribution lines in the trenches shall be laid level, and the leachfield shall be constructed in accordance with the following (See § 6.67 of this Part, Figure 9):
I. Summary of Dispersal Trench Construction Details:
| Maximum length per line without dosing | 50 feet |
| Maximum length per line with tipping distribution box | 75 feet |
| Maximum length per line with pump | 100 feet |
| Minimum diameter of distribution lines | 4 inches |
| Maximum width of dispersal trench bottom | 3 feet |
| Minimum distance between walls of adjacent trenches | 5 feet/10 feet (Note 1) |
| Minimum cover over invert of distribution lines | 1.5 feet |
| Maximum cover over invert of distribution lines | 2.5 feet |
| Note 1: Ten feet (10’) for those OWTSs on sloping sites and for those OWTSs where the invert of the distribution lines is above original grade |
C. Shallow Concrete Chambers
2. Site limitations – Shallow concrete chambers shall not be permitted where any of the following occur:
E. Shallow Concrete Chamber Effective Leaching Area
| Shallow Concrete Chambers | ||
| 12” stone below | 24” stone below (Note 1) | |
| Each end unit (sq. ft.) | 78 | 102 |
| Each Interior Unit (sq. ft.) | 64 | 80 |
| Note 1: Shallow concrete chambers installed with twenty-four inches (24”) of stone below the chamber may be used for OWTS Applications for Repair only. |
F. Deep Concrete Chambers
H. Deep Concrete Chamber Effective Leaching Area
| Deep Concrete Chambers | |
| 12” stone on sides, 12” stone below | |
| Each end unit (sq. ft.) | 98 |
| Each Interior Unit (sq. ft.) | 58 |
I. Concrete Chamber Construction
2. Access – The top of the chamber trench shall have an access opening into a chamber at intervals not greater than fifty feet (50’) that consists of a removable cover of concrete, iron or other durable material. For OWTSs designed to dispose of up to two thousand (2,000) gallons per day and OWTSs that are not located under a paved area, the top of the access opening shall accommodate a riser and shall be brought to within one foot (1’) of the finished grade and properly marked. For OWTSs designed to dispose of greater than two thousand (2,000) gallons per day, commercial OWTSs, and all OWTSs located under paved areas, the access openings shall meet the following requirements:
b. Lids on the top of the concrete chambers should remain in place where practical. Lids for the openings at finished grade shall prevent unauthorized entry by meeting either of the following:
J. Excavation and Construction of a Concrete Chamber Leachfield
K. Effluent Distribution
2. The maximum length of a chamber trench shall be as follows:
A. General design parameters for all pressurized drainfields
B. Common components for all pressurized drainfields
1. General
b. All advanced treatment units to precede pressurized drainfields designed in accordance with §§ 6.36, 6.37, and 6.38 of this Part must fall within one (1) of the following categories:
2. Dosing Tank Specifications
3. Pump, Discharge Assembly and Transport Line Specifications
h. Excavation: Sagging in the transport line shall be prevented by either:
4. Programmable Timer, Controls and Control Panels
a. Timer settings: The timer shall be programmed to provide several small doses of wastewater to the pressurized drainfield throughout a twenty four (24) hour clock time period.
b. Controls
c. Control panel
C. Common Final Installation Steps for all Pressurized Drainfields
D. Operation and Maintenance Requirements for all Pressurized Drainfields
3. Routine Periodic Maintenance
A. General
B. APD Common Design Parameters
4. Hydraulic loading rates for Advanced Pressure Drainfields
| Soil Category | Soil Texture | Soil Structure | Soil Consistence In-Hand Using Soil Clods | Excavation Difficulty | Category 1 Technologies Loading Rate (gal/ft2/day) | Category 2 Technologies Loading Rate (gal/ft2/day) |
| 1 | cos, s, lcos, ls, cosl, fs | structureless- single grain or subangular blocky | loose friable | none | 2.3 | 1.5 |
| 2 | vfs, lvfs | structureless- single grain | loose | none | 2.7 | 1.9 |
| 3 | ls, sl, l | granular, subangular blocky | very friable to friable | low | 3.5 | 2.3 |
| 4 | lfs, lvfs, fsl, vfs | granular, subangular blocky | very friable to friable | low | 3.1 | 2.0 |
| 5 | sil, si, vfsl | subangular blocky | very friable to friable | low | 2.7 | 1.9 |
| 6 | lcos, cosl, lfs, ls, sl, l, | structureless massive | very friable to friable | low | 2.3 | 1.5 |
| 7 | fsl, vfsl, sil, si, vfs | structureless- massive | very friable to friable | low to moderate | 2.1 | 1.5 |
| 8 | all textures | structureless- massive | firm to very firm | moderate | 1.9 | 1.3 |
| 9 | all textures | platy or structureless- massive | firm to very firm | high | 1.5 | 1.0 |
| 10 | all textures | platy or structureless- massive | extremely firm | very high to extremely high | Not Allowed | Not Allowed |
| Notes:(1) Loading rates shall be based on one hundred fifteen (115) gallons/bedroom and upon texture, structure, and consistence of the most restrictive horizon within three feet (3’) below the proposed base of the APD. Please see §§ 6.76, 6.77, 6.79, 6.82, and 6.83 of this Part, Figures 18, 19, 21, 24, and 25.(2) Pressurized shallow narrow drainfields placed in cos, vcos, gravelly or very gravelly soils shall be installed over a leveled-off six inch (6”) layer of sand meeting ASTM C-33 incorporated above at § 6.7(G) of this Part. |
C. Bottomless Sand Filters (BSFs)
1. BSF design guidelines: All BSFs shall conform to § 6.36(A) of this part “General design parameters for all pressurized drainfields.”
2. Additional components of the BSF: Bottomless sand filters shall also conform to the components in § 6.36(B) of this Part: “Common components for all pressurized drainfields.”
a. BSF Enclosures (See § 6.79, Figure 21)
c. BSF distribution laterals
3. BSF Installation Specifications
b. Installation of BSF media
D. Pressurized Shallow Narrow Drainfield
1. PSND Design Guidelines: PSNDs shall also conform to § 6.36(A) of this part, “Common design parameters for all pressurized drainfields.”
2. Additional Components of the PSND: PSNDs shall also conform to the components in § 6.36(B) of this Part, “Common components for all pressurized drainfields.”
3. PSND Installation Specifications
A. LPP design guidelines: LPPs shall also conform to § 6.36(A) of this Part: “General design parameters for all pressurized drainfields.”
B. Components of the LPP: LPPs shall also conform to other components in § 6.36(B) of this Part: “Common components for all pressurized drainfields.”
A. Applicability – Large OWTSs defined below shall comply with all other applicable provisions of these Rules in addition to the requirements in this § 6.36 of this Part. A large OWTS shall be any OWTS designed, installed or operated that meets any of the criteria in §§ 6.39(A)(1) through (4) of this Part below.
B. Application Requirements – All submittals for OWTSs meeting the definitions in § 6.39(A) of this Part shall include the following:
1. Notice Requirements: Each application for a large OWTS shall be accompanied by a list identifying the names and addresses of the local building official, the water supply agency whose water supply is drawn from the watershed or wellhead protection area wherein the property is located, if applicable, all property owners within four hundred feet (400’) of any component of the proposed OWTS, and all abutting property owners.
C. Impact Analysis – Applicants shall be required to demonstrate that the proposed disposal site is capable of accepting, treating and transmitting effluent at the proposed application rate without adverse impact to surface water or groundwater. Such analysis shall include, but not necessarily be limited to:
2. Groundwater: Applicants shall conduct modeling of nitrate concentrations in groundwater downgradient of the OWTS at any compliance point defined as the property boundary, drinking water well, or other sensitive receptor as determined by the Director. This compliance point may extend downgradient beyond the applicant’s property line if the adjacent property is designated as a groundwater discharge zone in accordance with Subchapter 05 Part 3 of this Chapter, Groundwater Quality Rules. The nitrate concentration modeling shall be done in accordance with the following:
A. Alternative toilets include composting toilets that meet or exceed performance standards equivalent to the requirements of the National Sanitation Foundation Standard 41, incorporated above at § 6.7(C) of this Part and incinerator toilets.
C. Residuals – Solids produced by alternative toilets may be buried on site, unless prohibited by § 6.43 of this Part. Residuals shall not be applied to food crops. Alternative toilets that may generate excess liquids shall either be designed such that the residual liquids are pumped to the graywater septic tank or to a separate holding tank. Liquids shall be removed from this separate holding tank by a DEM-permitted septage transporter. This holding tank shall be designed as follows:
B. Administrative – The Department shall:
D. Alternative Technology Evaluation Criteria – The Director may approve an alternative OWTS or technology if it meets the following criteria:
1. Class One:
2. Class Two: Satisfy either §§ 6.41(D)(2)(a) or (b) of this Part below:
a. For any technology:
b. For a nitrogen reducing technology:
E. Alternative OWTS Component Evaluation Criteria – The Director may approve an Alternative OWTS Component if it meets the following criteria:
1. Class One:
2. Class Two:
F. Experimental Technology Evaluation Criteria – The intent of an Experimental Technology Approval is to evaluate, under actual field conditions, alternative OWTS that appear technically capable of providing levels of environmental protection at least equivalent to those provided by an OWTS installed in compliance with these rules. Data gathered under an Experimental Technology approval may be used to apply for Alternative Technology Class Two approval.
2. The Director may approve an Experimental Technology if the vendor meets the following criteria:
c. Substandard Performance – The vendor agrees in writing to the following conditions regarding the performance of the Experimental Technology:
G. Review and Approval
1. The Director shall review the application and respond as follows:
4. If the Alternative or Experimental Technology is approved by the Director, the applicant shall submit a finalized guidance document to the Director detailing all design, installation, operation and maintenance requirements. Once the guidance document has been approved, the applicant shall schedule one (1) or more training events for Licensed OWTS Designers and Licensed OWTS Installers. The Alternative or Experimental Technology shall be placed on the Department's list after the first (1st) training event has been held. The Department shall maintain the approved Alternative or Experimental Technology List and maintain all appropriate guidance documents for the following:
H. Approved Alternative or Experimental Technologies
1. The Director may require any of the following:
2. Persons desiring to modify an approved Alternative or Experimental Technology currently on the approved Alternative or Experimental Technology List shall make the request in writing and submit the following to the Department:
3. In order to remain on the Department's approved Alternative or Experimental Technology List, the applicant shall submit:
I. OWTS Applications Utilizing Alternative or Experimental Technology – Once an Alternative or Experimental Technology application is approved, individual applications to design, construct, alter, or install a Department-approved Alternative or Experimental Technology may be submitted to the OWTS section of the Office of Water Resources.
1. All applicants obtaining an OWTS permit for a Department approved Alternative or Experimental Technology requiring special operation and maintenance procedures shall:
C. Designation – Areas designated as critical resource areas are defined below in §§ 6.42(C)(1) through (3) of this Part. If the applicant disputes a delineation in §§ 6.42(C)(1) through (3) of this Part, the applicant may submit information on groundwater or surface water flow to demonstrate to the Director by a preponderance of clear and scientifically valid evidence that the delineation in question is incorrect.
B. Nitrogen Reducing Technology
2. Use of Composting Toilets – Composting toilets meeting the criteria of § 6.40 of this Part may be approved for use as a nitrogen reducing technology provided that:
3. Exemptions for Applications for Repair – The provisions of § 6.43(B)(1) of this Part may not apply to an OWTS Application for Repair if the Municipality where the OWTS is located:
D. Site Suitability – OWTS shall not be located where the seasonal high groundwater table is within five feet (5’) of the original ground surface, or where a restrictive layer or bedrock is within seven feet (7’) of the original ground surface, except in areas where the seasonal high groundwater table is within two (2’) to five feet (5’) of the original ground surface, or where a restrictive layer or bedrock is within four (4’) to seven feet (7’) of the original ground surface and either of the following in §§ 6.43(D)(1) or (2) of this Part occur. Twenty-five feet (25’) shall be maintained from the leachfield to any area where the groundwater table is less than two feet (2’) to the original ground surface, or where bedrock is less than four feet (4’) to the original ground surface.
2. Application is for a dispersal trench OWTS that meets the following conditions:
D. Nitrogen Loading
| Nitrogen Removal (Percentage) | Effluent Nitrogen Concentration (mg/l) | Maximum Design Flow per 20,000 sq. ft. (gpd) |
| 50 | 19 | 690 |
| 66 | 13 | 1015 |
| 75 | 10 | 1380 |
E. Exceedance of Design Flow Calculation – The three hundred forty five (345) gallons per day per twenty thousand (20,000) square feet design limit or other design limit utilizing nitrogen reducing technologies pursuant to § 6.45(B) of this Part may be exceeded by the establishment of nitrogen credit land meeting the requirements of § 6.45(F) of this Part under the following circumstances:
F. Nitrogen Credit Land – Nitrogen credit land cannot be designated on land that is already being used to meet the nitrogen loading requirements for an OWTS approved by the Director. Nitrogen credit land must be restricted by a deed restriction, conservation easement, or other appropriate legal instrument recorded in the municipal land evidence records such that:
A. Expiration of Permits for OWTS Applications for New Building Construction and OWTS Applications for Alteration to a Structure
B. Expiration of Permit after Start of Construction
C. Expiration of Permits for OWTS Repairs – All permits for repairs to OWTSs issued in accordance with § 6.18(G) of this Part shall expire as follows:
E. Expiration of OWTS Suitability Determinations – OWTS Suitability Determinations may not be renewed. All OWTS Suitability Determinations issued in accordance with § 6.18(D) of this Part shall expire as follows:
B. Responsibilities of a Licensed Installer – A Licensed Installer shall adhere to the following:
F. Inspection – The Licensed Designer shall, at minimum, inspect and make measurements, where appropriate, of the following components and steps in the installation of the OWTS:
G. Unforeseen Conditions – If conditions are encountered during construction which indicate that the OWTS cannot be installed or is not installed in accordance with the permit, or any terms and conditions contained therein, the Licensed Designer shall notify the Director as soon as possible, but no later than twenty-four (24) hours after discovery. The Department shall maintain written guidance on specifications for construction tolerances as well as conditions under which as-built plans and redesigned plans are required. The Licensed Designer shall stop construction if conditions are such that a redesign is required. Notification is not required if all design elements are within the tolerances established by the Department through written guidance. In response to the designer's notification, the Director shall either:
H. Installation Verification – The Licensed Designer shall collect the information in §§ 6.47(H)(1) through (4) of this Part that can be used to verify that the installation of the OWTS was performed as specified. The Licensed Designer shall keep this information on file for a minimum of ten (10) years from the date of the Certificate of Construction in § 6.48 of this Part. At the Department's request, the Licensed Designer shall make this information available for review.
I. Replacement Designer – An applicant may apply to the Director for approval to have a Licensed Designer, other than the one that designed the OWTS, be responsible for witnessing and inspecting the installation under the conditions specified in §§ 6.47(I)(1) and (2) of this Part. The Director may grant the approval provided the replacement Licensed Designer has a license issued in accordance with §§ 6.10 and 6.11 of this Part authorizing the Licensed Designer to design the type of OWTS in question, and the replacement Licensed Designer signs an affidavit assuming full responsibility for installation of the OWTS in accordance with the DEM issued permit.
1. An applicant may apply to the Director for a replacement Licensed Designer in either of the following circumstances:
A. Certificate of Construction Required – The Licensed Designer that is responsible for the OWTS installation in accordance with § 6.47 of this Part shall complete a Certificate of Construction that certifies that the OWTS was installed in conformance with the approved application, plans, specifications, applicable statutes and regulations and that the License Designer is responsible for having witnessed and inspected the installation. The Certificate of Construction shall be on forms approved by the Director. The Certificate of Construction shall include, but not be limited to, the following:
C. Contents of Variance Request – Requests for variances shall be on forms approved by the Director. It is the applicant’s responsibility to demonstrate by a preponderance of clear and scientifically valid evidence by means of a comprehensive analysis having a probative value that the requested variance(s) will not be contrary to the public health, the public interest or the environment. Applicants must comply with local ordinances; however, such compliance cannot be used to justify or support a variance request under these Rules.
1. The comprehensive analysis shall provide adequate scientific and technical evidence on how the proposed design will mitigate potential adverse impacts on the following:
2. The comprehensive analysis shall include, but not be limited to:
F. Notification Requirements
2. Exemptions from Notification Requirements
3. Each notice shall include:
b. A cover letter conforming to a form to be provided by the Director, which shall include at least the following information:
G. Redesign Applications – For redesign applications submitted to the Department, any variance request previously approved by the Department shall remain valid, provided that the Department determines that either:
A. Preliminary Review and Recommendation – All variance requests shall be reviewed by the Department for the purpose of determining whether such variance(s) would be contrary to the public health, the public interest or the environment. In reviewing the applicant's variance requests, the Department may consult with other experts, whether employed by the Department or not. As part of the review of any variance request(s), the Department shall consider:
B. Variance Review Standards
2. Denial – A variance request from the minimum standards set forth in these Rules shall be denied when:
e. The variance request is for one (1) of the following:
(8) The variance request is from the two hundred foot (200’) public well setback requirement for a drilled rock, driven, or dug well in § 6.23(E) of this Part or from the four hundred foot (400’) public well setback from a gravel packed or gravel developed well in § 6.23(E) of this Part. Such a variance request may be approved if either of the following occurs:
D. Final Determination – Upon review of the recommendation submitted in accordance with § 6.52(C) of this Part, the Director shall render a final written decision approving or denying the requested variance(s). In arriving at a final decision, the Director may:
C. Contents of Appeal – Every appeal shall contain:
3. A list of the names and addresses of:
F. Burden of Proof – At the adjudicatory hearing, the applicant shall have the burden of proof to demonstrate through clear and convincing evidence that:
3. That the issuance of a permit will not be contrary to the public interest, public health and the environment. In order to demonstrate that the proposed OWTS will not be contrary to the public interest, public health and the environment, the applicant must introduce clear and convincing evidence to the satisfaction of the Director that:
G. The Director may approve a permit or grant a variance from a provision of these Rules, except for the prohibitions in § 6.9 of this Part, where it is determined by the Director that:
A. Administrative
B. Fee Schedule
| DESCRIPTION | FEE |
| Soil Evaluations | $150.00 per OWTS |
| Wet Season Determinations | $100.00 per OWTS |
| Bedrock Test Holes | $100.00 per OWTS |
| Test Holes in Storm Deposited Sand or Human Transported Material | $100.00 per OWTS |
| Reinspection | $100.00 |
| Application for OWTS Suitability Determination | $100.00 |
| OWTS Application for New Building Construction and OWTS Application for Alteration to a Structure. The fees for applications utilizing a pretreatment technology, excluding leachfield systems and components, approved as an Alternative or Experimental Technology pursuant to § 6.41 of this Part or a technology not included in these Rules specifically engineered for the application, shall be two (2) times the following fees:(The fee for a Joint OWTS/Freshwater Wetlands Permit Application is the sum of the OWTS fee and the Freshwater Wetlands Permit Application fee.) | |
| Single Family Residences: | |
| Single Family Residence | $150.00 |
| Commercial OWTSs: | |
| Less than 2,000 gpd | $200.00 |
| 2,000 gpd to 4,999 gpd | $500.00 |
| 5,000 gpd to 9,999 gpd | $1,000.00 |
| 10,000 gpd or more | $2,000.00 |
| Subdivision Review | |
| 1 to 9 Lots | $100.00 per lot |
| 10 Lots or more | $1,000.00 plus $50.00 per lot for each lot over 10 |
| OWTS Application for Repair. The fees for applications utilizing a pretreatment technology, excluding leachfield systems and components, approved as an Alternative or Experimental Technology pursuant to § 6.41 of this Part or a technology not included in these Rules specifically engineered for the application, shall be two (2) times the following fees: | |
| Single Family Residence | $100.00 |
| Commercial OWTSs: | |
| Less than 2,000 gpd | $150.00 |
| 2,000 gpd to 4,999 gpd | $300.00 |
| 5,000 gpd to 9,999 gpd | $600.00 |
| 10,000 gpd or more | $1,000.00 |
| Application Transfer, including Joint OWTS/Freshwater Wetlands Permit Application | $50.00 |
| Any Variance Request for OWTSs: Residential and Commercial (Variance Request Fee is in addition to the application fee) | $300.00 |
| If the application has been previously reviewed by the Department and found deficient and the re-submission does not address these deficiencies, then the Department will assess a fee for the second re-submission equal to fifty percent (50%) of the original fee. In no case shall this resubmission fee exceed three hundred dollars ($300.00). | |
| Alternative or Experimental Technology: | |
| Alternative OWTS or Technology: | |
| Class One | $1,000.00 |
| Upgrade from Class Two to Class One | $500.00 |
| Class Two | $1,000.00 |
| Alternative OWTS Component: | |
| Class One | $200.00 |
| Class Two | $300.00 |
| Experimental OWTS or Technology | $2,000.00 |
| Renewal of Alternative or Experimental Technology Application: | |
| Alternative OWTS or Technology Class Two | $500.00 |
| Alternative OWTS Component Class Two | $150.00 |
| Experimental OWTS or Technology | $1,000.00 |
| Approval Modification | $200.00 |
Installer's Licenses: | |
| Examination and New License Application (3 years, the Department may pro-rate fee if the license is issued for less than 3 years) | $175.00 |
| License Renewal (3 years, the Department may pro-rate fee if the renewal is for less than 3 years) | $150.00 |
| Class I, II, III, and IV Licenses: | |
| Examination and New License Application (3 years, the Department may pro-rate fee if the license is issued for less than 3 years) | $200.00 |
| License Renewal (3 years, the Department may pro-rate fee if the renewal is for less than 3 years) | $150.00 |
| License Renewal Late Fees | |
| < 1 year expired | $100.00 |
| 1-2 years expired | $200.00 |
| 2-3 years expired | $300.00 |
C. Additional Fees – These additional fees shall be collected prior to the Department's review of the submission(s) under consideration. No final approval or denial shall be issued by the Director until such time as these additional fees have been received.
| DESCRIPTION | FEE |
| Designers Affidavit Continuing Validity – per lot | $50.00 |
| Designers Affidavit – Subdivisions | $100.00 |
| Revision to Subdivision (1 to 9 lots) per lot | $50.00 |
| Revision to Subdivision (10 or more lots) | $500.00 |
| As Builts – Requested or Submitted | $50.00 |
| Redesign – Single Family | $100.00 |
| Redesign – Commercial – less than 2,000 gpd | $150.00 |
| Redesign – Commercial – more than 2,000 gpd | $400.00 |
| Redesign – Joint OWTS/Freshwater Wetlands Permit Application | $150.00 |
B. Maintenance – All OWTSs shall be maintained in good repair by the owner. The Director may order the owner to maintain or repair an OWTS within a reasonable time if the Director finds them to be in need of the same. In order to maintain long-term viability of the OWTS, it is the owner's responsibility to:
C. Cesspool Removal and Replacement – Cesspools shall cease to be used for wastewater disposal and shall be properly abandoned in accordance with the schedule below in §§ 6.57(C)(1) through (3) of this Part. Any cesspool required to be abandoned pursuant to this Rule shall be properly abandoned in accordance with § 6.56 of this Part and such cesspool shall be replaced with an approved OWTS, or the building served by the cesspool shall be connected to a public wastewater system, prior to the applicable deadlines contained in this Rule.
E. Exemptions
2. The provisions of §§ 6.57(C)(2) and (3) of this Part shall not apply to any cesspool located on a property that is properly designated to be served by a public wastewater system no later than January 1, 2020 provided that: