N.Y. Comp. Codes R. & Regs. tit. 1, § 2.48
(1) Batch pasteurizers:
(2) High-temperature-short-time pasteurizers. Recording thermometer charts shall contain all the information specified in paragraph (1) of this subdivision, except subparagraphs (iii) and (iv) and reference to airspace thermometers in subparagraph (vi), and, in addition, shall include the following: Note:
(ii) The cut-in and cut-out milk temperatures recorded daily by the operator at the beginning of the run, and initialed quarterly by the regulatory agency, section 2.46 of this Part (Item 16p[B]).
Note:
The recorded temperature shown on the controller chart shall be used to determine that the required temperature for milk products containing higher fat and/or sweeteners has been achieved.
(4) Removal of regulatory seals and resumption of pasteurization. No equipment required to be sealed pursuant to section 2.46 of this Part shall be used if the regulatory seal has been broken unless the conditions set forth in subparagraphs (i) through (iii) of this paragraph are met:
(iii) a sample of the milk, milk product, melloream or frozen dessert processed or manufactured in such equipment is properly taken immediately after the resumption of pasteurization and every two hours thereafter and properly analyzed in an officially designated laboratory for the presence of phosphatase and is found to not exceed the phosphatase standard set forth in section 2.8 of this Part. No milk, milk products, melloream or frozen dessert processed or manufactured in equipment from which a seal has been broken shall be removed from the milk plant until the processing plant superintendent determines that all of the provisions set forth in subparagraphs (i) through (iii) of this paragraph have been met.
(b) Table.
| Instrument or device | Test No. | Test objective |
|---|---|---|
| Batch pasteurizer indicating thermometer | 1 | Accuracy. |
| Batch pasteurizer recording thermometer | 2 | Temperature accuracy. |
| Batch pasteurizer recording thermometer | 3 | Time accuracy. |
| Batch pasteurizer recording thermometer | 4 | Check reading of recording thermometer against indicating thermometer. |
| Airspace thermometer | 1 | Accuracy. |
| Valves | 6 | Leakage in plug–type leak–protector valves and poppet–type valves. |
| HTST indicating thermometer | 1 | Accuracy. |
| HTST indicating thermometer | 7 | Thermometric response. |
| HTST recording thermometer | 2 | Temperature accuracy. |
| HTST recording thermometer | 3 | Time accuracy. |
| HTST recorder controller | 2 | Temperature accuracy. |
| HTST recorder controller | 4 | Check reading of recorder controller against indicating thermometer. |
| HTST recorder controller | 8 | Thermometric response. |
| HTST recorder controller | 10 | Confirm cut–in and cut–out temperatures. |
| HTST flow–diversion device | 5 | Assembly and function. |
| HTST auxiliary (booster) pump | 9 | Function of automatic control devices. |
| HTST auxiliary (booster) pump | 9 | Accuracy of pressure gauges. |
| HTST system | 11 | Check holding time. |
| HHST system | 12 | Thermal limit control for sequence logic. |
| HHST system | 13 | Setting of control switches for product pressure in the holding tube. |
| HHST system | 14 | Setting of control switches for differential pressure across the injector. |
(a) Temperature recording charts.
All temperature recording charts shall be preserved for a period of three months. The use of such charts shall not exceed the time limit for which they are designed. Overlapping of recorded data shall be a violation of this item. The following information shall be entered on the charts as applicable: