(b) The code shall apply to the construction of any new building. The code shall also apply to an addition to, and alteration of, any existing building or building system; provided, however, that the code shall not be interpreted to require any unaltered portion of the existing building or building system to comply with the code. The code shall not apply to the following provided that the energy use of the building is not increased:
- (1) storm windows installed over existing fenestration;
- (2) glass only replacements in an existing sash and frame;
- (3) existing ceiling, wall or floor cavities exposed during construction provided that these cavities are filled with insulation;
- (4) construction where the existing roof, wall or floor cavity is not exposed;
- (5) reroofing for roofs where neither the sheathing nor the insulation is exposed; roofs without insulation in the cavity and where the sheathing or insulation is exposed during reroofing shall be insulated either above or below the sheathing;
- (6) replacement of existing doors that separate conditioned space from the exterior shall not require the installation of a vestibule or revolving door, provided, however, that an existing vestibule that separates such conditioned space from the exterior shall not be removed;
- (7) alterations that replace less than fifty percent of the luminaires in a space, provided that such alterations do not increase the installed interior lighting power;
- (8) alterations that replace only the bulb and ballast within the existing luminaires in a space provided that the alteration does not increase the installed interior lighting power; and
- (9) any other exception adopted by the state fire prevention and building code council provided that such exception will not prevent the attainment of the compliance goals set forth in section 410(2)(c) of the American Recovery and Reinvestment Act of 2009.