Effective Nov 30, 1999section 414.142, RSMo Supp. 1998.* This rule was previously filed as 2 CSR 90-30.020. Emergency rule filed Dec. 1, 1987, effective Jan. 1, 1988, expired March 1, 1988. Original rule filed Oct. 16, 1987, effective Feb. 11, 1988. Amended: Filed April 2, 1990, effective June 28, 1990. Amended: Filed April 14, 1994, effective Sept. 30, 1994. Amended: Filed April 8, 1999, effective Nov. 30, 1999Weights, Measures and Consumer Protection
PURPOSE: This rule establishes requirements for the specifications, installation, use and tolerances of measuring devices.
PUBLISHER’S NOTE: The publication of the full text of the material that the adopting agency has incorporated by reference in this rule would be unduly cumbersome or expensive. Therefore, the full text of that material will be made available to any interested person at both the Office of the Secretary of State and the office of the adopting agency, pursuant to section 536.031.4, RSMo. Such material will be provided at the cost established by state law.
- (1) Each location dispensing products regulated by Chapter 414, RSMo shall have a measuring device for each product dispensed which shall be utilized for the sale of products regulated by Chapter 414, RSMo. All transactions involving the sale of petroleum products regulated by Chapter 414, RSMo shall be based on the gallons stated by the measuring device.
- (2) All measuring devices shall be installed in locations easily accessible for testing, inspection and maintenance purposes.
- (3) The director shall order any device installed in a manner not accessible for testing, inspection and maintenance to be corrected, discontinued from use or removed.
- (4) Each measuring device used in the sale of petroleum products regulated by Chapter 414, RSMo shall meet the requirements contained in the current edition of NIST Handbook 44, National Fire Protection Association (NFPA) Manual No. 30A, 1996 Edition which is incorporated herein by reference, and be installed and maintained as recommended by the device manufacturer.
- (5) At least every six (6) months, the director shall test and inspect the measuring devices used by any person selling an average of two hundred (200) or more gallons of gasoline, gasoline-alcohol blends, diesel fuel, heating oil, kerosene or aviation turbine fuel each month at either retail or wholesale in this state except marinas, which shall be tested and inspected at least once each year.
- (6) The meter of each dispensing device shall be sealed with an official state security seal applied by the director or his/her delegated representative. No person shall break or tamper with any official state security seal without the consent of the director or his/her delegated representative except for repair or replacement of that device, at which time notification is to be given to the director within five (5) days.
- (7) No person, except the director or his/her delegated representative, shall duplicate the state seal of Missouri to be used for sealing or applying seals to any measuring device dispensing products regulated by Chapter 414, RSMo.
- (8) Each retail measuring device shall display unit price and product identity on the face of the device as required in 2 CSR 90-30.040 and the current edition of NIST Handbook 44.
- (9) A container or storage shall be provided by the owner or operator of the device for storage of the fuel dispensed during the device test. The container or storage must comply with the requirements of NFPA Manual No. 30, 1996 Edition which is incorporated herein by reference.
- (10) Each measuring device dispensing products regulated by Chapter 414, RSMo shall be free of leaks; the dispensing hose shall be in a condition as to prevent a hazard of leaking or bursting; and electrical wiring shall meet requirements as contained in NFPA Manual No. 70, 1996 Edition which is incorporated herein by reference.
- (11) Each measuring device shall be equipped with an effective vapor eliminator or other means automatic in operation to prevent the passage of vapor and air through the meter. Vent lines from the air or vapor eliminator shall be made of metal or some similar other suitable rigid material.
- (12) Size of Nozzle Spout for Dispensing Motor Fuels. Each dispensing device from which gasoline or other motor fuel that contains lead or phosphorus is sold shall be equipped with a nozzle spout having a terminal end with an outside diameter of not less than ninety-three hundredths inch (0.93") (two and three hundred sixty-two thousandths centimeters (2.362 cm)). A gasoline or other motor fuel is considered to contain lead or phosphorus if it contains more than five hundredths (0.05) grams lead per United States gallon (thirteen thousandths (0.013) grams lead per liter) or more than five thousandths (0.005) grams phosphorus per United States gallon (thirteen ten thousandths (0.0013) per liter).
- (13) Any measuring device that does not meet the requirements of this rule shall be ordered corrected, discontinued or removed.
- (14) No person shall hinder or obstruct the director or his/her delegated representative in the reasonable performance of his/her duties.
- (15) No person shall break, tamper with, reproduce, remove or deface any official state seal, decal, tag, lock, label, form or equipment.
- (16) If the design, construction or location of any device is such as to require a testing procedure involving special equipment or accessories or an abnormal amount of labor, the equipment, accessories and labor shall be supplied by the owner or operator of the device as required by the weights and measures official.
- (17) A listed rigidly anchored emergency shut-off valve (fire-impact) incorporating a fusible link or other thermally actuated device designed to close automatically in the event of severe impact or fire exposure shall be installed in accordance with the manufacturer’s instructions in the supply line at the base of each island-type pump or dispenser or at the inlet of each overhead dispensing device. An emergency shut-off valve incorporating a slip joint feature shall not be used.
- (18) Each hose nozzle at automotive service stations shall be equipped with a device, such as a spout anchor spring, designed to retain the nozzle spout in the vehicle fuel tank inlet while refueling.
AUTHORITY: section 414.142, RSMo Supp. 1998.* This rule was previously filed as 2 CSR 90-30.020. Emergency rule filed Dec. 1, 1987, effective Jan. 1, 1988, expired March 1, 1988. Original rule filed Oct. 16, 1987, effective Feb. 11, 1988. Amended: Filed April 2, 1990, effective June 28, 1990. Amended: Filed April 14, 1994, effective Sept. 30, 1994. Amended: Filed April 8, 1999, effective Nov. 30, 1999.