Mo. Code Regs. Ann. tit. 10, § 60-4.080
PURPOSE: This rule establishes criteria for operation and operational monitoring.
Editor’s Note: The following material is incorporated into this rule by reference: 1) Methods for Chemical Analysis of Water and Wastes, Revised March 1983 (Springfield VA: U.S. Department of Commerce, 1983); 2) Standard Methods for the Examination of Water and Wastewater, 18th Edition (Baltimore, MD, Victor Graphics, Inc., 1992). In accordance with section 536.013(4), RSMo, the full text of material incorporated by reference will be made available to any interested person at the Office of the Secretary of State and the headquarters of the adopting state agency.
pH
JOHN R. ASHCROFT
At time of
Daily
As necessary 10 CSR 60-4
Operational Testing
Sampling Points
Entry point(s) X
Entry point to
| for control | distribution | X | X | X |
|---|---|---|---|---|
| As necessary | Raw Water | |||
| for control | X | |||
| Start-up and | ||||
| every 4 hours | ||||
| of operation | Filter effluent | X | ||
| As necessary | Primary & secondary | |||
| for control | basins | X |
| added) to distribution | ||||
|---|---|---|---|---|
| Monthly Representative point | ||||
| in distribution | X | |||
| Hardness Daily Entry point to | ||||
| distribution | X | X | X | |
| Iron Start-up and Filter influent and | ||||
| every 4 hours and effluent | ||||
| of operation | X | X2 | X2 | X2 |
| bacti sampling | X6,7 | X6 | X | X6 | X | X |
|---|---|---|---|---|---|---|
| Start-up and Filter influent | ||||||
| every 2 hours and effluent | ||||||
| of operation | X | X | ||||
| Start-up and Entry point to | ||||||
| every 2 hours distribution | ||||||
| of operation | X5 | X | X | |||
| Start-up and Entry point to | ||||||
| every 4 hours distribution | ||||||
| of operation | X6 |
| Sample | Iron | Zeolite | Lime Fluoride | |||||
|---|---|---|---|---|---|---|---|---|
| Test | Frequency | Location | Disinfection | Sequestration | Removal | Softening | Clarification | Softening Adjustment |
| Alkalinity | As necessary | Raw water | X | X | ||||
| (phenolphthalein | for control | |||||||
| and total) | ||||||||
| As necessary | Entry point | |||||||
| for control | to distribution | X | X | |||||
| Disinfectant | Continuous1 | Entry point | ||||||
| Residual | to distribution | X5 | X | X5 | ||||
| Daily | Entry point | |||||||
| to distribution | X6,7 | X6 | X6 |
Sample Iron Zeolite Lime Fluoride
Test Frequency Location Disinfection Sequestration Removal Softening Clarification Softening Adjustment
Phosphate As necessary Downstream for control from point of
X—Indicates test(s) needed 1—If system serves greater than 3300 population 2—If raw water contains > 0.3 mg/l iron 3—If phosphate compounds are added to the water 4—For facilities utilizing solids contact basins 5—Surface and ground water under the direct influence of surface water 6—Groundwater system not under the direct influence of surface water required to provide disinfection 7—Secondary system required to supplement disinfection or redisinfect
| application | X | X | X | X | X |
|---|---|---|---|---|---|
| Sludge As necessary Center cone and | |||||
| concentration4 for control sludge blowoff and | |||||
| sample taps | X | X | |||
| Temperature5 As necessary Entry point to | |||||
| for control distribution | X | X | X | X | |
| Turbidity5 Every 4 Entry point to | |||||
| hours of distribution and filter | |||||
| plant influent | X5 | X | X5 | ||
| operation |
AUTHORITY: section 640.100, RSMo 1994.* Original rule filed May 4, 1979, effective Sept. 14, 1979. Amended: Filed April 14, 1981, effective Oct. 11, 1981. Amended: Filed July 12, 1991, effective Feb. 6, 1992. Amended: Filed Feb. 1, 1996, effective Oct. 30, 1996. *Original authority: 640.100, RSMo 1939, amended 1978, 1981, 1982, 1988, 1989, 1992, 1993, 1995.