Kan. Admin. Regs. § 5-40-16
The allowable leakage rate for a principal spillway pipe installation in a dam shall not exceed 1,000 gallons per inch diameter of pipe per mile of pipe per day. The applicant shall use one of the following test methods in determining whether the allowable leakage rate has been exceeded:
(a) The applicant shall use the following test method procedure for a drop inlet structure if the starting and ending elevation of the water is within the vertical drop structure and above the top of the barrel:
(1) Calculate the allowable leakage rate in gallons per minute for the pipe being tested based on the following formula:
The allowable leakage rate in gallons per minute = 0.000132 × d × l where:
d = diameter of the tested pipe in inches
l = length of the tested pipe in feet
If the allowable leakage rate in gallons per minute is determined to be less than one, then it shall be assumed for the purposes of the test that the allowable leakage rate in gallons per minute is one.
(3) If the allowable leakage rate is one gallon per minute, the applicant may use the following table to determine the allowable drop in the elevation of the water in the riser.
| Nominal diameter of riser (inches) | Allowable drop (feet) |
| 18 | 1.13 |
| 20 | 0.83 |
| 24 | 0.64 |
| 30 | 0.41 |
| 36 | 0.28 |
(b) The applicant shall use the following test method procedure for all other types of installations, including canopy inlets:
(2) The allowable drop in elevation is a function of the allowable leakage rate, test duration, and the diameter and slope of the pipe. The allowable drop in the pipe in feet shall be calculated by use of the following formula:
allowable rate (gallons per minute)×test duration (minutes)×slope (\%) [diameter (inches)] 2 ×4.08
(Authorized by K.S.A. 82a-303a; implementing K.S.A. 82a-303b; effective Sept. 22, 2000.)