Ind. Admin. Code tit. 675, r. 30-10-8
Authority: IC 22-13-2-8
Affected: IC 22-15-6
Sec. 8. (a) Each low pressure steam heating boiler shall have a steam gauge connected to its steam space or to its water column, or its steam connections by means of a siphon or equivalent device to keep the gauge tube filled with water and so arranged that the gauge cannot be shut off from the boiler except by a cock with a tee or lever handle, placed in the pipe near the gauge. The handle of the cock shall be parallel to the pipe in which it is located when the cock is open.
(b) The scale on the dial of a low pressure steam heating boiler gauge shall be graduated to not less than thirty (30) psig. The gauge shall be provided with effective stops for the indicating pointer at the zero (0) point and at the maximum pressure point. The travel of the pointer from zero (0) to thirty (30) psig pressure shall be at least three (3) inches.
(c) Connections to steam-gauge siphons shall be of nonferrous metal when either:
(d) On a compound gauge, effective stops shall be set at the limits of the gauge readings on both pressure and vacuum sides.
(Fire Prevention and Building Safety Commission; 675 IAC 30-10-8; filed Jan 5, 1996, 10:15 a.m.: 19 IR 1134; readopted filed Jul 9, 2001, 1:33 p.m.: 24 IR 3822; readopted filed Sep 21, 2007, 9:16 a.m.: 20071010-IR-680070389RFA; readopted filed Oct 19, 2007, 1:08 p.m.: 20071114-IR-680070389RFA; readopted filed Sep 5, 2013, 10:09 a.m.: 20131009-IR-680130182RFA; readopted filed Sep 4, 2019, 2:20 p.m.: 20191002-IR-675190336RFA; filed Apr 28, 2021, 11:03 a.m.: 20210526-IR-675200627FRA, eff Jul 1, 2021; readopted filed Nov 18, 2025, 10:36 a.m.: 20251210-IR-675240566RFA) NOTE: Transferred from the Boiler and Pressure Vessel Rules Board (680 IAC 2-10-8) to the Fire Prevention and Building Safety Commission (675 IAC 30-10-8) by P.L.249-2019, SECTION 15, effective July 1, 2019.