Ind. Admin. Code tit. 410, r. 6-8.3-66
Authority: IC 16-19-3-4
Affected: IC 16-19-3-4
Sec. 66. (a) Concrete distribution boxes shall be constructed of concrete with a compressive strength of four thousand (4,000) pounds per square inch or greater. Other materials may be considered on a case-by-case basis. All materials must:
(b) The minimum interior dimension of a distribution box shall be twelve (12) inches.
(c) The distribution box shall be fitted with a watertight, removable lid for access. The distribution box may be fitted with a riser to the ground surface. The riser joints and the lid connection to the riser must be watertight.
(d) The interior bottom of the distribution box shall be at least four (4) inches below the invert elevation of the effluent ports. A minimum of eight (8) inches freeboard above the invert elevation of the effluent port shall be provided.
(e) The influent port shall be located or baffled to prevent unequal distribution of effluent to the distribution system. If baffles are provided, the baffles and their mounts or retainers shall:
(f) An elbow or sanitary tee in the vertical position may be used in place of a baffle, as follows:
(1) If an elbow is used, the elbow must:
(g) Each distribution box shall be designed to split the effluent flow equally among the effluent ports. All effluent ports shall be: