Fla. Admin. Code R. 62-761.430
(1) Incidents include:
(a) The following positive responses of release detection devices or methods described in Rule 62-761.600, F.A.C.:
1. Any visual observation of regulated substances in a piping or dispenser sump,
2. Any alarm that indicates that liquid, vacuum, or pressure monitoring levels are not being maintained, or that liquid has been detected by a sensor in a normally dry interstice or a dispenser, piping or containment sump,
3. Any visual observation that indicates that liquid monitoring levels are not being maintained,
4. Any complete loss of vacuum or a 50 percent change in pressure from one month to the next, or any change in pressure exceeding 50 percent of the initial level or of a pressure level that is reestablished at the time of an incident investigation or annual testing of the gauge,
5. Any visual inspection that indicates the presence of groundwater or surface water, other than condensate, or regulated substances in the interstice,
6. Any instance where a mechanical line leak detector is restricting flow,
7. Any instance where an electronic line leak detector has shut off power to the pump,
8. Any instance where a monitoring device has shut off the pump,
9. Liquid in excess of one inch in an out-of-service storage tank; and,
10. Any visual inspection of any part of a storage tank system, dispenser, pipe, valve, pump, or other wetted portion of the system containing regulated substances that reveals uncontrolled pitting corrosion, structural damage, leakage, or other similar programs.
(b) A failed integrity test for the following components:
1. Double-walled storage tanks,
2. Double-walled integral piping,
3. Piping sumps,
4. Dispenser sumps; and,
5. Spill containment systems.
Rulemaking Authority 376.303 FS. Law Implemented 376.303 FS. History–New 1-11-17, Amended 7-9-19. Editorial Note: Portions of this rule were copied from Rule 62-761.820, Formerly 17-761.820, F.A.C.