Fla. Admin. Code R. 62-6.013
(1) Onsite sewage tank design. The following requirements must apply to all onsite sewage tanks manufactured for use in Florida unless specifically exempted by other provisions of these rules:
(b) Design and testing of concrete treatment tanks:
1. Structural design of tanks must be by calculation or by performance.
2. Structural design must be verified by actual vacuum load or hydrostatic test in accordance with the Department’s policy for Test Requirements for Structural Proofing, February 28, 2022, herein adopted and incorporated by reference at HYPERLINK "http://www.flrules.org/Gateway/reference.asp?No=Ref-14367" http://www.flrules.org/Gateway/reference.asp?No=Ref-14367. Copies of this policy are available as provided in subsection (14) below. The vacuum test must be followed by a flow and water tightness test.
3. Tanks must be watertight as defined in ASTM C1227-20, Standard Specification for Precast Concrete Septic Tanks, paragraph 9.2., (2020) herein adopted and incorporated by reference. This standard has been deemed copyright protected and is available from the publisher at ASTM International, P.O. Box C700 West Conshohocken, Pennsylvania 19428-2959, or at publisher’s website at HYPERLINK "http://www.astm.org/" \t "_blank" www.astm.org/, and is available for inspection as provided in subsection (14) below. ASTM C1227-20, paragraph 9.2.2, must be modified to read as follows: Water tightness testing – Fill the tank with water to the invert of the outlet and let stand for 24 hours. Refill the tank. The tank is approved as water tight if the water level is held for one hour.
4. Manufacturers may use calculations provided by the design engineer in lieu of proof testing for tanks using reinforcement bars for structural strength and having a wall thickness of 5 inches or greater. Design by calculation must be completed using the Strength Design Method outlined in Chapters 4, 5 and 6 of the American Concrete Institute (ACI) publication ACI 318-19, Building Code Requirements for Structural Concrete and Commentary (2019), herein adopted and incorporated by reference. This document has been deemed copyright protected and is available from the publisher at American Concrete Institute, 38800 Country Club Drive, Farmington Hills, MI 48331-3439, or at publisher’s website at www.concrete.org/, and is available for inspection as provided in subsection (14) below. For the design strength a strength reduction factor will be applied per ACI 318-19 Chapter 21.
(c) Design and testing of fiberglass and polyethylene tanks:
1. Vacuum testing must be conducted in accordance with the Department’s policy for Test Requirements for Structural Proofing, February 28, 2022, herein adopted and incorporated by reference in subparagraph 62-6.013(1)(b)2., F.A.C. Copies of this policy are available as provided in subsection (14), below and at HYPERLINK "http://www.flrules.org/Gateway/reference.asp?No=Ref-14367" http://www.flrules.org/Gateway/reference.asp?No=Ref-14367. The vacuum test will be followed by a water-tightness test.
2. Vacuum testing must demonstrate a distortion of volume of no more than 1% at a safety factor of 1.0 and 2% at a safety value of 1.4 followed by passing a water-tightness test to be considered satisfactory. To determine the vacuum at a 1.0 safety factor, divide the required total vacuum values by 1.4. There must be no distortion of the access hatch perimeters at the full vacuum load and the access hatch must be able to be removed and reinstalled at the conclusion of the test.
3. Flow and water-tightness testing must be performed as follows: Fill the tank with water to the invert of the outlet. The tank is approved as water tight if the water level is held for one hour.
(2) Onsite sewage tank design requirements.
(j) The tank legend is the Department’s designated approval number for the tank, and the effective capacity of the tank in gallons. The tank legend must be cast or stamped into the wall or permanently stenciled or decaled onto the wall at the inlet end, to begin within 6 inches of the top of the wall. Tank legend lettering must be a minimum of two inches high.
1. Revisions. All tank legends must be inscribed or affixed at the place of manufacture and can only be revised outside the place of manufacture prior to construction approval by a manufacturer-authorized representative when one or more of the following conditions occur:
a. The legend on the tank does not match the tank that it is affixed to, and the tank is manufactured according to specifications approved under an alternate legend;
b. The legend is illegible, damaged or otherwise compromised; or
c. The legend is improperly positioned on the tank.
2. Manufacturers must inform the Department in writing that they allow tank legend revisions outside the place of manufacture prior to tank legend revisions taking place. The Department will maintain a list of the manufacturer’s pre-approval(s) on the Department’s website.
3. The revised tank legend must be clearly marked and must be permanently affixed onto the tank wall in compliance with paragraph 62-6.013(2)(j), F.A.C. The legend or the portion of the legend that needs to be revised must be covered.
4. When a tank legend is revised, the Department holds the manufacturer responsible for training, authorizing and ensuring that their authorized representatives comply with tank legend revision requirements in this rule. Upon request from the Department, the manufacturer must provide a list of trained representatives who are authorized to revise tank legends.
5. For each tank legend revision, the manufacturer or the manufacturer’s representative must submit to the Department the following information within seven calendar days of the revision:
a. Tank manufacturer name;
b. Construction permit number;
c. Installation site address;
d. Name of authorized representative who revised the legend;
e. Date of revision;
f. Reason for revision per subparagraph 62-6.013(2)(j)1., F.A.C.;
g. Verification the tank was not modified, and that the tank legend as revised is correct;
h. Photograph of the tank legend before and after the revision which identifies information regarding the time and location of the photograph through electronic metadata or included in the notes of the report;
i. The original tank legend and the revised tank legend;
j. A signed and dated statement by the manufacturer or the manufacturer’s representative that states: “I verify that the condition requiring a tank revision outside the place of manufacture complies with subparagraph 62-6.013(2)(j)1., F.A.C., and that the documents and all attachments, to the best of my knowledge and belief, are true, accurate and complete.”
6. The Department will request from the manufacturer or the manufacturer’s representative any additional information needed to confirm compliance with statutory and rule requirements regarding standards for tanks and the tank legend.
7. A summary report of the manufacturer’s tank legend revisions under this subsection must be submitted from the manufacturer to the Department annually by December 31st of each year. The Department will review the summary report to confirm compliance with the standards for tanks and the tank legend. The summary report must include the following:
a. A list of all authorized representatives who revised the Department’s designated approval number for the tank legend;
b. The total number of tank legend revisions performed during the annual cycle;
c. For each tank legend revision, indicate in what county the tank legend revision occurred and the date it occurred.
(k) Each compartment must have access using manholes, with each manhole having a minimum area of 225 square inches. Manholes must be located so as to allow access to the inlet and outlet devices. A minimum 6-inch diameter opening must be placed at the inlet and outlet ends of the lid if a minimum 225 square inch access port is placed in the middle of the lid. A riser is a pipe or conduit surrounding an access manhole and facilitating access to the inside of an onsite sewage tank. Access manhole and riser must be closed by a riser access lid or manhole cover. Risers must be watertight. The access manhole over the inlet and outlet must extend to within 8 inches of finished grade. If a riser is used, and if the riser access lid opens directly to the tank interior, joints around the riser and tank must be sealed and made watertight as specified in paragraph 62-6.013(2)(i), F.A.C., to prohibit intrusion of ground water into the tank. For multi-compartment tanks or tanks in series, manholes must extend to within 8 inches of finished grade over the first compartment inlet and the last compartment outlet. An appropriate mechanism must be provided to make access manholes vandal, tamper, and child resistant. Acceptable protection of openings must consist of one or more of the following methods as specified by the manufacturer:
1. A padlock.
2. A twist lock cover requiring special tools for removal.
3. Covers weighing 58 pounds or more, net weight.
4. A hinge and hasp mechanism which uses stainless steel or other corrosion resistant fasteners to fasten the hinge and hasp to the lid and tank for fiberglass, metal or plastic lids.
(3) Onsite sewage tank design approval. All onsite sewage tanks distributed in the state must be approved for use by the Department prior to being offered for sale or installed. Such approval must not be obtained until the manufacturer of a specific tank model has submitted the following:
(a) Detailed design drawings of the tank and lid showing:
1. Design calculations or proof testing results in accordance with subsection 62-6.013(1), F.A.C.
2. Dimensions, including location and size of all inlets, outlets, access hatches, manholes and pass through orifices.
3. Effective capacity in gallons.
4. Freeboard or air space in gallons.
5. Production materials. For concrete tanks include 28 day compressive strength, in pounds per square inch (psi).
6. Reinforcing materials. For concrete tanks, include size and location of all rebar, if any; and fiber reinforcing material size and quantity (in pounds) per cubic yard, if any.
(f) There must be two tank design classifications. The following criteria must be used for each category:
1. Category 3 tanks must be designed for saturated soil with the saturation at finished grade. The design must provide for a maximum of 18 inches of saturated soil cover over the top of the tank. Soil density must be 100 pounds per cubic foot. The lateral earth pressure coefficient (K) must be no less than 0.33.
2. Category 4 tanks must be designed for saturated soil with the saturation at finished grade. The design must provide for a maximum of 48 inches of saturated soil cover over the top of the tank. Soil density must be 100 pounds per cubic foot. The lateral earth pressure coefficient (K) must be no less than 0.33. Where a tank will be placed with greater than 48 inches of soil over the top of the tank, an engineer licensed in the state of Florida must design the tank for the specific conditions anticipated at the site.
(4) Onsite sewage tank manufacturer’s yearly inspection – Yearly inspection of the manufacturer’s facility must consist of the following:
(h) Inspect a minimum of five tanks in the manufacturers’ inventory. For different series, a minimum of one tank must be inspected from each series. Report the following unacceptable defects:
1. Cracks in all interior and exterior surfaces of the tanks.
2. Cold joint lines. This is an indication of non-monolithic pours. Examine both the interior and exterior of the tank for confirmation of a cold joint that extends across the thickness of the wall.
3. Evidence of improper steel cover. Rebar and wire mesh must not be exposed.
4. Watertight inlets and outlets must be provided per rule.
(5) Concrete tanks must be built of precast or poured in place concrete in accordance with ACI 318-19, Building Code Requirements for Structural Concrete and Commentary incorporated by reference in subparagraph 62-6.013(1)(b)4., F.A.C., effective 06-21-2022, or ASTM C-1227-20, Standard Specification for Precast Concrete Septic Tanks, incorporated by reference in subparagraph 62-6.013(1)(b)3., F.A.C., effective 06-21-2022, except as revised herein.
(k) Approval of new designs must not be granted until the following has been completed and submitted as part of the application:
1. Establish a design mix and production process. Record the aggregate material, size and gradation; type and strength of cement; cement to aggregate ratios; water to cement ratio; and any other pertinent design data. Record the production process, for example; measuring equipment, batch sizes, mixing sequence, transportation techniques from mixer to mold, pouring techniques with consolidation of concrete methods detailed.
2. Construct three tanks using the design mix.
3. Test two sets of cylinders from the design mix at 7 days and 28 days.
4. Structural proof test three tanks to the design strength in accordance with paragraph 62-6.013(1)(b), F.A.C., for tanks having an effective capacity of 1,350 gallons or less.
5. Structural proof test one tank to the design strength in accordance with paragraph 62-6.013(1)(b), F.A.C., for tanks having an effective capacity greater than 1,350 gallons but not more than 1,500 gallons.
6. Structural proof test one tank or provide tank strength calculations in accordance with paragraph 62-6.013(1)(b), F.A.C., for tanks having an effective capacity exceeding 1,500 gallons.
7. Verify that the manufacturer is not removing tanks from the producer’s facility prior to the tank achieving 75% of the design compressive strength. Record how this is accomplished.
(6) The following structural requirements are applicable to fiberglass and polyethylene tanks:
(b) Fiberglass tanks must be constructed so that all parts of the tank meet the following mechanical requirements. A test report from an independent testing laboratory is required to substantiate that individual tank designs and material formulations meet these requirements.
1. Ultimate tensile strength – minimum 12,000 psi when tested in accordance with ASTM D-638-14, Standard Test Method for Tensile Properties of Plastics (2014), herein adopted and incorporated by reference. This standard has been deemed copyright protected and is available from the publisher at ASTM International, P.O. Box C700, West Conshohocken, Pennsylvania 19428-2959, or at publisher’s website at www.astm.org/, and is available for inspection as provided in subsection (14) below.
2. Flexural strength – minimum 19,000 psi when tested in accordance with ASTM D-790-17, Standard Test Methods for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical Insulating Materials (2017), herein adopted and incorporated by reference. This standard has been deemed copyright protected and is available from the publisher at ASTM International, P.O. Box C700, West Conshohocken, Pennsylvania 19428-2959, or at publisher’s website at www.astm.org/, and is available for inspection as provided in subsection (14) below.
3. Flexural modulus of elasticity – minimum 800,000 psi when tested in accordance with ASTM D-790-17 Standard Test Methods for Flexural Properties of Unreinforced and Reinforced Plastics and Electrical Insulating Materials, incorporated by reference in subparagraph 62-6.013(6)(b)2., F.A.C., effective 06-21-2022.
4. Not less than 30 percent of the total weight of the fiberglass tank must be fiberglass reinforcement.
5. Internal surfaces must be coated with an appropriate gel coating or resin to provide a smooth, pore-free, watertight surface.
(d) Approval of new designs must not be granted until the following has been completed and submitted as part of the application:
1. Establish a design mix and production process. Record the material specifications and other pertinent design data. Record the production process, for example; measuring equipment, batch sizes, mixing sequence, transportation techniques from mixer to mold, and spraying techniques.
2. Construct three tanks using the design mix.
3. Test two sets of test strips from the design mix.
4. Structural proof test three tanks to the design strength per paragraph 62-6.013(1)(c), F.A.C., for tanks having an effective capacity of 1,350 gallons or less.
5. Structural proof test one tank to the design strength in accordance with paragraph 62-6.013(1)(c), F.A.C., for tanks having an effective capacity greater than 1,350 gallons.
6. Verify that the manufacturer is not planning to relocate the tanks prior to the tanks achieving 75% of the design compressive strength. Record how this is accomplished.
(7) Grease interceptors are not required for a residence. However, one or more grease interceptors are required where grease waste is produced in quantities that could otherwise cause line stoppage or hinder sewage disposal. The design of grease interceptors must be based on standards found in paragraph (a) below. In addition, the following general requirements found in paragraphs (b), (c), and (d), apply when determining the proper use and installation of a grease interceptor used as a component of an onsite sewage treatment and disposal system.
(d) Sizing of grease interceptors must be based on the equations below. The minimum volume of any grease interceptor must be 750 gallons and the maximum volume of an individual single grease interceptor chamber must be 1,250 gallons. When the required effective capacity of the grease interceptor is greater than 1,250 gallons, installation of multi-chambered grease interceptors or grease interceptors in series is required.
1. Restaurants: (S) X (GS) X (HR/12) X (LF) = effective capacity of grease interceptor in gallons.
S = number of seats in the dining area.
GS = gallons of wastewater per seat; use 25 gallons for ordinary restaurant, use 10 gallons for single service article restaurants.
HR = number of hours establishment is open.
LF = loading factor: use 2.0 interstate highways, 1.5 other freeways, 1.25 recreational areas,
1.0 main highways, and 0.75 other roads.
2. Other type establishments with commercial kitchens: (M) X (GM) X (LF) = effective capacity of grease interceptor in gallons.
M = meals prepared per day.
GM = gallons of wastewater per meal: use 5 gallons.
LF = loading factor: use 1.00 with dishwashing and 0.75 without dishwashing.
(8) Laundry tank or laundry waste interceptor – when a separate system is installed to accept effluent from a single home washing machine only, the laundry tank or laundry waste interceptor for such system must meet the following minimum standards:
(9) Pump tanks and pumps – when used as part of an onsite sewage treatment and disposal system, the following requirements must apply to all pump tanks manufactured for use in Florida unless specifically exempted by other provisions of these rules:
(c) When a pump is used as part of a system, the following conditions must apply.
1. Pumps used to distribute sewage effluent must be certified by the manufacturer to be suitable for such purpose or pumps must be designed in accordance with the Sump and Sewage Pump Manufacturers Association’s Recommended Standards for Sump, Effluent and Sewage Pumps (2019 Revision) for the purpose intended, herein adopted and incorporated by reference. This standard has been deemed copyright protected and is available from the publisher at the Sump and Sewage Pump Manufacturers Association, P.O. Box 44071, Indianapolis, Indiana, 46244, or at publisher’s website at www.sspma.org/, and is available for inspection as provided in subsection (14) below. The use of a timer as part of any pump system is not allowed unless it is part of a design submitted by an engineer, or Master Septic Tank Contractor, and is approved by the Department.
2. An audio and visual high water alarm must be provided in a conspicuous location visible by system users to warn of pump failures. If the alarm is located outdoors, the alarm must be waterproof and specified by the manufacturer for outdoor use.
3. A pump must be placed in a separate compartment or tank, except when using a pump chamber insert. Except as noted below, any compartment or tank in which a pump is located must not be considered when determining total effective capacity of a septic tank.
4. A pump chamber insert may, at the applicant’s discretion, be used to house a pump inside a septic tank. If a pump chamber insert is used, it must be approved for use by the Department. Approval must be based on the ability of the pump chamber insert to effectively filter solids from the effluent prior to intake by the pump. The efficiency of solids removal by the pump chamber insert must be at least equal to a currently approved outlet filter device. Pump chamber inserts that do not meet these criteria must not be approved and must not be used. The filter device used as part of the pump chamber insert must be considered to meet the requirement of using an outlet filter device for purposes of subsection 62-6.008(2), F.A.C. The tank or compartment used to house the pump chamber insert must be included in calculating the minimum effective capacity of the tank, subject to the following conditions:
a. When placed in a compartmentalized tank or tanks in series, the pump chamber insert must be placed in the last chamber or tank. When placed in a single compartment tank, the pump chamber insert must be placed as close to the outlet side of the tank as possible. In no case must the insert be placed farther than 1/2 the distance to the inlet as measured from the outlet of the tank. The pump chamber insert and filter must be accessible for routine maintenance. The manufacturer must provide instructions on how to maintain the filter unit and the insert device.
b. Pump levels must be set so that the high water alarm is activated when the liquid level of the tank will exceed the height of the inlet invert of the tank. The pump-on switch must be set to maintain the greatest possible effective capacity of the tank, and in no case must it be set higher than 1 inch below the inlet invert. Floats used for operation of the pump must be allowed outside the pump chamber insert.
c. The intake openings of the pump chamber insert must not be located within 12 inches of the bottom of the tank, or within 12 inches of the liquid level line of the tank.
d. The volume discharged by the pump must not exceed 1/4 of the average daily sewage flow in any dose.
e. A pump chamber insert must not be used when the total absorption area for the system is greater than 1,000ꞌ square feet, or when automatic dosing is required.
f. For new system installations, in addition to the requirements above, the total septic tank capacity must include the required minimum septic tank effective capacity, which must be contained below the pump-off switch level, plus the pumping tank capacity per Table II, plus the required 15% airspace.
g. For repair installations, in addition to the requirements of subparagraphs a. through e. above, pump chamber inserts must not be used in an existing septic tank of less than 750 gallons effective capacity. In addition, the minimum tank liquid depth must be 36 inches below the pump-off switch level and the minimum effective capacity contained below the pump-off switch level must be within two tank sizes of that required in Rule 62-6.008, F.A.C., Table II. The total septic tank capacity must include the minimum effective capacity within two tank sizes of required tank size, plus dosing capacity, plus dosing reserve capacity equal to the dosing capacity, plus freeboard or air space capacity which is equal to 15% of the minimum effective capacity.
(10) Electrical conduit, effluent dosing pipe, aeration lines, and vent pipe requirements:
(b) Electrical conduit, effluent dosing pipe, aeration lines, and vent pipes must exit or enter the onsite sewage tank using one of the following methods:
1. Through a tank outlet using plumbing fittings and reducers to produce a watertight seal,
2. Through a hole drilled or cut through an attached riser or a notch cut into the bottom of the attached riser and above the top of the tank. All such penetrations must be sealed water-tight.
3. Through a maximum four-inch access port installed in the tank lid or top of the tank, or the wall of the tank above the liquid level by the manufacturer as approved by the Department. After installation the port must be sealed watertight with a bonding compound per paragraph 62-6.013(2)(i), F.A.C., or a seal meeting the requirements for outlet devices per paragraph 62-6.013(2)(f), F.A.C. Unused ports must be made watertight.
4. Through a 2 to 4 inch notch installed at the top of a tank immediately beneath the lid by the manufacturer as approved by the Department. After installation, the notch must be sealed watertight with a bonding compound per paragraph 62-6.013(2)(i), F.A.C.
(11) Transportation and installation.
(12) Repair of tanks – Repairs are allowed for tanks prior to shipment per ASTM, ACI, PCA standards and publications and National Precast Concrete Association (NPCA), Septic Tank Manufacturing Best Practices Manual (2010), herein adopted and incorporated by reference. This document has been deemed copyright protected and is available from the publisher at the National Precast Concrete Association, 1320 City Centre Drive, Suite 200, Carmel, Indiana 46032, or at publisher’s website at www.precast.org/, and is available for inspection as provided in subsection (14) below. Tanks damaged after they leave the manufacturer’s facility may be repaired for the following defects:
(13) Removal of removable compartment walls from installed tanks. Removal of an existing tank compartment wall is permissible if all of the following conditions are met:
Rulemaking Authority 381.0065(3)(a), 381.0065(4)(e) FS. Law Implemented 381.0065 FS. History–New 12-22-82, Amended 2-5-85, Formerly 10D-6.55, Amended 3-17-92, 1-3-95, Formerly 10D-6.055, Amended 11-19-97, 2-3-98, 3-22-00, 4-21-02, 5-24-04, 11-26-06, 6-25-09, 4-28-10, Formerly 64E-6.013, Amended 6-21-22, 6-8-26.