Fla. Admin. Code R. 60D-4.004
(1) New construction and additions:
(a) This Rule applies to all of the following:
1. New facilities constructed for the use of a state agency.
2. Additions to existing state-owned facilities.
3. Renovations to existing state-owned facilities shall be allowed to comply with subsection 60D-4.004(1), F.A.C., when the agency determines that the scope of the proposed renovation addresses enough energy-consuming equipment and architectural elements to comply with the whole-building energy performance requirements as described in this Rule. Otherwise, subsection 60D-4.004(2), (3) or (4), F.A.C., shall apply.
(b) Alternative designs:
(IV) Additional alternative designs, if developed, shall demonstrate equal or less energy consumption than the maximum allowable energy consumption described in in sub-subparagraph (1)(b)6.a. of this section.
c. For renovations pursuant to subparagraph 60D-4.004(1)(a)3., F.A.C.:
(III) Additional alternative designs, if developed, shall demonstrate equal or less energy consumption than the maximum allowable energy consumption described in in sub-subparagraph (1)(b)6.a. of this section.
d. The percentage reduction (PR) shall be calculated as follows:
PR = 100 × (required consumption – proposed consumption) / required consumption
1. At least three alternative designs shall be developed for the agency’s consideration.
2. Each alternative design shall be modeled with a computer-based simulation program to simulate total energy usage for the entire building or addition.
3. Each alternative design shall be modeled with the same computer-based simulation program.
4. The computer-based simulation program shall comply with Rule 60D-4.005, F.A.C.
5. The computer-based simulation shall include HVAC heat load calculations and equipment sizing. The HVAC heat load calculations shall include all internal building heat loads.
6. Specific energy performance requirements:
a. Maximum allowable energy consumption: The maximum allowable annual energy consumption for alternative designs shall be based on the minimum energy performance requirement of the sustainable building rating adopted by the agency in accordance with Section 255.257(4)(a), F.S.
b. For new construction and additions:
(c) Selection of preferred design:
1. The selection of the preferred alternative design shall be made by the agency only after a life-cycle cost analysis is performed in compliance with Rule 60D-4.006, F.A.C.
2. For new facilities and additions, construction shall proceed only after the life-cycle cost analysis has been evaluated by the department for technical correctness and completeness, pursuant to Section 255.254(1), F.S.
(2) Major equipment-related projects:
(a) This Rule applies to renovations in existing state-owned facilities whenever any one of the following items of energy-consuming equipment is installed new or replaced:
1. Chillers with a total cooling capacity of 25 tons (300,000 BTUH) or greater.
2. Boilers with a total input heating capacity of 300,000 BTUH (88 kW) or greater.
3. Unitary HVAC equipment (single and multiple units) within a single building where the total cooling or heating capacity being installed in the project is 25 tons (300,000 BTUH) or greater. Unitary HVAC equipment as defined here shall include:
a. Self-contained air-conditioners and heat pumps;
b. Complete split system air-conditioners and heat pumps, which shall be defined here as the both the condenser and evaporator sections of the system;
c. Fuel-burning furnaces;
d. Electric heaters.
4. Service water heaters (single and multiple units) within a single building where the total input heating capacity being installed in the project is 300,000 BTUH (88 kW) or greater.
5. Lighting fixtures within a single building where the total lighting capacity being installed in the project is 30 kW or greater.
(d) Alternative designs:
(A) Exceptions:
i. The existing supply or return well has failed and is not repairable.
ii. The permit application for groundwater consumption has been denied by the authority having jurisdiction or will not be renewed.
iii. The amount of groundwater available from the well system or permitted by the authority having jurisdiction is insufficient for proper or reliable HVAC equipment operation.
iv. New water-cooled or related equipment will not fit in the available space.
v. The space available to install new water-cooled or related equipment does not comply with the clearance recommendations or requirements of the equipment manufacturer.
vi. Applicable codes and ordinances that prohibit the installation of such equipment.
(A) Exceptions:
(II) Lamp and ballast replacements for existing lighting fixtures shall be considered an acceptable alternative design.
c. Service water heating equipment:
i. A new centrifugal type chiller will not fit in the available space.
ii. The space available to install a new centrifugal type chiller or related equipment does not comply with the clearance recommendations or requirements of the equipment manufacturer.
iii. Applicable codes and ordinances that prohibit the installation of such equipment.
b. Lighting equipment:
1. At least three alternative designs shall be developed for the agency’s consideration.
2. Each alternative design shall be modeled with a computer-based simulation program to simulate the total energy usage of all energy-consuming equipment being installed new or replaced within the project.
Exception: For projects where lighting fixtures, service water heaters, or a combination of both are the only energy-consuming equipment being installed new or replaced, the energy usage of the alternative designs shall be considered unrelated to the effects of weather and therefore may be developed manually without a computer-based simulation at the agency’s discretion.
3. The computer-based simulation shall include HVAC heat load calculations and equipment sizing for projects that include new or replacement HVAC equipment. The HVAC heat load calculations shall include all internal building heat loads for the areas affected by the renovation.
4. The computer-based simulation program shall comply with Rule 60D-4.005, F.A.C.
5. Specific energy performance requirements:
a. Each alternative design shall meet or exceed the minimum energy performance requirements of the sustainable building rating adopted by the agency in accordance with Section 255.257(4)(a), F.S.
b. Each alternative design shall demonstrate different energy consumption.
6. Equipment type requirements:
a. HVAC equipment:
(3) Minor equipment-related projects:
(a) This Rule applies to renovations in existing state-owned facilities whenever any of the following items of energy-consuming equipment are installed new or replaced:
1. Chillers with a total cooling capacity of less than 25 tons (300,000 BTUH).
2. Boilers with a total input heating capacity of less than 300,000 BTUH (90 kW).
3. Unitary HVAC equipment (single and multiple units) within a single building where the total cooling or heating capacity being installed in the project is less than 25 tons (300,000 BTUH). Unitary HVAC equipment as defined here shall include:
a. Self-contained air-conditioners and heat pumps;
b. Complete split system air-conditioners and heat pumps, which shall be defined here as both the condenser and evaporator sections of the system;
c. Fuel-burning furnaces;
d. Electric heaters.
4. Service water heaters (single and multiple units) within a single building where the total input heating capacity being installed in the project is less than 300,000 BTUH (88 kW).
5. Lighting fixtures within a single building where the total lighting capacity being installed in the project is less than 30 kW.
(d) Alternative designs:
1. There is no minimum number of alternative designs required.
2. Specific energy performance requirement: Each alternative design shall meet or exceed the minimum energy performance requirements of the sustainable building rating adopted by the agency in accordance with Section 255.257(4)(a), F.S.
(4) Guaranteed energy, water, and wastewater performance savings projects:
(g) Alternative designs:
1. The agency shall specify the number of alternative designs. One alternative design shall be considered acceptable.
2. Specific energy performance requirement: Each alternative design shall meet or exceed the minimum energy performance requirements of the sustainable building rating adopted by the agency in accordance with Section 255.257(4)(a), F.S.
(h) Selection of preferred design:
1. The selection of the preferred design or scope of work shall be made by the agency only after an investment grade energy audit as defined in Section 489.145(3)(f), F.S., is reviewed by the department in accordance with Sections 489.145(4)(c) and 489.145(6), F.S.
2. Life-cycle cost analysis:
a. The investment grade energy audit required in Section 489.145(6), F.S., shall include a life-cycle cost analysis for each alternative design and the baseline energy model that complies with subsection 60D-4.004(6), F.A.C.
b. The life-cycle cost analysis for the baseline energy model shall incorporate all reasonably-expected costs based on the computer-based simulation throughout the analysis period assuming no energy conservation measures are employed.
c. The results of the life-cycle cost analysis as described in Rule 60D-4.006, F.A.C., shall not replace any part of the investment grade energy audit required in Section 489.145(6), F.S., or be used as the basis of guaranteed cost savings, but shall be based on the information contained within the investment grade energy audit in accordance with Rule 60D-4.006, F.A.C. The life-cycle cost analysis as described in Rule 60D-4.006, F.A.C., shall be used by the agency and the department in conjunction with the investment grade energy audit to assist in the evaluation of the project’s life-cycle costs pursuant to Sections 489.145(4)(c) and 255.255(1), F.S.
Rulemaking Authority 255.255 FS., Section 61, Chapter 210-176, Laws of Florida. Law Implemented 255.255, 255.256 FS. History–New 5-26-76, Formerly 13D-10.04, 13D-10.004, Amended 3-17-10.