The following are minimum standards of construction and specified minimum essential physical plant requirements which must be met when providing second trimester abortions.
- (1) Consultation room(s) with adequate private space specifically designated for interviewing, counseling, and medical evaluations;
- (2) Dressing rooms designated for staff and patients;
- (3) Handwashing station(s) equipped with a mixing valve and wrist blades and located in each patient exam/procedure room or area;
- (4) Private procedure room(s) with light and ventilation for abortion procedures;
- (5) Post-procedure recovery room(s) equipped to meet the patient’s needs;
- (6) Emergency exits wide enough to accommodate a standard stretcher or gurney;
- (7) Cleaning and sterilizing area(s) for the cleaning and sterilizing of instruments;
- (8) Secure storage area(s) for the storage of medical records and necessary equipment and supplies; and,
- (9) If not otherwise required by the Florida Building Code, at least one general use toilet room equipped with a hand washing station.
Rulemaking Authority 390.012(1) FS. Law Implemented 390.012(3)(a) FS. History–New 9-25-06, Amended 4-5-17.