49 C.F.R. § 180.209
(a) Periodic qualification of cylinders. Each specification cylinder that becomes due for periodic requalification, as specified in the following table, must be requalified and marked in conformance with the requirements of this subpart. Requalification records must be maintained in accordance with § 180.215. Table 1 follows:
| Specification under which cylinder was made | Minimum test pressure (psig) 2 | Requalification period (years) |
|---|---|---|
| 3 | 3000 psig | 5. |
| 3A, 3AA | 5/3 times service pressure, except non-corrosive service (see § 180.209(g)) | 5, 10, or 12 (see § 180.209(b), (f), (h), and (j)). |
| 3AL | 5/3 times service pressure | 5 or 12 (see § 180.209(j) and (m) 4). |
| 3AX, 3AAX | 5/3 times service pressure | 5. |
| 3B, 3BN | 2 times service pressure (see § 180.209(g)) | 5 or 10 (see § 180.209(f)). |
| 3E | Test not required | |
| 3HT | 5/3 times service pressure | 3 (see §§ 180.209(k) and 180.213(c)). |
| 3T | 5/3 times service pressure or UE3 | 5. |
| 4AA480 | 2 times service pressure (see § 180.209(g)) | 5 or 10 (see § 180.209(h)). |
| 4B, 4BA, 4BW, 4B-240ET | 2 times service pressure, except non-corrosive service (see § 180.209(g)) | 5, 7, 10, or 12 (see § 180.209(e), (f), and (j)). |
| 4D, 4DA, 4DS | 2 times service pressure | 5. |
| 4E | 2 times service pressure, except non-corrosive service (see § 180.209(g)) | 5, 10, or 12 (see § 180.209(e)). |
| 4L | Test not required | |
| 8, 8AL | 10 or 20 (see § 180.209(i)). | |
| Exemption or special permit cylinder | See current exemption or special permit, or UE3 as allowed by CGA C-20 (2014) | See current exemption or special permit. |
| Foreign cylinder (see § 173.301(j) of this subchapter for restrictions on use) | As marked on cylinder, but not less than 5/3 of any service or working pressure marking | 5 (see §§ 180.209(l) and 180.213(d)(2)). |
| 1 Any cylinder not exceeding two inches outside diameter and less than two feet in length is excepted from volumetric expansion test. | ||
| 2 For cylinders not marked with a service pressure, see § 173.301a(b) of this subchapter. | ||
| 3 Minimum test pressure is not applicable to those cylinders and tubes requalified using ultrasonic examination. | ||
| 4 This provision does not apply to cylinders used for carbon dioxide, fire extinguisher, or other industrial gas service. |
(b) DOT 3A or 3AA cylinders.
(1) A cylinder conforming to specification DOT 3A or 3AA with a water capacity of 56.7 kg (125 lb) or less that is removed from any cluster, bank, group, rack, or vehicle each time it is filled, may be requalified every ten years instead of every five years, provided the cylinder conforms to all of the following conditions:
(g) Visual inspections. A cylinder conforming to a specification listed in the table in this paragraph (g) and used exclusively in the service indicated may, instead of a periodic hydrostatic test, be given a complete external visual inspection at the time periodic requalification becomes due. External visual inspection must be in conformance with CGA C-6 or C-6.3, as applicable. When this inspection is used instead of hydrostatic testing, subsequent inspections are required at five-year intervals after the first inspection. Inspections must be made only by persons holding a current RIN and the results recorded and maintained in conformance with § 180.215. Records must include: Date of inspection (month and year); DOT-specification number; cylinder identification (registered symbol and serial number, date of manufacture, and owner); type of cylinder protective coating (including statement as to need of refinishing or recoating); conditions checked (e.g., leakage, corrosion, gouges, dents or digs in shell or heads, broken or damaged footring or protective ring or fire damage); and disposition of cylinder (returned to service, returned to cylinder manufacturer for repairs or condemned). A cylinder passing requalification by the external visual inspection must be marked in conformance with § 180.213. Specification cylinders must be in exclusive service as shown in table 2 to this paragraph (g):
| Cylinders conforming to— | Used exclusively for— |
|---|---|
| DOT 3A, DOT 3AA, DOT 3A480X, DOT 4AA480 | Anhydrous ammonia of at least 99.95% purity. |
| DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B, DOT 4B, DOT 4BA, DOT 4BW | Butadiene, inhibited, that is commercially free from corroding components. |
| DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B. DOT 4AA480, DOT 4B, DOT 4BA, DOT 4BW | Cyclopropane that is commercially free from corroding components. |
| DOT 3A, DOT 3AA, DOT 3A480X, DOT 4B, DOT 4BA, DOT 4BW, DOT 4E | Chlorinated hydrocarbons and mixtures thereof that are commercially free from corroding components. |
| DOT 3A, DOT 3AA, DOT 3A480X, DOT 4B, DOT 4BA, DOT 4BW, DOT 4E | Fluorinated hydrocarbons and mixtures thereof that are commercially free from corroding components. |
| DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B, DOT 4B, DOT 4BA, DOT 4BW, DOT 4E | Liquefied hydrocarbon gas that is commercially free of corroding components. |
| DOT 3A, DOT 3AA, DOT 3A480X, DOT 3B, DOT 4B, DOT 4BA, DOT 4BW, DOT 4E | Liquefied petroleum gas that meets the detail requirements limits in Table 1 of ASTM 1835, Standard Specification for Liquefied Petroleum (LP) Gases (incorporated by reference; see § 171.7 of this subchapter) or an equivalent standard containing the same limits. |
| DOT 3A, DOT 3AA, DOT 3B, DOT 4B, DOT 4BA, DOT 4BW, DOT 4E | Methylacetylene-propadiene, stabilized, that is commercially free from corroding components. |
| DOT 3A, DOT 3AA, DOT 3B, DOT 4B, DOT 4BA, DOT 4BW, DOT 4E | Propylene that is commercially free from corroding components. |
| DOT 3A, DOT 3AA, DOT 3B, DOT 4B, DOT 4BA, DOT 4BW | Anhydrous mono, di, trimethylamines that are commercially free from corroding components. |
| DOT 4B240, DOT 4BW240 | Ethyleneimine, stabilized. |
| DOT 4BW | Alkali metal alloys, liquid, n.o.s., Alkali metal dispersions or Alkaline earth metal dispersions, Potassium, Potassium Sodium alloys and Sodium that are commercially free of corroding components. |
(i) Requalification of DOT-8 series cylinders.
(1) Each owner of a DOT-8 series cylinder used to transport acetylene must have the cylinder shell and the porous filler requalified in accordance with CGA Pamphlet C-13 (IBR, see § 171.7 of this subchapter). Requalification must be performed in accordance with the following schedule:
| Date of cylinder manufacture | Shell (visual inspection) requalification | Porous filler requalification | ||
|---|---|---|---|---|
| Initial | Subsequent | Intial | Subsequent | |
| Before January 1, 1991 | Before January 1, 2001 | 10 years | Before January 1, 2011 | Not required. |
| On or after January 1, 1991 | 10 years 1 | 10 years | 5 to 20 years 2 | Not required. |
| 1 Years from the date of cylinder manufacture. | ||||
| 2 No sooner than 5 years, and no later than 20 years from the date of manufacture. |
(j) Cylinder used as a fire extinguisher. Only a DOT-specification cylinder used as a fire extinguisher in conformance with § 173.309(a) of this subchapter may be requalified in conformance with this paragraph (j). The testing procedures, calibration of the testing equipment, accuracy of the pressure indicating device, accuracy of the testing equipment must be as prescribed in CGA C-1.
(1) A DOT 4B, 4BA, 4B240ET or 4BW cylinder used as a fire extinguisher may be tested as follows:
(i) For a cylinder with a water capacity of 5.44 kg (12 pounds) or less, by the water-jacket, direct expansion or proof pressure test methods as prescribed in CGA C-1. A requalification must be performed by the end of 12 years after the original test date and at 12-year intervals thereafter.
(ii) For a cylinder having a water capacity over 5.44 kg (12 pounds), by the water-jacket, direct expansion or proof pressure test methods as prescribed in CGA C-1. For the water-jacket or direct expansion test, the requalification must be performed by the end of 12 years after the original test date and at 12-year intervals theafter. For the proof-pressure test, a requalification must be performed by the end of 12 years after the original test date and at seven (7) year intervals.
(2) A DOT 3A, 3AA, or 3AL cylinder must be requalified by:
(l) Requalification of foreign cylinders filled for export. A cylinder manufactured outside the United States, other than as provided in §§ 171.12(a) and 171.23(a) of this subchapter, that has not been manufactured, inspected, tested and marked in accordance with part 178 of this subchapter may be filled with compressed gas in the United States, and shipped solely for export if it meets the following requirements, in addition to other requirements of this subchapter:
(m) DOT-3AL cylinders manufactured of 6351-T6 aluminum alloy. In addition to the periodic requalification and marking described in § 180.205, each cylinder manufactured of aluminum alloy 6351-T6 used in self-contained underwater breathing apparatus (SCUBA), self-contained breathing apparatus (SCBA), or oxygen service must be requalified and inspected for sustained load cracking in accordance with the non-destructive examination method described in the following table. Each cylinder with sustained load cracking that has expanded into the neck threads must be condemned in accordance with § 180.205(j). This paragraph (m) does not apply to cylinders used for carbon dioxide, fire extinguisher, or other industrial gas service.
| Requalification requirement | Examination procedure 1 | Sustained Load Cracking Condemnation Criteria 2 | Requalification period (years) |
|---|---|---|---|
| Eddy current examination combined with visual inspection | Eddy current—In accordance with Appendix C of this partVisual inspection—In accordance with CGA Pamphlet C-6.1 (IBR; see § 171.7 of this subchapter) | Any crack in the neck or shoulder of 2 thread lengths or more | 5 |
| 1 The requalifier performing eddy current must be familiar with the eddy current equipment and must standardize (calibrate) the system in accordance with the requirements provided in Appendix C to this part. | |||
| 2 The eddy current must be applied from the inside of the cylinder's neck to detect any sustained load cracking that has expanded into the neck threads. |
Editorial Note:At 71 FR 54397, Sept. 14, 2006, § 180.209 was amended in (a)(1) table 1; however, because of the inaccurate amendatory language, the amendment could not be incorporated.
[67 FR 51660, Aug. 8, 2002, as amended at 68 FR 24662, May 8, 2003; 68 FR 55544, Sept. 26, 2003; 68 FR 48572, Aug. 14, 2003; 68 FR 75764, Dec. 31, 2003; 70 FR 73166, Dec. 9, 2005; 71 FR 51128, Aug. 29, 2005; 72 FR 55696, Oct. 1, 2007; 74 FR 53189, Oct. 16, 2009; 81 FR 3685, Jan. 21, 2016; 81 FR 35545, June 2, 2016; 85 FR 68797, Oct. 30, 2020; 85 FR 75716, Nov. 25, 2020; 85 FR 85434, Dec. 28, 2020; 89 FR 15667, Mar. 4, 2024]