46 C.F.R. § 181.500
(b) Table 1 to § 181.500(b) indicates the minimum required classification for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table.
| Space | Portable fire extinguishers | |
|---|---|---|
| Minimum required rating | Quantity and location | |
| Operating Station | 10-B:C | 1. |
| Machinery Space | 40-B:C | 1 in the vicinity of the exit. |
| Open Vehicle Deck | 40-B | 1 for every 10 vehicles. |
| Accommodation Space | 2-A | 1 each for each 2,500 square feet (232.3 square meters) or fraction thereof. |
| Galley | 40-B:C | 1. |
| Pantry, concession stand | 2-A | 1 in the vicinity of the exit. |
[USCG-2012-0196, 81 FR 48300, July 22, 2016, as amended by USCG-2020-0519, 89 FR 76707, Sept. 18, 2024]