46 C.F.R. § 169.567
(a) The minimum number of portable fire extinguishers required on each vessel is determined by the Officer in Charge, Marine Inspection, in accordance with table 1 to § 169.567(a) and other provisions of this subpart.
| Space | Portable fire extinguishers | |
|---|---|---|
| Minimum required rating | Quantity and location | |
| Propulsion machinery space without fixed extinguishing system | 40-B:C | 2. |
| Propulsion machinery space with fixed extinguishing system | 40-B:C | 1 in the vicinity of the exit. |
| Living space and open boats | 2-A | 1 per 1,000 cubic foot of space. |
| Galley (without fixed system) | 40-B:C | 1 per 500 cubic foot. |
| Spare Units | 2-A | 10 percent of the required number rounded up. |
| 40-B:C | 10 percent of the required number rounded up. |