- (a) Minimum safety and trip controls required for specific types of automated vital systems are listed in table 1 to § 62.35-50.
- (b) Safety trip controls must not operate as a result of failure of the normal electrical power source unless it is determined to be the failsafe state.
- (c) Automatic operation of a safety control must be alarmed in the machinery spaces and at the cognizant remote-control location.
- (d) Local manual safety trip controls must be provided for all main boilers, turbines, and internal combustion engines.
(e) Automatic safety trip control systems must—
- (1) Be provided where there is an immediate danger that a failure will result in serious damage, complete breakdown, fire, or explosion;
- (2) Require manual reset prior to renewed operation of the equipment; and
- (3) Not be provided if safety limit controls provide a safe alternative and trip would result in loss of propulsion.
Note 1 to paragraph (a): Safety control systems include automatic and manual safety trip controls and automatic safety limit controls.
[CGD 81-030, 53 FR 17838, May 18, 1988, as amended by USCG-2020-0634, 89 FR 50191, June 12, 2024]