10 C.F.R. § 431.306
(a) Each walk-in cooler or walk-in freezer manufactured on or after January 1, 2009, shall—
(3) Contain wall, ceiling, and door insulation of at least R-25 for coolers and R-32 for freezers, except that this paragraph shall not apply to:
(5) For evaporator fan motors of under 1 horsepower and less than 460 volts, use—
(6) For condenser fan motors of under 1 horsepower, use—
(b) Each walk-in cooler or walk-in freezer with transparent reach-in doors manufactured on or after January 1, 2009, shall also meet the following specifications:
(2) Transparent reach-in doors for walk-in coolers and windows in walk-in cooler doors shall be—
(c) Walk-in cooler and freezer display doors. All walk-in cooler and walk-in freezer display doors manufactured starting June 5, 2017, must satisfy the following standards:
| Class descriptor | Class | Equations formaximum energyconsumption(kWh/day) * |
|---|---|---|
| Display Door, Medium Temperature | DD.M | 0.04 × Add + 0.41. |
| Display Door, Low Temperature | DD.L | 0.15 × Add + 0.29. |
| *Add represents the surface area of the display door. |
(d) Walk-in cooler and freezer non-display doors. All walk-in cooler and walk-in freezer non-display doors manufactured starting on June 5, 2017, must satisfy the following standards:
| Class descriptor | Class | Equations formaximum energyconsumption(kWh/day) * |
|---|---|---|
| Passage door, Medium Temperature | PD.M | 0.05 × And + 1.7. |
| Passage Door, Low Temperature | PD.L | 0.14 × And + 4.8. |
| Freight Door, Medium Temperature | FD.M | 0.04 × And + 1.9. |
| Freight Door, Low Temperature | FD.L | 0.12 × And + 5.6. |
| *And represents the surface area of the non-display door. |
(e) Walk-in cooler refrigeration systems. All walk-in cooler and walk-in freezer refrigeration systems manufactured starting on the dates listed in the table, except for walk-in process cooling refrigeration systems (as defined in § 431.302), must satisfy the following standards:
| Equipment class | Minimum AWEF(Btu/W-h)* | Compliance date: equipment manufactured starting on . . . |
|---|---|---|
| Dedicated Condensing System—Medium, Indoor | 5.61 | June 5, 2017. |
| Dedicated Condensing System—Medium, Outdoor | 7.60 | |
| Dedicated Condensing System—Low, Indoor with a Net Capacity (qnet) of: | ||
| < 6,500 Btu/h | 9.091 × 10 −5 × qnet + 1.81 | July 10, 2020. |
| ≥ 6,500 Btu/h | 2.40 | |
| Dedicated Condensing System—Low, Outdoor with a Net Capacity (qnet) of: | ||
| < 6,500 Btu/h | 6.522 × 10−5 × qnet + 2.73 | |
| ≥ 6,500 Btu/h | 3.15 | |
| Unit Cooler—Medium | 9.00 | |
| Unit Cooler—Low with a Net Capacity (qnet) of: | ||
| < 15,500 Btu/h | 1.575 × 10 −5 × qnet + 3.91 | |
| ≥ 15,500 Btu/h | 4.15 | |
| * Where qnet is net capacity as determined in accordance with § 431.304 and certified in accordance with 10 CFR part 429. |
[74 FR 12074, Mar. 23, 2009, as amended at 78 FR 62993, Oct. 23, 2013; 79 FR 32123, June 3, 2014; 80 FR 69838, Nov. 12, 2015; 82 FR 31885, July 10, 2017]