10 C.F.R. § 431.25
(a) Except as provided for fire pump electric motors in paragraph (b) of this section, each general purpose electric motor (subtype I) with a power rating of 1 horsepower or greater, but not greater than 200 horsepower, including a NEMA Design B or an equivalent IEC Design N motor that is a general purpose electric motor (subtype I), manufactured (alone or as a component of another piece of equipment) on or after December 19, 2010, but before June 1, 2016, shall have a nominal full-load efficiency that is not less than the following:
| Motor horsepower/Standard kilowatt equivalent | Nominal full-load efficiency | |||||
|---|---|---|---|---|---|---|
| Open motors(number of poles) | Enclosed motors(number of poles) | |||||
| 6 | 4 | 2 | 6 | 4 | 2 | |
| 1/.75 | 82.5 | 85.5 | 77.0 | 82.5 | 85.5 | 77.0 |
| 1.5/1.1 | 86.5 | 86.5 | 84.0 | 87.5 | 86.5 | 84.0 |
| 2/1.5 | 87.5 | 86.5 | 85.5 | 88.5 | 86.5 | 85.5 |
| 3/2.2 | 88.5 | 89.5 | 85.5 | 89.5 | 89.5 | 86.5 |
| 5/3.7 | 89.5 | 89.5 | 86.5 | 89.5 | 89.5 | 88.5 |
| 7.5/5.5 | 90.2 | 91.0 | 88.5 | 91.0 | 91.7 | 89.5 |
| 10/7.5 | 91.7 | 91.7 | 89.5 | 91.0 | 91.7 | 90.2 |
| 15/11 | 91.7 | 93.0 | 90.2 | 91.7 | 92.4 | 91.0 |
| 20/15 | 92.4 | 93.0 | 91.0 | 91.7 | 93.0 | 91.0 |
| 25/18.5 | 93.0 | 93.6 | 91.7 | 93.0 | 93.6 | 91.7 |
| 30/22 | 93.6 | 94.1 | 91.7 | 93.0 | 93.6 | 91.7 |
| 40/30 | 94.1 | 94.1 | 92.4 | 94.1 | 94.1 | 92.4 |
| 50/37 | 94.1 | 94.5 | 93.0 | 94.1 | 94.5 | 93.0 |
| 60/45 | 94.5 | 95.0 | 93.6 | 94.5 | 95.0 | 93.6 |
| 75/55 | 94.5 | 95.0 | 93.6 | 94.5 | 95.4 | 93.6 |
| 100/75 | 95.0 | 95.4 | 93.6 | 95.0 | 95.4 | 94.1 |
| 125/90 | 95.0 | 95.4 | 94.1 | 95.0 | 95.4 | 95.0 |
| 150/110 | 95.4 | 95.8 | 94.1 | 95.8 | 95.8 | 95.0 |
| 200/150 | 95.4 | 95.8 | 95.0 | 95.8 | 96.2 | 95.4 |
(b) Each fire pump electric motor that is a general purpose electric motor (subtype I) or general purpose electric motor (subtype II) manufactured (alone or as a component of another piece of equipment) on or after December 19, 2010, but before June 1, 2016, shall have a nominal full-load efficiency that is not less than the following:
| Motor horsepower/standard kilowatt equivalent | Nominal full-load efficiency | |||||||
|---|---|---|---|---|---|---|---|---|
| Open motors(number of poles) | Enclosed motors(number of poles) | |||||||
| 8 | 6 | 4 | 2 | 8 | 6 | 4 | 2 | |
| 1/.75 | 74.0 | 80.0 | 82.5 | 74.0 | 80.0 | 82.5 | 75.5 | |
| 1.5/1.1 | 75.5 | 84.0 | 84.0 | 82.5 | 77.0 | 85.5 | 84.0 | 82.5 |
| 2/1.5 | 85.5 | 85.5 | 84.0 | 84.0 | 82.5 | 86.5 | 84.0 | 84.0 |
| 3/2.2 | 86.5 | 86.5 | 86.5 | 84.0 | 84.0 | 87.5 | 87.5 | 85.5 |
| 5/3.7 | 87.5 | 87.5 | 87.5 | 85.5 | 85.5 | 87.5 | 87.5 | 87.5 |
| 7.5/5.5 | 88.5 | 88.5 | 88.5 | 87.5 | 85.5 | 89.5 | 89.5 | 88.5 |
| 10/7.5 | 89.5 | 90.2 | 89.5 | 88.5 | 88.5 | 89.5 | 89.5 | 89.5 |
| 15/11 | 89.5 | 90.2 | 91.0 | 89.5 | 88.5 | 90.2 | 91.0 | 90.2 |
| 20/15 | 90.2 | 91.0 | 91.0 | 90.2 | 89.5 | 90.2 | 91.0 | 90.2 |
| 25/18.5 | 90.2 | 91.7 | 91.7 | 91.0 | 89.5 | 91.7 | 92.4 | 91.0 |
| 30/22 | 91.0 | 92.4 | 92.4 | 91.0 | 91.0 | 91.7 | 92.4 | 91.0 |
| 40/30 | 91.0 | 93.0 | 93.0 | 91.7 | 91.0 | 93.0 | 93.0 | 91.7 |
| 50/37 | 91.7 | 93.0 | 93.0 | 92.4 | 91.7 | 93.0 | 93.0 | 92.4 |
| 60/45 | 92.4 | 93.6 | 93.6 | 93.0 | 91.7 | 93.6 | 93.6 | 93.0 |
| 75/55 | 93.6 | 93.6 | 94.1 | 93.0 | 93.0 | 93.6 | 94.1 | 93.0 |
| 100/75 | 93.6 | 94.1 | 94.1 | 93.0 | 93.0 | 94.1 | 94.5 | 93.6 |
| 125/90 | 93.6 | 94.1 | 94.5 | 93.6 | 93.6 | 94.1 | 94.5 | 94.5 |
| 150/110 | 93.6 | 94.5 | 95.0 | 93.6 | 93.6 | 95.0 | 95.0 | 94.5 |
| 200/150 | 93.6 | 94.5 | 95.0 | 94.5 | 94.1 | 95.0 | 95.0 | 95.0 |
| 250/186 | 94.5 | 95.4 | 95.4 | 94.5 | 94.5 | 95.0 | 95.0 | 95.4 |
| 300/224 | 95.4 | 95.4 | 95.0 | 95.0 | 95.4 | 95.4 | ||
| 350/261 | 95.4 | 95.4 | 95.0 | 95.0 | 95.4 | 95.4 | ||
| 400/298 | 95.4 | 95.4 | 95.4 | 95.4 | ||||
| 450/336 | 95.8 | 95.8 | 95.4 | 95.4 | ||||
| 500/373 | 95.8 | 95.8 | 95.8 | 95.4 |
(c) Except as provided for fire pump electric motors in paragraph (b) of this section, each general purpose electric motor (subtype II) with a power rating of 1 horsepower or greater, but not greater than 200 horsepower, including a NEMA Design B or an equivalent IEC Design N motor that is a general purpose electric motor (subtype II), manufactured (alone or as a component of another piece of equipment) on or after December 19, 2010, but before June 1, 2016, shall have a nominal full-load efficiency that is not less than the following:
| Motor horsepower/Standard kilowatt equivalent | Nominal full-load efficiency | |||||||
|---|---|---|---|---|---|---|---|---|
| Open motors(number of poles) | Enclosed motors(number of poles) | |||||||
| 8 | 6 | 4 | 2 | 8 | 6 | 4 | 2 | |
| 1/.75 | 74.0 | 80.0 | 82.5 | 74.0 | 80.0 | 82.5 | 75.5 | |
| 1.5/1.1 | 75.5 | 84.0 | 84.0 | 82.5 | 77.0 | 85.5 | 84.0 | 82.5 |
| 2/1.5 | 85.5 | 85.5 | 84.0 | 84.0 | 82.5 | 86.5 | 84.0 | 84.0 |
| 3/2.2 | 86.5 | 86.5 | 86.5 | 84.0 | 84.0 | 87.5 | 87.5 | 85.5 |
| 5/3.7 | 87.5 | 87.5 | 87.5 | 85.5 | 85.5 | 87.5 | 87.5 | 87.5 |
| 7.5/5.5 | 88.5 | 88.5 | 88.5 | 87.5 | 85.5 | 89.5 | 89.5 | 88.5 |
| 10/7.5 | 89.5 | 90.2 | 89.5 | 88.5 | 88.5 | 89.5 | 89.5 | 89.5 |
| 15/11 | 89.5 | 90.2 | 91.0 | 89.5 | 88.5 | 90.2 | 91.0 | 90.2 |
| 20/15 | 90.2 | 91.0 | 91.0 | 90.2 | 89.5 | 90.2 | 91.0 | 90.2 |
| 25/18.5 | 90.2 | 91.7 | 91.7 | 91.0 | 89.5 | 91.7 | 92.4 | 91.0 |
| 30/22 | 91.0 | 92.4 | 92.4 | 91.0 | 91.0 | 91.7 | 92.4 | 91.0 |
| 40/30 | 91.0 | 93.0 | 93.0 | 91.7 | 91.0 | 93.0 | 93.0 | 91.7 |
| 50/37 | 91.7 | 93.0 | 93.0 | 92.4 | 91.7 | 93.0 | 93.0 | 92.4 |
| 60/45 | 92.4 | 93.6 | 93.6 | 93.0 | 91.7 | 93.6 | 93.6 | 93.0 |
| 75/55 | 93.6 | 93.6 | 94.1 | 93.0 | 93.0 | 93.6 | 94.1 | 93.0 |
| 100/75 | 93.6 | 94.1 | 94.1 | 93.0 | 93.0 | 94.1 | 94.5 | 93.6 |
| 125/90 | 93.6 | 94.1 | 94.5 | 93.6 | 93.6 | 94.1 | 94.5 | 94.5 |
| 150/110 | 93.6 | 94.5 | 95.0 | 93.6 | 93.6 | 95.0 | 95.0 | 94.5 |
| 200/150 | 93.6 | 94.5 | 95.0 | 94.5 | 94.1 | 95.0 | 95.0 | 95.0 |
(d) Each NEMA Design B or an equivalent IEC Design N motor that is a general purpose electric motor (subtype I) or general purpose electric motor (subtype II), excluding fire pump electric motors, with a power rating of more than 200 horsepower, but not greater than 500 horsepower, manufactured (alone or as a component of another piece of equipment) on or after December 19, 2010, but before June 1, 2016 shall have a nominal full-load efficiency that is not less than the following:
| Motor horsepower/standard kilowatt equivalent | Nominal full-load efficiency | |||||||
|---|---|---|---|---|---|---|---|---|
| Open motors(number of poles) | Enclosed motors(number of poles) | |||||||
| 8 | 6 | 4 | 2 | 8 | 6 | 4 | 2 | |
| 250/186 | 94.5 | 95.4 | 95.4 | 94.5 | 94.5 | 95.0 | 95.0 | 95.4 |
| 300/224 | 95.4 | 95.4 | 95.0 | 95.0 | 95.4 | 95.4 | ||
| 350/261 | 95.4 | 95.4 | 95.0 | 95.0 | 95.4 | 95.4 | ||
| 400/298 | 95.4 | 95.4 | 95.4 | 95.4 | ||||
| 450/336 | 95.8 | 95.8 | 95.4 | 95.4 | ||||
| 500/373 | 95.8 | 95.8 | 95.8 | 95.4 |
(e) For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilowatt ratings listed in any table of energy conservation standards in paragraphs (a) through (d) of this section, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows:
(g) The standards in Table 5 through Table 7 of this section apply only to electric motors, including partial electric motors, that satisfy the following criteria:
(h) Each NEMA Design A motor, NEMA Design B motor, and IEC Design N (including NE, NEY, or NY variants) motor that is an electric motor meeting the criteria in paragraph (g) of this section and with a power rating from 1 horsepower through 500 horsepower, but excluding fire pump electric motors, manufactured (alone or as a component of another piece of equipment) on or after June 1, 2016, but before June 1, 2027, shall have a nominal full-load efficiency of not less than the following:
| Motor horsepower/standard kilowatt equivalent | Nominal full-load efficiency (%) | |||||||
|---|---|---|---|---|---|---|---|---|
| 2 Pole | 4 Pole | 6 Pole | 8 Pole | |||||
| Enclosed | Open | Enclosed | Open | Enclosed | Open | Enclosed | Open | |
| 1/.75 | 77.0 | 77.0 | 85.5 | 85.5 | 82.5 | 82.5 | 75.5 | 75.5 |
| 1.5/1.1 | 84.0 | 84.0 | 86.5 | 86.5 | 87.5 | 86.5 | 78.5 | 77.0 |
| 2/1.5 | 85.5 | 85.5 | 86.5 | 86.5 | 88.5 | 87.5 | 84.0 | 86.5 |
| 3/2.2 | 86.5 | 85.5 | 89.5 | 89.5 | 89.5 | 88.5 | 85.5 | 87.5 |
| 5/3.7 | 88.5 | 86.5 | 89.5 | 89.5 | 89.5 | 89.5 | 86.5 | 88.5 |
| 7.5/5.5 | 89.5 | 88.5 | 91.7 | 91.0 | 91.0 | 90.2 | 86.5 | 89.5 |
| 10/7.5 | 90.2 | 89.5 | 91.7 | 91.7 | 91.0 | 91.7 | 89.5 | 90.2 |
| 15/11 | 91.0 | 90.2 | 92.4 | 93.0 | 91.7 | 91.7 | 89.5 | 90.2 |
| 20/15 | 91.0 | 91.0 | 93.0 | 93.0 | 91.7 | 92.4 | 90.2 | 91.0 |
| 25/18.5 | 91.7 | 91.7 | 93.6 | 93.6 | 93.0 | 93.0 | 90.2 | 91.0 |
| 30/22 | 91.7 | 91.7 | 93.6 | 94.1 | 93.0 | 93.6 | 91.7 | 91.7 |
| 40/30 | 92.4 | 92.4 | 94.1 | 94.1 | 94.1 | 94.1 | 91.7 | 91.7 |
| 50/37 | 93.0 | 93.0 | 94.5 | 94.5 | 94.1 | 94.1 | 92.4 | 92.4 |
| 60/45 | 93.6 | 93.6 | 95.0 | 95.0 | 94.5 | 94.5 | 92.4 | 93.0 |
| 75/55 | 93.6 | 93.6 | 95.4 | 95.0 | 94.5 | 94.5 | 93.6 | 94.1 |
| 100/75 | 94.1 | 93.6 | 95.4 | 95.4 | 95.0 | 95.0 | 93.6 | 94.1 |
| 125/90 | 95.0 | 94.1 | 95.4 | 95.4 | 95.0 | 95.0 | 94.1 | 94.1 |
| 150/110 | 95.0 | 94.1 | 95.8 | 95.8 | 95.8 | 95.4 | 94.1 | 94.1 |
| 200/150 | 95.4 | 95.0 | 96.2 | 95.8 | 95.8 | 95.4 | 94.5 | 94.1 |
| 250/186 | 95.8 | 95.0 | 96.2 | 95.8 | 95.8 | 95.8 | 95.0 | 95.0 |
| 300/224 | 95.8 | 95.4 | 96.2 | 95.8 | 95.8 | 95.8 | ||
| 350/261 | 95.8 | 95.4 | 96.2 | 95.8 | 95.8 | 95.8 | ||
| 400/298 | 95.8 | 95.8 | 96.2 | 95.8 | ||||
| 450/336 | 95.8 | 96.2 | 96.2 | 96.2 | ||||
| 500/373 | 95.8 | 96.2 | 96.2 | 96.2 |
(i) Starting on June 1, 2016, each NEMA Design C motor and IEC Design H (including HE, HEY, or HY variants) motor that is an electric motor meeting the criteria in paragraph (g) of this section and with a power rating from 1 horsepower through 200 horsepower manufactured (alone or as a component of another piece of equipment) shall have a nominal full-load efficiency that is not less than the following:
| Motor horsepower/standard kilowatt equivalent | Nominal full-load efficiency (%) | |||||
|---|---|---|---|---|---|---|
| 4 Pole | 6 Pole | 8 Pole | ||||
| Enclosed | Open | Enclosed | Open | Enclosed | Open | |
| 1/.75 | 85.5 | 85.5 | 82.5 | 82.5 | 75.5 | 75.5 |
| 1.5/1.1 | 86.5 | 86.5 | 87.5 | 86.5 | 78.5 | 77.0 |
| 2/1.5 | 86.5 | 86.5 | 88.5 | 87.5 | 84.0 | 86.5 |
| 3/2.2 | 89.5 | 89.5 | 89.5 | 88.5 | 85.5 | 87.5 |
| 5/3.7 | 89.5 | 89.5 | 89.5 | 89.5 | 86.5 | 88.5 |
| 7.5/5.5 | 91.7 | 91.0 | 91.0 | 90.2 | 86.5 | 89.5 |
| 10/7.5 | 91.7 | 91.7 | 91.0 | 91.7 | 89.5 | 90.2 |
| 15/11 | 92.4 | 93.0 | 91.7 | 91.7 | 89.5 | 90.2 |
| 20/15 | 93.0 | 93.0 | 91.7 | 92.4 | 90.2 | 91.0 |
| 25/18.5 | 93.6 | 93.6 | 93.0 | 93.0 | 90.2 | 91.0 |
| 30/22 | 93.6 | 94.1 | 93.0 | 93.6 | 91.7 | 91.7 |
| 40/30 | 94.1 | 94.1 | 94.1 | 94.1 | 91.7 | 91.7 |
| 50/37 | 94.5 | 94.5 | 94.1 | 94.1 | 92.4 | 92.4 |
| 60/45 | 95.0 | 95.0 | 94.5 | 94.5 | 92.4 | 93.0 |
| 75/55 | 95.4 | 95.0 | 94.5 | 94.5 | 93.6 | 94.1 |
| 100/75 | 95.4 | 95.4 | 95.0 | 95.0 | 93.6 | 94.1 |
| 125/90 | 95.4 | 95.4 | 95.0 | 95.0 | 94.1 | 94.1 |
| 150/110 | 95.8 | 95.8 | 95.8 | 95.4 | 94.1 | 94.1 |
| 200/150 | 96.2 | 95.8 | 95.8 | 95.4 | 94.5 | 94.1 |
(j) Starting on June 1, 2016, each fire pump electric motor meeting the criteria in paragraph (g) of this section and with a power rating of 1 horsepower through 500 horsepower, manufactured (alone or as a component of another piece of equipment) shall have a nominal full-load efficiency that is not less than the following:
| Motor horsepower/standard kilowattequivalent | Nominal full-load efficiency (%) | |||||||
|---|---|---|---|---|---|---|---|---|
| 2 Pole | 4 Pole | 6 Pole | 8 Pole | |||||
| Enclosed | Open | Enclosed | Open | Enclosed | Open | Enclosed | Open | |
| 1/.75 | 75.5 | 82.5 | 82.5 | 80.0 | 80.0 | 74.0 | 74.0 | |
| 1.5/1.1 | 82.5 | 82.5 | 84.0 | 84.0 | 85.5 | 84.0 | 77.0 | 75.5 |
| 2/1.5 | 84.0 | 84.0 | 84.0 | 84.0 | 86.5 | 85.5 | 82.5 | 85.5 |
| 3/2.2 | 85.5 | 84.0 | 87.5 | 86.5 | 87.5 | 86.5 | 84.0 | 86.5 |
| 5/3.7 | 87.5 | 85.5 | 87.5 | 87.5 | 87.5 | 87.5 | 85.5 | 87.5 |
| 7.5/5.5 | 88.5 | 87.5 | 89.5 | 88.5 | 89.5 | 88.5 | 85.5 | 88.5 |
| 10/7.5 | 89.5 | 88.5 | 89.5 | 89.5 | 89.5 | 90.2 | 88.5 | 89.5 |
| 15/11 | 90.2 | 89.5 | 91.0 | 91.0 | 90.2 | 90.2 | 88.5 | 89.5 |
| 20/15 | 90.2 | 90.2 | 91.0 | 91.0 | 90.2 | 91.0 | 89.5 | 90.2 |
| 25/18.5 | 91.0 | 91.0 | 92.4 | 91.7 | 91.7 | 91.7 | 89.5 | 90.2 |
| 30/22 | 91.0 | 91.0 | 92.4 | 92.4 | 91.7 | 92.4 | 91.0 | 91.0 |
| 40/30 | 91.7 | 91.7 | 93.0 | 93.0 | 93.0 | 93.0 | 91.0 | 91.0 |
| 50/37 | 92.4 | 92.4 | 93.0 | 93.0 | 93.0 | 93.0 | 91.7 | 91.7 |
| 60/45 | 93.0 | 93.0 | 93.6 | 93.6 | 93.6 | 93.6 | 91.7 | 92.4 |
| 75/55 | 93.0 | 93.0 | 94.1 | 94.1 | 93.6 | 93.6 | 93.0 | 93.6 |
| 100/75 | 93.6 | 93.0 | 94.5 | 94.1 | 94.1 | 94.1 | 93.0 | 93.6 |
| 125/90 | 94.5 | 93.6 | 94.5 | 94.5 | 94.1 | 94.1 | 93.6 | 93.6 |
| 150/110 | 94.5 | 93.6 | 95.0 | 95.0 | 95.0 | 94.5 | 93.6 | 93.6 |
| 200/150 | 95.0 | 94.5 | 95.0 | 95.0 | 95.0 | 94.5 | 94.1 | 93.6 |
| 250/186 | 95.4 | 94.5 | 95.0 | 95.4 | 95.0 | 95.4 | 94.5 | 94.5 |
| 300/224 | 95.4 | 95.0 | 95.4 | 95.4 | 95.0 | 95.4 | ||
| 350/261 | 95.4 | 95.0 | 95.4 | 95.4 | 95.0 | 95.4 | ||
| 400/298 | 95.4 | 95.4 | 95.4 | 95.4 | ||||
| 450/336 | 95.4 | 95.8 | 95.4 | 95.8 | ||||
| 500/373 | 95.4 | 95.8 | 95.8 | 95.8 |
(k) For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilowatt ratings listed in any table of energy conservation standards in paragraphs (h) through (l) of this section, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows:
(l) The standards in Table 5 through Table 7 of this section do not apply to the following electric motors exempted by the Secretary, or any additional electric motors that the Secretary may exempt:
(m) The standards in tables 8 through 10 of this section apply only to electric motors, including partial electric motors, that satisfy the following criteria:
(n) Starting on June 1, 2027, each NEMA Design A motor, NEMA Design B motor, and IEC Design N (including NE, NEY, or NY variants) motor that is an electric motor meeting the criteria in paragraph (m) of this section and with a power rating from 1 horsepower through 750 horsepower, but excluding fire pump electric motors and air-over electric motors, manufactured (alone or as a component of another piece of equipment) shall have a nominal full-load efficiency of not less than the following:
| Motor horsepower/standard kilowatt equivalent | Nominal full-load efficiency (%) | |||||||
|---|---|---|---|---|---|---|---|---|
| 2 Pole | 4 Pole | 6 Pole | 8 Pole | |||||
| Enclosed | Open | Enclosed | Open | Enclosed | Open | Enclosed | Open | |
| 1/.75 | 77.0 | 77.0 | 85.5 | 85.5 | 82.5 | 82.5 | 75.5 | 75.5 |
| 1.5/1.1 | 84.0 | 84.0 | 86.5 | 86.5 | 87.5 | 86.5 | 78.5 | 77.0 |
| 2/1.5 | 85.5 | 85.5 | 86.5 | 86.5 | 88.5 | 87.5 | 84.0 | 86.5 |
| 3/2.2 | 86.5 | 85.5 | 89.5 | 89.5 | 89.5 | 88.5 | 85.5 | 87.5 |
| 5/3.7 | 88.5 | 86.5 | 89.5 | 89.5 | 89.5 | 89.5 | 86.5 | 88.5 |
| 7.5/5.5 | 89.5 | 88.5 | 91.7 | 91.0 | 91.0 | 90.2 | 86.5 | 89.5 |
| 10/7.5 | 90.2 | 89.5 | 91.7 | 91.7 | 91.0 | 91.7 | 89.5 | 90.2 |
| 15/11 | 91.0 | 90.2 | 92.4 | 93.0 | 91.7 | 91.7 | 89.5 | 90.2 |
| 20/15 | 91.0 | 91.0 | 93.0 | 93.0 | 91.7 | 92.4 | 90.2 | 91.0 |
| 25/18.5 | 91.7 | 91.7 | 93.6 | 93.6 | 93.0 | 93.0 | 90.2 | 91.0 |
| 30/22 | 91.7 | 91.7 | 93.6 | 94.1 | 93.0 | 93.6 | 91.7 | 91.7 |
| 40/30 | 92.4 | 92.4 | 94.1 | 94.1 | 94.1 | 94.1 | 91.7 | 91.7 |
| 50/37 | 93.0 | 93.0 | 94.5 | 94.5 | 94.1 | 94.1 | 92.4 | 92.4 |
| 60/45 | 93.6 | 93.6 | 95.0 | 95.0 | 94.5 | 94.5 | 92.4 | 93.0 |
| 75/55 | 93.6 | 93.6 | 95.4 | 95.0 | 94.5 | 94.5 | 93.6 | 94.1 |
| 100/75 | 95.0 | 94.5 | 96.2 | 96.2 | 95.8 | 95.8 | 94.5 | 95.0 |
| 125/90 | 95.4 | 94.5 | 96.2 | 96.2 | 95.8 | 95.8 | 95.0 | 95.0 |
| 150/110 | 95.4 | 94.5 | 96.2 | 96.2 | 96.2 | 95.8 | 95.0 | 95.0 |
| 200/150 | 95.8 | 95.4 | 96.5 | 96.2 | 96.2 | 95.8 | 95.4 | 95.0 |
| 250/186 | 96.2 | 95.4 | 96.5 | 96.2 | 96.2 | 96.2 | 95.4 | 95.4 |
| 300/224 | 95.8 | 95.4 | 96.2 | 95.8 | 95.8 | 95.8 | ||
| 350/261 | 95.8 | 95.4 | 96.2 | 95.8 | 95.8 | 95.8 | ||
| 400/298 | 95.8 | 95.8 | 96.2 | 95.8 | ||||
| 450/336 | 95.8 | 96.2 | 96.2 | 96.2 | ||||
| 500/373 | 95.8 | 96.2 | 96.2 | 96.2 | ||||
| 550/410 | 95.8 | 96.2 | 96.2 | 96.2 | ||||
| 600/447 | 95.8 | 96.2 | 96.2 | 96.2 | ||||
| 650/485 | 95.8 | 96.2 | 96.2 | 96.2 | ||||
| 700/522 | 95.8 | 96.2 | 96.2 | 96.2 | ||||
| 750/559 | 95.8 | 96.2 | 96.2 | 96.2 |
(o) Starting on June 1, 2027, each NEMA Design A motor, NEMA Design B motor, and IEC Design N (including NE, NEY, or NY variants) motor that is an air-over electric motor meeting the criteria in paragraph (m) of this section and with a power rating from 1 horsepower through 250 horsepower, built in a standard frame size, but excluding fire pump electric motors, manufactured (alone or as a component of another piece of equipment) shall have a nominal full-load efficiency of not less than the following:
| Motor horsepower/standard kilowatt equivalent | Nominal full-load efficiency (%) | |||||||
|---|---|---|---|---|---|---|---|---|
| 2 Pole | 4 Pole | 6 Pole | 8 Pole | |||||
| Enclosed | Open | Enclosed | Open | Enclosed | Open | Enclosed | Open | |
| 1/.75 | 77.0 | 77.0 | 85.5 | 85.5 | 82.5 | 82.5 | 75.5 | 75.5 |
| 1.5/1.1 | 84.0 | 84.0 | 86.5 | 86.5 | 87.5 | 86.5 | 78.5 | 77.0 |
| 2/1.5 | 85.5 | 85.5 | 86.5 | 86.5 | 88.5 | 87.5 | 84.0 | 86.5 |
| 3/2.2 | 86.5 | 85.5 | 89.5 | 89.5 | 89.5 | 88.5 | 85.5 | 87.5 |
| 5/3.7 | 88.5 | 86.5 | 89.5 | 89.5 | 89.5 | 89.5 | 86.5 | 88.5 |
| 7.5/5.5 | 89.5 | 88.5 | 91.7 | 91.0 | 91.0 | 90.2 | 86.5 | 89.5 |
| 10/7.5 | 90.2 | 89.5 | 91.7 | 91.7 | 91.0 | 91.7 | 89.5 | 90.2 |
| 15/11 | 91.0 | 90.2 | 92.4 | 93.0 | 91.7 | 91.7 | 89.5 | 90.2 |
| 20/15 | 91.0 | 91.0 | 93.0 | 93.0 | 91.7 | 92.4 | 90.2 | 91.0 |
| 25/18.5 | 91.7 | 91.7 | 93.6 | 93.6 | 93.0 | 93.0 | 90.2 | 91.0 |
| 30/22 | 91.7 | 91.7 | 93.6 | 94.1 | 93.0 | 93.6 | 91.7 | 91.7 |
| 40/30 | 92.4 | 92.4 | 94.1 | 94.1 | 94.1 | 94.1 | 91.7 | 91.7 |
| 50/37 | 93.0 | 93.0 | 94.5 | 94.5 | 94.1 | 94.1 | 92.4 | 92.4 |
| 60/45 | 93.6 | 93.6 | 95.0 | 95.0 | 94.5 | 94.5 | 92.4 | 93.0 |
| 75/55 | 93.6 | 93.6 | 95.4 | 95.0 | 94.5 | 94.5 | 93.6 | 94.1 |
| 100/75 | 95.0 | 94.5 | 96.2 | 96.2 | 95.8 | 95.8 | 94.5 | 95.0 |
| 125/90 | 95.4 | 94.5 | 96.2 | 96.2 | 95.8 | 95.8 | 95.0 | 95.0 |
| 150/110 | 95.4 | 94.5 | 96.2 | 96.2 | 96.2 | 95.8 | 95.0 | 95.0 |
| 200/150 | 95.8 | 95.4 | 96.5 | 96.2 | 96.2 | 95.8 | 95.4 | 95.0 |
| 250/186 | 96.2 | 95.4 | 96.5 | 96.2 | 96.2 | 96.2 | 95.4 | 95.4 |
(p) Starting on June 1, 2027, each NEMA Design A motor, NEMA Design B motor, and IEC Design N (including NE, NEY, or NY variants) motor that is an air-over electric motor meeting the criteria in paragraph (m) of this section and with a power rating from 1 horsepower through 20 horsepower, built in a specialized frame size, but excluding fire pump electric motors, manufactured (alone or as a component of another piece of equipment) shall have a nominal full-load efficiency of not less than the following:
| Motor horsepower/standard kilowatt equivalent | Nominal full-load efficiency (%) | |||||||
|---|---|---|---|---|---|---|---|---|
| 2 Pole | 4 Pole | 6 Pole | 8 Pole | |||||
| Enclosed | Open | Enclosed | Open | Enclosed | Open | Enclosed | Open | |
| 1/.75 | 74.0 | 82.5 | 82.5 | 80.0 | 80.0 | 74.0 | 74.0 | |
| 1.5/1.1 | 82.5 | 82.5 | 84.0 | 84.0 | 85.5 | 84.0 | 77.0 | 75.5 |
| 2/1.5 | 84.0 | 84.0 | 84.0 | 84.0 | 86.5 | 85.5 | 82.5 | 85.5 |
| 3/2.2 | 85.5 | 84.0 | 87.5 | 86.5 | 87.5 | 86.5 | 84.0 | 86.5 |
| 5/3.7 | 87.5 | 85.5 | 87.5 | 87.5 | 87.5 | 87.5 | 85.5 | 87.5 |
| 7.5/5.5 | 88.5 | 87.5 | 89.5 | 88.5 | 89.5 | 88.5 | 85.5 | 88.5 |
| 10/7.5 | 89.5 | 88.5 | 89.5 | 89.5 | 89.5 | 90.2 | ||
| 15/11 | 90.2 | 89.5 | 91.0 | 91.0 | ||||
| 20/15 | 90.2 | 90.2 | 91.0 | 91.0 |
(q) For purposes of determining the required minimum nominal full-load efficiency of an electric motor that has a horsepower or kilowatt rating between two horsepower or two kilowatt ratings listed in any table of energy conservation standards in paragraphs (n) through (p) through of this section, each such motor shall be deemed to have a listed horsepower or kilowatt rating, determined as follows:
(r) The standards in tables 8 through 10 of this section do not apply to the following electric motors exempted by the Secretary, or any additional electric motors that the Secretary may exempt:
[79 FR 31010, May 29, 2014, as amended at 87 FR 63657, Oct. 19, 2022; 88 FR 36150, Sept. 29, 2023]