10 C.F.R. § 429.134
(b) Refrigerators, refrigerator-freezers, and freezers—(1) Verification of total refrigerated volume. The total refrigerated volume of the basic model will be measured pursuant to the test requirements of 10 CFR part 430 for each unit tested. The results of the measurement(s) will be averaged and compared to the value of total refrigerated volume certified by the manufacturer. The certified total refrigerated volume will be considered valid only if:
(ii) The measurement is greater than the certified total refrigerated volume.
(c) Clothes washers—(1) Determination of Remaining Moisture Content. These provisions address anomalous remaining moisture content (RMC) results that are not representative of a basic model's performance, as well as differences in RMC values that may result from DOE using a different test cloth lot than was used by the manufacturer for testing and certifying the basic model.
(i) When testing according to appendix J to subpart B of part 430:
(C) If the measured RMC value of a tested unit is higher than the certified RMC value of the basic model and the difference between the measured and certified RMC values would affect the unit's compliance with the applicable standards, then:
(1) If DOE used the same test cloth lot that was used by the manufacturer for testing and certifying the basic model, then the measured RMC value will be considered the tested unit's final RMC value.
(2) If DOE used a different test cloth lot than was used by the manufacturer for testing and certifying the basic model, then:
(i) If the measured RMC value of a tested unit is higher than the certified RMC value of the basic model by more than three RMC percentage points, then a value three RMC percentage points less than the measured RMC value will be considered the tested unit's final RMC value.
(ii) If the measured RMC value of a tested unit is higher than the certified RMC value of the basic model, but by no more than three RMC percentage points, then the certified RMC value of the basic model will be considered the tested unit's final RMC value.
(ii) When testing according to appendix J2 to subpart B of part 430:
(D) If the measured RMC value of a tested unit is higher than the certified RMC value of the basic model but by no more than two RMC percentage points and the difference between the measured and certified RMC values would affect the unit's compliance with the applicable standards, then:
(1) If DOE used the same test cloth lot that was used by the manufacturer for testing and certifying the basic model, then the measured RMC value will be considered the tested unit's final RMC value.
(2) If DOE used a different test cloth lot than was used by the manufacturer for testing and certifying the basic model, then the certified RMC value of the basic model would be considered the tested unit's final RMC value.
(E) If the measured RMC value of a tested unit is higher than the certified RMC value of the basic model by more than two RMC percentage points, then DOE will perform two replications of the RMC measurement procedure, each pursuant to the provisions of section 3.8.5 of appendix J2 to subpart B of part 430, for a total of three independent RMC measurements of the tested unit. The average of the three RMC measurements will be calculated.
(1) If the average of the three RMC measurements is equal to or lower than the certified RMC value of the basic model, then the average RMC value will be considered the tested unit's final RMC value.
(2) If the average of the three RMC measurements is higher than the certified RMC value of the basic model but the difference between the measured and certified RMC values would not affect the unit's compliance with the applicable standards, then the average RMC value will be considered the tested unit's final RMC value.
(3) If the average of the three RMC measurements is higher than the certified RMC value of the basic model and the difference between the measured and certified RMC values would affect the unit's compliance with the applicable standards, then DOE will apply paragraph (c)(1)(ii)(F) of this section.
(F) If the average of the three RMC measurements is higher than the certified RMC value of the basic model and the difference between the measured and certified RMC values would affect the unit's compliance with the applicable standards, then:
(1) If DOE used the same test cloth lot that was used by the manufacturer for testing and certifying the basic model, then the average RMC pursuant to paragraph (c)(1)(ii)(E) of this section will be considered the tested unit's final RMC value.
(2) If DOE used a different test cloth lot than was used by the manufacturer for testing and certifying the basic model, then:
(i) If the average RMC value pursuant to paragraph (c)(1)(ii)(D) of this section is higher than the certified valued of the basic model by more than three RMC percentage points, then a value three RMC percentage points less than the average RMC value will be considered the tested unit's final RMC value.
(ii) If the average RMC value pursuant to paragraph (c)(1)(ii)(D) of this section is higher than the certified RMC value of the basic model, but by no more than three RMC percentage points, then the certified RMC value of the basic model will be considered the tested unit's final RMC value.
(d) Residential Water Heaters and Residential-Duty Commercial Water Heaters—(1) Verification of first-hour rating and maximum GPM rating. The first-hour rating or maximum gallons per minute (GPM) rating of the basic model will be measured pursuant to the test requirements of 10 CFR part 430 for each unit tested. The mean of the measured values will be compared to the rated values of first-hour rating or maximum GPM rating as certified by the manufacturer. The certified rating will be considered valid only if the measurement is within five percent of the certified rating.
(2) Verification of rated storage volume. The storage volume of the basic model will be measured pursuant to the test requirements of appendix E to subpart B of 10 CFR part 430 for each unit tested. The mean of the measured values will be compared to the rated storage volume as certified by the manufacturer. The rated value will be considered valid only if the measurement is within 3 percent of the certified rating.
(3) Verification of fuel input rate. The fuel input rate of each tested unit of the basic model will be measured pursuant to the test requirements of section 5.2.3 of 10 CFR part 430, subpart B, appendix E. The measured fuel input rate (either the measured fuel input rate for a single unit sample or the average of the measured fuel input rates for a multiple unit sample) will be compared to the rated input certified by the manufacturer. The certified rated input will be considered valid only if the measured fuel input rate is within ±2 percent of the certified rated input.
(4) Circulating water heaters. A storage tank for testing will be selected as described in paragraphs (d)(4)(i) and (ii) of this section. The effective storage volume of the circulating water heater determined in testing will be measured in accordance with appendix E to subpart B of 10 CFR part 430 with the storage tank that is used for testing.
(ii) All other circulating water heaters. For UEF and first-hour rating testing, circulating water heaters are paired with unfired hot water storage tanks (“UFHWSTs”) that have certified storage volumes between 80 and 120 gallons and are at exactly the minimum thermal insulation standard, in terms of R-value, for UFHWSTs, as per the standards set at § 431.110(a) of this chapter. Testing will be performed as follows:
(e) Packaged terminal air conditioners and packaged terminal heat pumps—(1) Verification of cooling capacity. The total cooling capacity of the basic model will be measured pursuant to the test requirements of 10 CFR part 431 for each unit tested. The results of the measurement(s) will be averaged and compared to the value of cooling capacity certified by the manufacturer. The certified cooling capacity will be considered valid only if the average measured cooling capacity is within five percent of the certified cooling capacity.
(f) Dehumidifiers—(1) Verification of capacity. The capacity will be measured pursuant to the test requirements of part 430 for each unit tested. The results of the measurement(s) will be averaged and compared to the value of capacity certified by the manufacturer for the basic model. The certified capacity will be considered valid only if the measurement is within five percent, or 1.00 pint per day, whichever is greater, of the certified capacity.
(2) Verification of whole-home dehumidifier case volume. The case volume will be measured pursuant to the test requirements of part 430 for each unit tested. The results of the measurement(s) will be averaged and compared to the value of case volume certified by the manufacturer for the basic model. The certified case volume will be considered valid only if the measurement is within two percent, or 0.2 cubic feet, whichever is greater, of the certified case volume.
(g) Commercial package air conditioning and heating equipment (excluding air-cooled equipment with a cooling capacity less than 65,000 Btu/h). Before May 15, 2025, the provisions in 10 CFR 429.134, revised as of January 1, 2024, are applicable. On and after May 15, 2025, the following provisions apply.
(h) Residential boilers—test protocols for functional verification of automatic means for adjusting water temperature. These tests are intended to verify the functionality of the design requirement that a boiler has an automatic means for adjusting water temperature for single-stage, two-stage, and modulating boilers. These test methods are intended to permit the functional testing of a range of control strategies used to fulfill this design requirement. Section 2, Definitions, and paragraph 6.1.a of appendix EE to subpart B of part 430 of this chapter apply for the purposes of this paragraph (h).
(D) Adjust the inferential load controller. (1) Adjust the boiler controls (in accordance with the I&O manual) to the default setting that allows for activation of the means for adjusting water temperature. For boiler controls that do not allow for control adjustment during active mode operation, terminate call for heat and adjust the inferential load controller in accordance with the I&O manual and then reinitiate call for heat.
(2) If the means for adjusting water temperature uses outdoor temperature reset, the maximum outdoor temperature setting (if equipped) should be set to a temperature high enough that the boiler operates continuously during the duration of this test (i.e., if the conditions in paragraph (h)(1)(ii)(A) of this section equal room ambient temperature, then the maximum outdoor temperature should be set at a temperature greater than the ambient air temperature during the test).
(ii) Establish low inferred load conditions at minimum boiler supply water temperature—(A) Establish low inferred load conditions. (1) Establish the inferred load conditions (simulated using a controlling parameter, such as outdoor temperature, thermostat patterns, or boiler cycling) so that the supply water temperature is maintained at the minimum supply water temperature prescribed by the boiler manufacturer's temperature reset control strategy found in the I&O manual.
(2) The minimum supply water temperature of the default temperature reset curve is usually provided in the I&O manual. If there is no recommended minimum supply water temperature, set the minimum supply water temperature equal to 20 °F less than the high supply water temperature specified in paragraph (h)(1)(iii)(A) of this section.
(B) Supply water temperature stabilization at low inferred load. (1) Maintain the call for heat until the boiler supply water temperature has stabilized. Temperature stabilization is deemed to be obtained when the boiler supply water temperature does not vary by more than ±3 °F over a period of five minutes. The duration of time required to stabilize the supply water, following the procedure in paragraph (h)(1)(ii)(A) of this section, is dependent on the reset strategy and may vary from model to model.
(2) Record the boiler supply water temperature while the temperature is stabilized.
(B) Supply water temperature stabilization at high inferred load. (1) Maintain the call for heat until the boiler supply water temperature has stabilized. Temperature stabilization is deemed to be obtained when the boiler supply water temperature does not vary by more than ±3 °F over a period of five minutes. The duration of time required to stabilize the supply water, following the procedure in paragraph (h)(1)(iii)(A) of this section, is dependent on the reset strategy and may vary from model to model.
(2) Record the boiler supply water temperature while the temperature is stabilized.
(3) Terminate the call for heat.
(2) Test protocol for single-stage products employing burner delay. This test will be used in place of paragraph (h)(1) of this section for products manufacturers have certified to DOE under § 429.18(b)(3) as employing a burner delay automatic means strategy. This test verifies whether the automatic means in single-stage boiler products establishes a burner delay upon a call for heat until the means has determined that the inferred heat load cannot be met by the residual heat of the water in the system.
(i) The volume rate of flow (flow rate) at BEP and nominal speed of rotation of each tested unit of the basic model will be measured pursuant to the test requirements of § 431.464 of this chapter, where the value of volume rate of flow (flow rate) at BEP and nominal speed of rotation certified by the manufacturer will be treated as the expected BEP flow rate. The results of the measurement(s) will be compared to the value of volume rate of flow (flow rate) at BEP and nominal speed of rotation certified by the manufacturer. The certified volume rate of flow (flow rate) at BEP and nominal speed of rotation will be considered valid only if the measurement(s) (either the measured volume rate of flow (flow rate) at BEP and nominal speed of rotation for a single unit sample or the average of the measured flow rates for a multiple unit sample) is within five percent of the certified volume rate of flow (flow rate) at BEP and nominal speed of rotation.
(2) Dedicated-purpose pool pumps.
(i) The rated hydraulic horsepower of each tested unit of the basic model of dedicated-purpose pool pump will be measured pursuant to the test requirements of § 431.464(b) of this chapter and the result of the measurement(s) will be compared to the value of rated hydraulic horsepower certified by the manufacturer. The certified rated hydraulic horsepower will be considered valid only if the measurement(s) (either the measured rated hydraulic horsepower for a single unit sample or the average of the measured rated hydraulic horsepower values for a multiple unit sample) is within 5 percent of the certified rated hydraulic horsepower.
(ii) To verify the self-priming capability of non-self-priming pool filter pumps and of self-priming pool filter pumps that are not certified with NSF/ANSI 50-2015 (incorporated by reference, see § 429.4) as self-priming, the vertical lift and true priming time of each tested unit of the basic model of self-priming or non-self-priming pool filter pump will be measured pursuant to the test requirements of § 431.464(b) of this chapter.
(A) For self-priming pool filter pumps that are not certified with NSF/ANSI 50-2015 as self-priming, at a vertical lift of 5.0 feet, the result of the true priming time measurement(s) will be compared to the value of true priming time certified by the manufacturer. The certified value of true priming time will be considered valid only if the measurement(s) (either the measured true priming time for a single unit sample or the average of true priming time values for a multiple unit sample) is within 5 percent of the certified value of true priming time.
(1) If the representative value of true priming time is found to be valid, the value of true priming time certified by the manufacturer will be used to determine the appropriate equipment class and standard level for that basic model.
(2) If the representative value of true priming time is found to be invalid, the mean of the values of true priming time determined from the tested unit(s) will be used to determine the appropriate equipment class and standard level for that basic model.
(B) For non-self-priming pool filter pumps, at a vertical lift of 5.0 feet, the result of the true priming time measurement(s) (either the measured true priming time for a single unit sample or the average of true priming time values, for a multiple unit sample) will be compared to the value of true priming time referenced in the definition of non-self-priming pool filter pump at § 431.462 (10.0 minutes).
(1) If the measurement(s) of true priming time are greater than 95 percent of the value of true priming time referenced in the definition of non-self-priming pool filter pump at § 431.462 with a vertical lift of 5.0 feet, the DPPP model will be considered a non-self-priming pool filter pump for the purposes of determining the appropriate equipment class and standard level for that basic model.
(2) If the conditions specified in paragraph (i)(2)(ii)(B)(1) of this section are not satisfied, then the DPPP model will be considered a self-priming pool filter pump for the purposes of determining the appropriate equipment class and standard level for that basic model.
(iii) To verify the maximum head of self-priming pool filter pump, non-self-priming pool filter pumps, and waterfall pumps, the maximum head of each tested unit of the basic model of self-priming pool filter pump, non-self-priming pool filter pump, or waterfall pump will be measured pursuant to the test requirements of § 431.464(b) of this chapter and the result of the measurement(s) will be compared to the value of maximum head certified by the manufacturer. The certified value of maximum head will be considered valid only if the measurement(s) (either the measured maximum head for a single unit sample or the average of the maximum head values for a multiple unit sample) is within 5 percent of the certified values of maximum head.
(iv) To verify that a DPPP model complies with the applicable freeze protection control design requirements, the initiation temperature, run-time, and speed of rotation of the default control configuration of each tested unit of the basic model of dedicated-purpose pool pump will be evaluated according to the procedure specified in paragraph (i)(2)(iv)(A) of this section:
(A) (1) Set up and configure the dedicated-purpose pool pump under test according to the manufacturer instructions, including any necessary initial priming, in a test apparatus as described in appendix A of HI 40.6-2014-B (incorporated by reference, see § 429.4), except that the ambient temperature registered by the freeze protection ambient temperature sensor will be able to be measured and controlled by, for example, exposing the freeze protection temperature sensor to a specific temperature by submerging the sensor in a water bath of known temperature, by adjusting the actual ambient air temperature of the test chamber and measuring the temperature at the freeze protection ambient temperature sensor location, or by other means that allows the ambient temperature registered by the freeze protection temperature sensor to be reliably simulated, varied, and measured. Do not adjust the default freeze protection control settings or enable the freeze protection control if it is shipped disabled.
(2) Activate power to the pump with the flow rate set to zero (i.e., the pump is energized but not circulating water). Set the ambient temperature to 42.0 ± 0.5 °F and allow the temperature to stabilize, where stability is determined in accordance with section 40.6.3.2.2 of HI 40.6-2014-B. After 5 minutes, decrease the temperature measured by the freeze protection temperature sensor by 1.0 ± 0.5 °F and allow the temperature to stabilize. After each reduction in ambient temperature and subsequent stabilization, record the DPPP rotating speed, if any, and freeze protection ambient temperature reading, where the “freeze protection ambient temperature reading” is representative of the temperature measured by the freeze protection ambient temperature sensor, which may be recorded by a variety of means depending on how the temperature is being simulated and controlled. If no flow is initiated, record zero rpm or no flow. Continue decreasing the temperature measured by the freeze protection temperature sensor by 1.0 ± 0.5 °F after 5.0 minutes of stable operation at the previous temperature reading until the pump freeze protection initiates water circulation or until the ambient temperature of 38.0 ± 0.5 °F has been evaluated (i.e., the end of the 5.0 minute interval of 38.0 °F), whichever occurs first.
(3) If and when the DPPP freeze protection controls initiate water circulation, increase the ambient temperature reading registered by the freeze protection temperature sensor to a temperature of 42.0 ± 0.5 °F and maintain that temperature for 60.0 minutes. Do not modify or interfere with the operation of the DPPP freeze protection operating cycle. After 60.0 minutes, record the freeze protection ambient temperature and rotating speed, if any, of the dedicated-purpose pool pump under test.
(3) Circulator pumps.
(i) The flow rate at BEP and maximum speed of each tested unit of the basic model will be measured pursuant to the test requirements of § 431.464(c) of this chapter, where the value of flow rate at BEP and maximum speed certified by the manufacturer will be treated as the expected BEP flow rate at maximum speed. The resulting measurement(s) will be compared to the value of flow rate at BEP and maximum speed certified by the manufacturer. The certified flow rate at BEP and maximum speed will be considered valid only if the measurement (either the measured flow rate at BEP and maximum speed for a single unit sample or the average of the measured flow rates for a multiple unit sample) is within 5 percent of the certified flow rate at BEP and maximum speed.
(ii) The rated hydraulic horsepower of each tested unit of the basic model will be measured pursuant to the test requirements of § 431.464(c) of this chapter. The resulting measurement will be compared to the rated hydraulic horsepower certified by the manufacturer. The certified rated hydraulic horsepower will be considered valid only if the measurement (either the measured rated hydraulic horsepower for a single unit sample or the average of the measured rated hydraulic horsepower values for a multiple unit sample) is within 5 percent of the certified rated hydraulic horsepower.
(j) Refrigerated bottled or canned beverage vending machines—(1) Verification of refrigerated volume. The refrigerated volume (V) of each tested unit of the basic model will be measured pursuant to the test requirements of 10 CFR 431.296. The results of the measurement(s) will be compared to the representative value of refrigerated volume certified by the manufacturer. The certified refrigerated volume will be considered valid only if the measurement(s) (either the measured refrigerated volume for a single unit sample or the average of the measured refrigerated volumes for a multiple unit sample) is within five percent of the certified refrigerated volume.
(2) Verification of surface area, transparent, and non-transparent areas. The percent transparent surface area on the front side of the basic model will be measured pursuant to these requirements for the purposes of determining whether a given basic model meets the definition of Class A or Combination A, as presented at 10 CFR 431.292. The transparent and non-transparent surface areas shall be determined on the front side of the beverage vending machine at the outermost surfaces of the beverage vending machine cabinet, from edge to edge, excluding any legs or other protrusions that extend beyond the dimensions of the primary cabinet. Determine the transparent and non-transparent areas on each side of a beverage vending machine as described in paragraphs (j)(2)(i) and (ii) of this section. For combination vending machines, disregard the surface area surrounding any refrigerated compartments that are not designed to be refrigerated (as demonstrated by the presence of temperature controls), whether or not it is transparent. Determine the percent transparent surface area on the front side of the beverage vending machine as a ratio of the measured transparent area on that side divided by the sum of the measured transparent and non-transparent areas, multiplying the result by 100.
(i) Determination of transparent area. Determine the total surface area that is transparent as the sum of all surface areas on the front side of a beverage vending machine that meet the definition of transparent at 10 CFR 431.292. When determining whether or not a particular wall segment is transparent, transparency should be determined for the aggregate performance of all the materials between the refrigerated volume and the ambient environment; the composite performance of all those materials in a particular wall segment must meet the definition of transparent for that area be treated as transparent.
(ii) Determination of non-transparent area. Determine the total surface area that is not transparent as the sum of all surface areas on the front side of a beverage vending machine that are not considered part of the transparent area, as determined in accordance with paragraph (j)(2)(i) of this section.
(k) Central air conditioners and heat pumps. Before July 7, 2025, the provisions in this section of this title as it appeared in the 10 CFR parts 200-499 edition revised as of January 1, 2023 are applicable. On and after July 7, 2025, provisions in paragraphs (k)(1), (2) and (3) of this section shall apply. On and after July 7, 2026, provisions in paragraph (k)(4) of this section shall also apply.
(2) Verification of CD value.
(i) For central air conditioners and heat pumps other than models of outdoor units with no match, if manufacturers certify that they did not conduct the optional tests to determine the CD c and/or CD h value for an individual model (for single-package systems) or individual combination (for split systems), as applicable, for each unit tested, the default CD c and/or CD h value will be used as the basis for the calculation of SEER2 or HSPF2 when testing in accordance with appendix M1 to subpart B of 10 CFR part 430, or SCORE or SHORE when testing in accordance with appendix M2 to subpart B of 10 CFR part 430. If manufacturers certify that they conducted the optional tests to determine the CD c and/or CD h value for an individual model (for single-package systems) or individual combination (for split systems), as applicable, the following provisions apply.
(3) Verification of cut-out and cut-in temperatures for central heat pumps.
(4) Verification of Variable Capacity Operation and of Fixed Settings for the Compressor and the Indoor Fan when Testing Variable Capacity Compressor Systems—(i) Conducting the controls verification procedure (CVP). A CVP may be performed for any model certified as a variable capacity compressor system for the purposes of assessment or enforcement testing conducted according to appendix M1 to subpart B of 10 CFR part 430 or appendix M2 to subpart B of 10 CFR part 430 (i.e., the certification tests), as applicable. For a heat pump, either a cooling mode CVP, a heating mode CVP, or both may be conducted, as elected by DOE. If a CVP is not conducted, the override instructions for the compressor and indoor fan, as specified by the manufacturer, will be used to conduct the tests per appendix M1 to subpart B of 10 CFR part 430 or, appendix M2 to subpart B of 10 CFR part 430, as applicable.
(ii) Variable capacity determination.
(iii) CVP tolerance evaluation for full and minimum load intervals.
(A) The data collected in the CVP per paragraph (k)(4)(i)(A) or (B) of this section shall be evaluated for the duration of the individual CVP full or minimum load interval excluding the preliminary 30 minutes of equilibrium data, to determine compliance with test condition tolerances and test operating tolerances listed in section I5.1 of appendix I of AHRI 210/240-2024 (if testing in accordance with appendix M1 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)) or of AHRI 1600-2024 (if testing in accordance with appendix M2 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)), with the exception that indoor entering wet bulb deviation in I5.1 and test operating tolerance in I5.1.3 is applicable only for cooling mode CVP.
(1) If the specified tolerances are met under system operation for 60 minutes, the average capacity and average power measured over this 60-minute test interval shall be recorded.
(2) If the four-hour time limit is reached by the system without maintaining the tolerances for a 60-minute period, but two successive test period sub-intervals are identified, each a minimum of 30 minutes, and comprised of a whole number of compressor cycles (either compressor on-off cycles or speed/capacity cycles) or in which minimal fluctuations of the compressor speed/capacity level are observed, where both the time averaged integrated capacity and time averaged integrated power of the two successive test period sub-intervals are observed to be within two percent of each other, a single capacity average and a single power average shall be recorded, both averaged over compressor-on periods of the two successive test period sub-intervals. These average capacity and power values shall be considered the capacity and power values recorded for the test interval.
(3) If the four-hour time limit is reached by the system without complying with either paragraph (k)(4)(iii)(A)(1) or (2) of this section, the time averaged integrated capacity and time averaged integrated power shall be recorded for only the compressor-on periods over the final 120 minutes of the test interval.
(B) Determine whether the measured capacity for each full load interval, as evaluated per the CVP conducted in paragraph (k)(4)(i)(A) or (B) of this section, is no more than 6% less than the corresponding certification test capacity, as follows:

Where: q A,Full = Certification test capacity at AFull condition, q CVP,A,Full = CVP test capacity at AFull condition, q H3,Full = Certification test capacity at H3Full condition, q CVP,H3,Full = CVP test capacity at H3Full condition, q H4,Full = Certification test capacity at H4Full condition, q CVP,H4,Full= CVP test capacity at H4Full condition,
(C) Determine whether the measured capacity for each minimum load interval, as evaluated per the CVP conducted in paragraph (k)(4)(i)(A) or (B) of this section, is no more than 6% less than the corresponding certification test capacity, as follows:

Where: q CVP,F,Low= CVP test capacity at FLow condition, q F,Low = Certification test capacity at FLow condition, q CVP,H1,Low = CVP test capacity at H1Low condition, q H1,Low= Certification test capacity at H1Low condition,
(D) Determine whether the measured efficiency for the full and minimum load interval, as evaluated per the CVP conducted in paragraph (k)(4)(i)(A) or (B) of this section, is no more than 10% less than the corresponding certification test efficiency, as follows:


(v) Evaluation of results when CVP tolerances are not met. If the tolerances for capacity and efficiency are not met by the applicable full and minimum load intervals as per paragraphs (k)(4)(iii)(B) through (D) of this section, the unit shall be tested per instructions in paragraphs (k)(4)(v)(A) through (C) of this section, as applicable. The instructions in paragraphs (k)(4)(v)(A) through (C) shall be followed, as applicable, only for the certification tests corresponding to the out of tolerance compressor speed interval based on the evaluations of paragraphs (k)(4)(iii)(B) through (D). For all compressor speed intervals for which the capacity and EER2/COP2/EER/COP are in tolerance as per paragraphs (k)(4)(iii)(B) through (D), the corresponding certification tests shall be used without adjustments.
(A) The instructions of this paragraph shall be applied to systems for which the same control device used as per the CVP conducted in paragraph (k)(4)(i)(A) or (B) of this section is used as the means for overriding the controls, and both of the following are supported by the control device: monitoring of the compressor and indoor blower speed during native-control operation without otherwise impacting the control of the system; and monitoring and adjustment of the compressor and indoor blower speed during certification tests, where monitoring and adjustment means the control device has the ability to display and make discrete adjustments, as required, to the compressor and indoor blower speeds without additional hardware or non-publicly available software.
(1) The compressor and indoor blower speed shall be monitored during the CVP conducted in paragraph (k)(4)(i)(A) or (B) of this section. The average compressor and indoor blower speeds and indoor air volume rate shall be evaluated for the same time period(s) used as described in paragraph (k)(4)(iii)(A) of this section to determine average capacity and power for the CVP test. The compressor speed for the certification test shall be set at this average value observed during the corresponding CVP test interval. The indoor blower speed shall be set as described in section 6.1.5 of AHRI 210/240-2024 (if testing in accordance with appendix M1 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)) or of AHRI 1600-2024 (if testing in accordance with appendix M2 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)), except the “specified airflow” shall be set as the average value observed during the corresponding CVP test interval. The same adjusted compressor speed shall be used for the other certification tests that require the same speed, as applicable, as detailed in table 1 to this paragraph (k)(4)(v)(A). Specifically, for each of the CVP tests listed in the first column for which either the capacity tolerances of paragraph (k)(4)(iii)(B) or (C) of this section are not met or the efficiency tolerances of paragraph (k)(4)(iii)(D) of this section are not met, the certification tests to be conducted again using the compressor speed determined in the corresponding CVP test are listed in the last three columns of the table, depending on which of the three kinds of system the model is designated.
(2) If required, the adjusted q H3,Full and PH3,Full shall be used to calculate q k=2hcalc(47) and Pk=2hcalc(47), respectively, to represent performance at 47 °F as described in section 11.2.2.4 of AHRI 210/240-2024 (if testing in accordance with appendix M1 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)) or of AHRI 1600-2024 (if testing in accordance with appendix M2 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)) and for use in calculating performance at 35 °F. If required, the adjusted H1Low and H3Low tests shall be used to calculate q thi,H2,Low and PH2,Low, respectively, as described in section 6.1.3.4 of AHRI 210/240-2024 (if testing in accordance with appendix M1 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)) or of AHRI 1600-2024 (if testing in accordance with appendix M2 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)). No adjustments are required for intermediate or nominal compressor speed tests or, if cyclic tests are conducted, for the degradation coefficient(s).
| CVP test | Certification tests that use the indicated CVP test compressor speed or would have certification test results adjusted per paragraph (k)(4)(v)(B) of this section, if the CVP test is out of capacity or EER/COP tolerance per paragraph (k)(4)(iii) of this section | ||
|---|---|---|---|
| Variable capacity certified, single capacity system | Variable capacity certified, two capacity system | Variable capacity system | |
| AFull | AFull, BFull | AFull, BFull | AFull, BFull. |
| FLow | N/A | BLow, FLow | BLow, FLow. |
| H1Low | N/A | H0Low, H1Low, H3Low | H0Low, H1Low. |
| H3Full | H2Full, H3Full | H3Full | H3Full. |
| H4Full | H4Full | H4Full | H4Full. |
(B) The instructions of this paragraph shall be applied to systems for which the means for overriding the compressor and indoor blower speed as discussed in paragraph (k)(4)(v)(A) of this section is not provided by the control used for conducting the CVP. For each of the CVP tests listed in the first column of table 1 to paragraph (k)(4)(v)(A) of this section for which either the capacity tolerances of paragraph (k)(4)(iii)(B) or (C) of this section are not met or the efficiency tolerances of paragraph (k)(4)(iii)(D) of this section are not met, depending on which of the three kinds of system the model is designated, the certification test results to be adjusted based on the results of the CVP test are indicated by the last three columns of the table for each CVP test listed in the first column.
(1) The average capacities and power(s) measured during the CVP time period(s) described in paragraph (k)(4)(iii)(A) of this section shall be used (with no adjustment for tests having a CVP interval). For the certification tests requiring adjustment with no CVP interval (any required certification test in column 2, 3, or 4 of table 1 to paragraph (k)(4)(v)(A) of this section other than AFull, FLow, H1Low, H3Full and H4Full for which the column 1 CVP interval did not meet capacity or EER2/COP2/EER/COP tolerances), the capacity and power shall be adjusted. The capacity shall be adjusted by applying the ratio of the capacity measured during the CVP test interval divided by the capacity measured during the certification test (for the corresponding CVP interval). The power shall be adjusted by applying the ratio of the power measured during the CVP test interval divided by the power measured during the certification test (for the corresponding CVP interval), as follows:
Cooling full capacity:

Cooling full power:

Cooling minimum capacity:

Cooling minimum power:

Heating minimum capacity:

Heating minimum power:

Where: CSF = 0.0204/ °F, capacity slope factor for Split Systems CSF = 0.0262/ °F, capacity slope factor for Single Package Units PSF = 0.00455/ °F, power slope factor for all products
(2) If required, the measured QH3,Full and EH3,Full from the CVP shall be used to calculate q k=2hcalc(47) and Pk=2hcalc(47), respectively, to represent performance at 47 °F as described in section 11.2.2.4 of AHRI 210/240-2024 (if testing in accordance with appendix M1 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)) or of AHRI 1600-2024 (if testing in accordance with appendix M2; (incorporated by reference, see § 429.4)), and for use in calculating performance at 35 °F. If required, the measured H1Low from the CVP and the adjusted H3Low tests shall be used to calculate q thi,H2,Low and PH2,Low, respectively, as described in section 6.1.3.4 of AHRI 210/240-2024 (if testing in accordance with appendix M1 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)) or of AHRI 1600-2024 (if testing in accordance with appendix M2 to subpart B of 10 CFR part 430; (incorporated by reference, see § 429.4)). No adjustments are required for intermediate or nominal compressor speed tests or, if cyclic tests are conducted, the degradation coefficient(s).
(l) Miscellaneous refrigeration products—(1) Verification of total refrigerated volume. For all miscellaneous refrigeration products, the total refrigerated volume of the basic model will be measured pursuant to the test requirements of part 430 of this chapter for each unit tested. The results of the measurement(s) will be averaged and compared to the value of total refrigerated volume certified by the manufacturer. The certified total refrigerated volume will be considered valid only if:
(ii) The measurement is greater than the certified total refrigerated volume.
(m) Commercial packaged boilers—(1) Verification of fuel input rate. The fuel input rate of each tested unit will be measured pursuant to the test requirements of § 431.86 of this chapter. The results of the measurement(s) will be compared to the value of rated input certified by the manufacturer. The certified rated input will be considered valid only if the measurement(s) (either the measured fuel input rate for a single unit sample or the average of the measured fuel input rates for a multiple unit sample) is within two percent of the certified rated input.
(n) Commercial water heating equipment other than residential-duty commercial water heaters—(1) Verification of fuel input rate. The fuel input rate of each tested unit of the basic model will be measured pursuant to the test requirements of § 431.106 of this chapter. The measured fuel input rate (either the measured fuel input rate for a single unit sample or the average of the measured fuel input rates for a multiple unit sample) will be compared to the rated input certified by the manufacturer. The certified rated input will be considered valid only if the measured fuel input rate is within two percent of the certified rated input.
(o) Uninterruptible power supplies.
(1) To determine the uninterruptible power supply (UPS) architecture:
(p) Compressors—(1) Verification of full-load operating pressure.
(i) The maximum full-flow operating pressure of each tested unit of the basic model will be measured pursuant to the test requirements of appendix A to subpart T of part 431 of this chapter, where 90 percent of the value of full-load operating pressure certified by the manufacturer will be the starting point of the test method prior to increasing discharge pressure. The measured maximum full-flow operating pressure (either the single measured value for a single unit sample or the mean of the measured maximum full-flow operating pressures for a multiple unit sample) will be compared to the certified rating for full-load operating pressure to determine if the certified rating is valid or not. The certified rating for full-load operating pressure will be considered valid only if the certified rating for full-load operating pressure is less than or equal to the measured maximum full-flow operating pressure and greater than or equal to the lesser of—
(2) Verification of full-load actual volume flow rate. The measured full-load actual volume flow rate will be measured, pursuant to the test requirements of appendix A to subpart T of part 431 of this chapter, at the full-load operating pressure determined in paragraph (p)(1) of this section. The certified full-load actual volume flow rate will be considered valid only if the measurement(s) (either the measured full-load actual volume flow rate for a single unit sample or the mean of the measured values for a multiple unit sample) are within the percentage of the certified full-load actual volume flow rate specified in Table 1 of this section:
| Manufacturer certified full-load actual volume flow rate(m3/s) × 10−3 | Allowablepercent of the certifiedfull-loadactual volumeflow rate(%) |
|---|---|
| 0 < and ≤ 8.3 | ±7 |
| 8.3 < and ≤ 25 | ±6 |
| 25 < and ≤ 250 | ±5 |
| > 250 | ±4 |
(3) Verification of door surface area. The surface area of a display door or non-display door basic model will be measured pursuant to the requirements of 10 CFR part 431, subpart R, appendix A for each unit tested. The results of the measurement(s) will be averaged and compared to the value of the surface area certified by the manufacturer. The certified surface area will be considered valid only if the average measured surface area is within plus or minus three percent of the certified surface area.
(4) Verification of door electricity-consuming device power. For each basic model of walk-in cooler and walk-in freezer door, DOE will calculate the door's energy consumption using the input power listed on the nameplate of each electricity-consuming device shipped with the door. If an electricity-consuming device shipped with a walk-in door does not have a nameplate or the nameplate does not list the device's input power, then DOE will use the device's rated input power included in the door's certification report. If the door is not certified or if the certification does not include a rated input power for an electricity-consuming device shipped with a walk-in door, DOE will use the measured input power. DOE also may validate the power listed on the nameplate or the rated input power by measuring it when energized using a power supply that provides power within the allowable voltage range listed on the component nameplate or the door nameplate, whichever is available. If the measured input power is more than 10 percent higher than the input power listed on the nameplate or the rated input power, as appropriate, then the measured input power shall be used in the door's energy consumption calculation.
(r) Portable air conditioners. Verification of seasonally adjusted cooling capacity. The seasonally adjusted cooling capacity will be measured pursuant to the test requirements of 10 CFR part 430 for each unit tested. The results of the measurement(s) will be averaged and compared to the value of seasonally adjusted cooling capacity certified by the manufacturer. The certified seasonally adjusted cooling capacity will be considered valid only if the average measured seasonally adjusted cooling capacity is within five percent of the certified seasonally adjusted cooling capacity.
(s) Direct Expansion-Dedicated Outdoor Air Systems.
(3) If the manufacturer certified testing in accordance with Option 1 using VERS exhaust air transfer ratio (EATR) values or Option 2 using VERS effectiveness and EATR values determined using an analysis tool certified in accordance with the DOE test procedure in appendix B to subpart F of part 431 of this chapter, DOE may conduct its own testing to determine VERS performance in accordance with the DOE test procedure in appendix B to subpart F of part 431 of this chapter.
(t) Ceiling Fans—(1) Verification of blade span. DOE will measure the blade span and round the measurement pursuant to the test requirements of 10 CFR part 430 of this chapter for each unit tested. DOE will consider the represented blade span valid only if the rounded measurement(s) (either the rounded measured value for a single unit, or the mean of the rounded measured values for a multiple unit sample, rounded to the nearest inch) is the same as the represented blade span.
(2) Verification of the distance between the ceiling and lowest point of fan blades. DOE will measure the distance between the ceiling and lowest point of the fan blades and round the measurement pursuant to the test requirements of 10 CFR part 430 of this chapter for each unit tested. DOE will consider the represented distance valid only if the rounded measurement(s) (either the measured value for a single unit, or the mean of the measured values for a multiple unit sample, rounded to the nearest quarter inch) are the same as the represented distance.
(3) Verification of blade revolutions per minute (RPM) measured at high speed. DOE will measure the blade RPM at high speed pursuant to the test requirements of 10 CFR part 430 of this chapter for each unit tested. DOE will consider the represented blade RPM measured at high speed valid only if the measurement(s) (either the measured value for a single unit, or the mean of the measured values for a multiple unit sample, rounded to the nearest RPM) are within 2 percent of the represented blade RPM at high speed.
(4) Verification of blade edge thickness. DOE will measure the blade edge thickness and round the measurement pursuant to the test requirements of 10 CFR part 430 for each unit tested. DOE will consider the represented blade edge thickness valid only if the measurement(s) (either the measured value for a single unit, or the mean of the measured values for a multiple unit sample, rounded to the nearest 0.01 inch) are the same as the represented blade edge thickness.
(v) Variable refrigerant flow multi-split air conditioners and heat pumps (other than air-cooled with rated cooling capacity less than 65,000 btu/h). The following provisions apply for assessment and enforcement testing of models subject to standards in terms of IEER:
(2) Manufacturer involvement in assessment or enforcement testing. A manufacturer's representative will be allowed to support commissioning and witness assessment and/or enforcement testing for variable refrigerant flow multi-split air conditioners and heat pumps, including during the controls verification procedures (CVPs) specified in paragraph (v)(3) of this section, with allowance for additional involvement as described in the following provisions.
(3) Controls Verification Procedure (CVP). This procedure validates the certified values of critical parameters for which positions may be manually set during the full- and part-load IEER cooling test conditions specified at appendix D1 to subpart F of 10 CFR part 431. The CVP will only be conducted for a single system.
(ii) Validating critical parameters—At each load point, certified critical parameter values will be validated or invalidated according to Section C6 of AHRI 1230-2021 with the following amendments:
(iii) Determining critical parameters for use in steady-state IEER cooling tests. If, following a CVP, IEER testing is conducted per appendix D1 to subpart F of 10 CFR part 431, the following provisions apply:
(B) Invalidated critical parameter settings. At each load point, if certified critical parameter values identified pursuant to paragraph (v)(3) of this section are found to be invalid according to the results of the CVP, determine alternate critical parameter values for use in the corresponding IEER test (as specified in appendix D1 to subpart F of 10 CFR part 431) as follows:
(1) Select the CVP measurement period—this period must have duration determined per paragraph (v)(3)(ii)(A) of this section and must be the period where the RSS points total has a lower average value over the measurement period than over any other time period in the CVP of the same duration. If multiple periods exist with the same RSS points total, select the measurement period closest to but before the time that the first indoor unit switches to thermally inactive (denoted as “toff” in AHRI 1230-2021).
(2) Determine alternate critical parameters—calculate the average position for each critical parameter during the measurement period selected in paragraph (v)(3)(iii)(B)(1) of this section. When initially setting critical parameters per section 5.1 of appendix D1 to subpart F of 10 CFR part 431, instead of using the certified critical parameter values, use the alternate critical parameter values as control inputs. The same initial alternate critical parameter values must be used for all systems in the assessment/enforcement sample (though critical parameter adjustments as needed to achieve target capacity or sensible heat ratio (SHR) limits are made independently for each tested system, per paragraph (v)(3)(iii)(B)(3) of this section.
(3) For each system, determine whether critical parameter adjustments are needed to achieve the target capacity or SHR limit for an IEER cooling test. Perform critical parameter adjustments independently on each system as described in section 5.2 of appendix D1 to subpart F of 10 CFR part 431, with the following exceptions:
(i) Replace all references to “certified critical parameter values” with “alternate critical parameter values” as determined in paragraph (v)(3)(iii)(B) of this section.
(ii) Determine CPMax from a CVP conducted at full-load cooling conditions as the maximum value observed during the R2 period as described in Section C.4.4.2.3 of AHRI 1230-2021. If multiple components corresponding to a single parameter are present, determine CPMax at the point during the R2 period at which the average value across all components corresponding to that critical parameter is maximized.
(w) Automatic commercial ice makers—verification of harvest rate. The harvest rate will be measured pursuant to the test requirements of 10 CFR part 431 for each unit tested. The results of the measurement(s) will be averaged and compared to the value of harvest rate certified by the manufacturer of the basic model. The certified harvest rate will be considered valid only if the average measured harvest rate is within five percent of the certified harvest rate.
(x) Single package vertical air conditioners and heat pumps. The following provisions apply for assessment and enforcement testing of models subject to standards in terms of IEER.
(3) Validation of outdoor ventilation airflow rate. The outdoor ventilation airflow rate in cubic feet per minute (“CFM”) of the basic model will be measured in accordance with ASHRAE 41.2-1987 and Section 6.4 of ASHRAE 37-2009 (both incorporated by reference, see § 429.4). All references to the inlet shall be determined to mean the outdoor air inlet.
(i) The outdoor ventilation airflow rate validation shall be conducted at the conditions specified in Table 3 of AHRI 390-2021 (incorporated by reference, see § 429.4), Full Load Standard Rating Capacity Test, Cooling, except for the following:
The outdoor ventilation airflow rate shall be determined at 0 in. H2O external static pressure with a tolerance of −0.00/+0.05 in. H2O.
(y) Air-cooled, three-phase, small commercial package air conditioning and heating equipment with a cooling capacity of less than 65,000 Btu/h and air-cooled, three-phase, variable refrigerant flow multi-split air conditioners and heat pumps with a cooling capacity of less than 65,000 Btu/h. The following provisions apply for assessment and enforcement testing of models subject to standards in terms of SEER2 and HSPF2 (as applicable).
(2) Verification of CD value.
(aa) Computer room air conditioners. The following provisions apply for assessment and enforcement testing of models subject to energy conservation standards denominated in terms of NSenCOP.
(bb) Room air conditioners. The cooling capacity will be measured pursuant to the test requirements of 10 CFR part 430 for each unit tested. The results of the measurement(s) will be averaged and compared to the value of cooling capacity certified by the manufacturer for the basic model. The certified cooling capacity will be considered valid only if the measurement is within five percent of the certified cooling capacity.
(1) Verification of input capacity for gas-fired pool heaters. The input capacity of each tested unit will be measured pursuant to the test requirements of § 430.23(p) of this subchapter. The results of the measurement(s) will be compared to the represented value of input capacity certified by the manufacturer for the basic model. The certified input capacity will be considered valid only if the measurement(s) (either the measured input capacity for a single unit sample or the average of the measured input capacity for a multiple unit sample) is within two percent of the certified input capacity.
(2) Verification of active electrical power for electric pool heaters. The active electrical power of each tested unit will be measured pursuant to the test requirements of § 430.23 of this subchapter. The results of the measurement(s) will be compared to the represented value of active electrical power city certified by the manufacturer for the basic model. The certified active electrical power will be considered valid only if the measurement(s) (either the measured active electrical power for a single unit sample or the average of the measured active electrical power for a multiple unit sample) is within five percent of the certified active electrical power.
(ee) Dedicated-purpose pool pump motors.
(ff) Commercial refrigerators, freezers, and refrigerator-freezers—(1) Verification of volume. The volume will be measured pursuant to the test requirements of 10 CFR part 431 for each unit tested. The results of the measurement(s) will be averaged and compared to the value of the certified volume of the basic model. The certified volume will be considered valid only if the average measured volume is within five percent of the certified volume.
(2) Verification of total display area. The total display area will be measured pursuant to the test requirements of 10 CFR part 431 for each unit tested. The results of the measurement(s) will be averaged and compared to the value of the certified total display area of the basic model. The certified total display area will be considered valid only if the average measured total display area is within five percent of the certified total display area.
(3) Determination of pull-down temperature application. A classification of a basic model as pull-down temperature application will be considered valid only if a model meets the definition of “pull-down temperature application” specified in § 431.62 of this chapter as follows.
[79 FR 22348, Apr. 21, 2014, as amended at 79 FR 40566, July 11, 2014; 80 FR 37148, June 30, 2015; 80 FR 45824, July 31, 2015; 80 FR 46760, Aug. 5, 2015; 80 FR 79669, Dec. 23, 2015; 81 FR 2646, Jan. 15, 2016; 81 FR 15426, Mar. 23, 2016; 81 FR 24009, Apr. 25, 2016; 81 FR 37055, June 8, 2016; 81 FR 38395, June 13, 2016; 81 FR 46791, July 18, 2016; 81 FR 79320, Nov. 10, 2016; 81 FR 96236, Dec. 29, 2016; 81 FR 89304, Dec. 9, 2016; 81 FR 89822, Dec. 12, 2016; 81 FR 95800, Dec. 28, 2016; 82 FR 1100, Jan. 4, 2017; 82 FR 36919, Aug. 7, 2017; 85 FR 1446, Jan. 10, 2020; 86 FR 56820, Oct. 12, 2021; 87 FR 33379, June 1, 2022; 87 FR 45197, July 27, 2022; 87 FR 50423, Aug. 16, 2022; 87 FR 55122, Sept. 8, 2022; 87 FR 57298, Sept. 19, 2022; 87 FR 63895, Oct. 20, 2022; 87 FR 65667, 65899, Nov. 1, 2022; 87 FR 75167, Dec. 7, 2022; 87 FR 77324, Dec. 16, 2022; 88 FR 3276, Jan. 18, 2023; 88 FR 15537, Mar. 13, 2023; 88 FR 17975, Mar. 24, 2023; 88 FR 21838, Apr. 11, 2023; 88 FR 28837, May 4, 2023; 88 FR 40472, June 21, 2023; 88 FR 34362, May 26, 2023; 88 FR 34702, May 30, 2023; 88 FR 48357, July 27, 2023; 88 FR 66222, Sept. 26, 2023; 88 FR 67041, Sept. 28, 2023; 88 FR 84228, Dec. 4, 2023; 89 FR 37942, May 6, 2024; 89 FR 44035, May 20, 2024; 89 FR 82070, Oct. 9, 2024; 90 FR 6790, Jan. 21, 2025; 90 FR 1278, Jan. 7, 2025; 90 FR 43371, 43384, Sept. 9, 2025]