(f) An operational single station carbon monoxide detector with a suitable alarm or a combination smoke detector and carbon monoxide detector, which shall be alternating current (AC) powered, either plugged directly in to an electrical outlet that is not controlled by a switch or hardwired into an alternating current (AC) electrical source, with battery backup, shall be installed, maintained, tested, repaired, or replaced, if necessary, in accordance with the manufacturer’s direction:
- (1) In any newly constructed residential unit which has a fuel-burning heating or cooking source including, but not limited to, an oil or gas furnace or stove;
- (2) In any residential unit which is connected to a newly constructed building, including, but not limited to, a garage, storage shed, or barn, which has a fuel-burning heating or cooking source, including, but not limited to, an oil or gas furnace or stove; and
- (3) In either a common area where the general public has access or all rooms in which a person will be sleeping that are adjoining to and directly below and above all areas or rooms that contain permanently installed fuel-burning appliances and equipment that emit carbon monoxide as a byproduct of combustion located within all apartment buildings, boarding houses, dormitories, long-term care facilities, adult or child care facilities, assisted living facilities, one- and two-family dwellings intended to be rented or leased, hotels, and motels.