(1) Attached garage.
- (a) Common walls between a CBRF and an attached garage shall be protected with at least one layer of 5/8-inch type X gypsum board with taped joints on the garage side and with at least one layer of ½-inch gypsum board with taped joints, or equivalent, on the CBRF side. The walls shall provide a complete separation.
- (b) Floor-ceiling assemblies between a garage and the CBRF shall be protected with at least one layer of 5/8-inch type X gypsum board on the garage side of the ceiling or room framing.
- (c) A self-closing 1¾-inch solid core wood door or an equivalent self-closing fire-resistive rated door shall protect openings between an attached garage and the CBRF.
- (d) When a required exit leads into a garage, the garage shall have at least a 32 inch service door to the outside.
- (2) Detached garages. A detached garage shall either be located at least 3 feet from the CBRF or shall comply with the requirements for attached garages under sub. (1).
- (3) Utility buildings. A utility building where fueled, motorized vehicles and appliances such as snowmobiles, power lawn mowers, motorcycles, and snow blowers are stored shall be located at least of 3 feet from the CBRF or comply with the requirements for attached garages under sub. (1).
History
History: CR 07-095: cr. Register January 2009 No. 637, eff. 4-1-09.