Wis. Admin. Code § ATCP 93.440
(2) Inspection of field-erected metallic aboveground storage tanks.
(c)
1. The agency conducting an API 653 inspection shall report all applicable information from the inspection on an API 653 tank inspection summary form supplied by the department.
Note: TR-WM-119-API 653 Tank Inspection Summary is available from the Bureau of Weights and Measures, P. O. Box 8911, Madison, WI 53708-8911, or at telephone (608) 224-4942, or from the Bureau’s Web site at https://datcp.wi.gov/Pages/Programs_Services/PetroleumHazStorageTanksForms.aspx.
(e) For tanks undergoing a transition from storing an unregulated substance to storing a regulated substance, any inspection in Table 93.440 that has not occurred shall be performed before putting the regulated substance into the tank. For the purposes of this paragraph, the service date is the date the tank was initially placed into service after construction.
Table 93.440
Inspection Type and Schedule
(3) Inspection of shop-built metallic aboveground storage tanks.
(a)
2.
c. This paragraph does not apply to heating oil tanks or to tanks at farms and construction projects.
Note: STI SP001 requires monthly and annual inspections and requires maintaining records of these inspections. For almost all ASTs that have a capacity of 5,000 gallons or less, these inspections are only required to be visual. For most tanks that have a capacity of more than 5,000 gallons, the requirements include, but are not limited to, having a certified inspection every 20 years, consisting of a visual exam and spot, ultrasonic examination, with no requirement for an integrity pressure test. STI SP001 includes optional checklists that may be used for the required record keeping. These checklists and a compendium that contains further guidance for these inspections are available from the Bureau of Weights and Measures, P. O. Box 8911, Madison, WI 53708-8911, or at telephone (608) 224-4942, or from the Bureau’s Web site at https://datcp.wi.gov/Pages/Programs_Services/PetroleumHazStorageTanksForms.aspx.
Note: Tanks that are not required by this paragraph to have periodic inspections may otherwise be required to have periodic inspections, by the federal Spill Prevention Control and Countermeasure regulations in 40 CFR 112.
Note: Heating oil tanks and tanks at farms and construction projects are subject to the requirements in NFPA 31 or 30A under ss. ATCP 93.310 and 93.630, respectively.
(b)
(c) If product is found within a tank’s interstitial space during an inspection under this subsection, delivery of product into the tank shall be immediately suspended, and either of the following actions shall be taken within 10 business days:
2. The tank shall be closed in accordance with s. ATCP 93.460.
Note: See sub. (5) for further requirements for corrective action.
(4) Inspection of nonmetallic aboveground storage tanks.
(a) The owner or operator of all nonmetallic aboveground storage tanks — including concrete, tile−lined, fiber−reinforced plastic, and homogeneous plastic tanks — that have a capacity of 5,000 gallons or more shall have the tanks inspected in accordance with all of the following:
1. ‘Monthly inspection.’
2. ‘Annual inspection.’
(5) Corrective action.
(b) All corrective actions, including repairs that are indicated by the inspections under this section, shall be completed before the tank system is returned to service.
Note: Under s. ATCP 93.400 (11) (a) 1., (b) 1., and (c) 9., records of the inspections that are required under this section must be maintained at the storage-tank site for at least either three years or the interval between inspections, whichever is longer.
History: CR 17-092: cr. Register October 2019 No. 766, eff. 11-1-19; CR 24-034: r. (3) (a) 2. b., am. (4) (a) (intro.) Register October 2025 No. 838, eff. 11-1-25.