The vertical clearance for overhead power and communication lines above the highway and the lateral and vertical clearance from bridges shall conform with the National Electrical Safety Code and/or with the clearances as shown below, whichever is greater.
| type of utility line | lines crossingroadways | longi-tudinal |
| Communications and Cable Television | 24' | 20' |
| Communications and/or Cable Television joint usage with electrical | 20' | 20' |
| electrical | ||
| 0 - 750 volts | 24' | 24' |
| 751 - 15,000 volts | 30' | 27' |
| 15,001 - 50,000 volts | 32' | 32' |
| 50,001 volts and over | 34' | 32' |