- (1) The stabilization, assessment, and intervention facility (SAIF) must be located in an area with public fire protection.
(2) SAIF must have a working smoke detector and carbon monoxide detector installed:
- (a) In every client's bedroom; and
- (b) On every floor of the facility.
(3) Each smoke detector and carbon monoxide detector must:
- (a) Be in working condition; and
- (b) Address the needs of clients who are deaf or hard of hearing.
- (4) SAIF must have fire extinguishers located throughout the facility as prescribed by the local fire marshal.
- (5) SAIF must have the type and number of fire extinguishers as prescribed by the local fire marshal.
(6) Each fire extinguisher must be:
- (a) Installed according to manufacturer recommendations;
- (b) Annually replaced or inspected and serviced;
- (c) In working condition; and
- (d) Readily available for use.
[Statutory Authority: RCW 71A.12.030 and 2019 c 415 § 203(j). WSR 22-11-056, § 388-847-0190, filed 5/16/22, effective 6/16/22.]