The inspection of the electrical system includes the service drop through the main panel; subpanels including feeders; branch circuits, connected devices, and lighting fixtures.
(1) The inspector will:
- (a) Describe in the report the type of primary service, whether overhead or underground, voltage, amperage, over-current protection devices (fuses or breakers) and the type of branch wiring used.
(b) Report
- (i) The existence of a connected service-grounding conductor and service-grounding electrode when same can be determined.
- (ii) When no connection to a service grounding electrode can be confirmed.
- (c) Inspect the main and branch circuit conductors for proper over-current protection and condition by visual observation after removal of the readily accessible main and subelectric panel cover(s).
- (d) Report, if present, solid conductor aluminum branch circuits. Include a statement in the report that solid conductor aluminum wiring may be hazardous and a licensed electrician should inspect the system to ensure it's safe.
(e) Verify
- (i) The operation of a representative number of accessible switches, receptacles and light fixtures.
- (ii) The grounding and polarity of a representative number of receptacles; particularly in close proximity to plumbing fixtures or at the exterior.
- (iii) Ground fault circuit interrupter (GFCI) protection and arc-fault circuit interrupter (AFCI) protection where required.
- (f) Report the location of any inoperative or missing GFCI and/or AFCI devices when they are recommended by industry standards.
- (g) Advise clients that homes without ground fault protection should have GFCI devices installed where recommended by industry standards.
- (h) Report on any circuit breaker panel or subpanel known within the home inspection profession to have safety concerns.
- (i) Describe any deficiencies of these systems or components.
(2) The inspector is not required to:
- (a) Insert any tool, probe or testing device into the main or subpanels.
- (b) Activate electrical systems or branch circuits that are not energized.
- (c) Operate circuit breakers, service disconnects or remove fuses.
(d) Inspect ancillary systems, including but not limited to:
- (i) Timers.
- (ii) Security systems.
- (iii) Low voltage relays.
- (iv) Smoke/heat detectors.
- (v) Antennas.
- (vi) Intercoms.
- (vii) Electrical deicing tapes.
- (viii) Lawn sprinkler wiring.
- (ix) Swimming pool or spa wiring.
- (x) Central vacuum systems.
- (xi) Electrical equipment that's not readily accessible.
- (e) Dismantle any electrical device or control, except for the removal of the deadfront covers from the main service panel and subpanels.
- (f) Move any objects, furniture, or appliances to gain access to any electrical component.
- (g) Test every switch, receptacle, and fixture.
- (h) Remove switch and receptacle cover plates.
- (i) Verify the continuity of connected service ground(s).
[Statutory Authority: RCW 18.280.050 and 18.280.060(6). WSR 09-08-014, § 308-408C-110, filed 3/20/09, effective 4/20/09.]