Wash. Admin. Code § 296-96-02605
(1) Private residence, battery operated, inclined stairway chairlifts are not required to be supplied by an individual branch circuit in order to comply with NFPA 70 620.51 (A) Exception 2. The cord and plug is permitted by the disconnecting means from the outlet to the unit's batteries. A second disconnect shall be provided on the unit and shall comply with the following:
(b) The disconnecting means shall open all ungrounded main power supply conductors for the motor.
The circuit, which is used for the equipment, shall have overcurrent protection that will protect the circuit and the equipment. The circuit shall have sufficient capacity to support the additional load of the stairway chairlift. Units that are operated by line voltage shall comply with NFPA 70, 620.51 (A) Exception 2.
(2) Commercial, battery operated, inclined stairway chairlifts installed in compliance with NFPA 70, 620.51(A), Exception No. 2 shall also comply with the following:
[Statutory Authority: RCW 70.87.030. WSR 23-17-141, § 296-96-02605, filed 8/22/23, effective 10/2/23. Statutory Authority: Chapter 70.87 RCW. WSR 21-18-096, § 296-96-02605, filed 8/31/21, effective 10/1/21; WSR 18-18-070, § 296-96-02605, filed 8/31/18, effective 10/1/18; WSR 13-24-066, § 296-96-02605, filed 11/27/13, effective 1/1/14; WSR 07-24-041, § 296-96-02605, filed 11/30/07, effective 1/1/08.]