Wash. Admin. Code § 296-878-18020
You must make sure you travel on the outside of the building only when:
(2) The anchors are not more than forty-eight inches apart.
| Note: | Anchors can be up to seventy-two inches apart if: |
| 1. The sill or ledge is continuous; | |
| 2. The sill or ledge is at least twelve inches wide; | |
| 3. The sill or ledge has a slope less than five degrees; | |
| 4. There is at least six inches of window sill in front of the mullions. |
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060, and chapter 49.17 RCW. WSR 14-09-095, § 296-878-18020, filed 4/22/14, effective 7/1/14. Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 02-22-027, § 296-878-18020, filed 10/28/02, effective 1/1/03.]