Wash. Admin. Code § 296-835-13005
(1) You must provide an automatic fire extinguishing system or an automatic dip tank cover for any hardening and tempering tank that uses flammable liquids or liquids with flashpoints greater than 199.4°F (93°C) and:
(2) Prevent fires.
(a) You must make sure hardening and tempering tanks are:
(3) You must make sure air under pressure is not used to:
(6) You must have a circulating cooling system if the temperature of the liquid can exceed the alarm set point.
| Note: | The bottom drain of the tank may be combined with the oil circulating system if the requirements for bottom drains in WAC 296-835-12015 are satisfied. |
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 17-18-075, § 296-835-13005, filed 9/5/17, effective 10/6/17. Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060 and 29 C.F.R. 1910 Subpart Z. WSR 14-07-086, § 296-835-13005, filed 3/18/14, effective 5/1/14. Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. WSR 02-15-102, § 296-835-13005, filed 7/17/02, effective 10/1/02.]