Wash. Admin. Code § 296-835-12025
(1) You must provide at least one automatic fire extinguishing system or an automatic dip tank cover if the tank:
(2) You must make sure automatic fire extinguishing systems or automatic dip tank covers meet the requirements of Table 1.
Exemption: An automatic fire extinguishing system or an automatic dip tank cover is not required for a hardening or tempering tank that:
1. Holds less than five hundred gallons; or
2. Has less than twenty-five square feet of liquid surface area.
Table 1: Automatic Fire Protection System Requirements
| IF YOU PROVIDE: | THEN YOU MUST: |
| An automatic fire extinguishing system | • Use extinguishing materials suitable for a fire fueled by the liquid in the tank• Make sure the system protects the:– Tanks– Drain boards– Stock over drain boards. |
| A dip tank cover | • Make sure the cover is:– Closed by approved automatic devices in the event of fire– Able to be manually activated– Kept closed when the tank is not being used- Made of noncombustible material or tin-clad material with locked metal joints. |
Reference: Automatic fire extinguishing systems have specific requirements. See:
1. WAC 296-24-622 for automatic dry chemical extinguishing system requirements.
2. WAC 296-24-623 for automatic carbon dioxide extinguishing system requirements.
3. WAC 296-24-627 for automatic water spray extinguishing system and automatic foam extinguishing system requirements.
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 17-18-075, § 296-835-12025, filed 9/5/17, effective 10/6/17; WSR 07-03-163, § 296-835-12025, filed 1/24/07, effective 4/1/07. Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. WSR 02-15-102, § 296-835-12025, filed 7/17/02, effective 10/1/02.]