Wash. Admin. Code § 296-826-50020
Important:
In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
(1) You must make sure each container has all of the following:
(c) Either of the following:
(2) You must provide one or more spring-loaded safety relief valves, or an equivalent type, on all containers, that do all of the following:
(a) Discharges in the following ways:
(3) You must make sure shut off valves are not installed between the safety relief valve and the container or system. A shut off valve may be used if arranged so that the required capacity flow is maintained.
| EXEMPTION: | You are exempt from the requirement not to install the shut off valve between the safety relief valve and the container or systems in the following situations: |
| 1. A three-way valve installed under two safety relief valves, each with: | |
| a. The required rate of discharge; and | |
| b. Installed to allow either of the safety relief valves to be closed off but not at the same time. | |
| 2. Two separate relief valves are installed with individual shut off valves. | |
| 3. The two shut off valve stems must be mechanically interconnected to allow the full required flow of one safety relief valve at all times. | |
| 4. When a safety relief valve manifold that allows: | |
| a. One valve of two or more to be closed off; and | |
| b. The remaining valve or valves will provide not less than the rate of discharge shown on the manifold nameplate. |
(4) You must follow additional requirements found in Table 11, Appurtenances for Systems Mounted on Trucks, Semi-Trailers and Trailers.
Table 11
Appurtenances for Systems Mounted on Trucks, Semi-Trailers and Trailers
| If you have: | Then make sure they: | |
| All container connections | Are provided with either of the following: | |
| 1. | Automatic excess flow valves; or | |
| 2. | Quick-closing internal valves that remain closed except during delivery operations. | |
| Note: If the control mechanism is provided with a secondary control remote from the delivery connection, then a fusible section (melting point 208°F to 220°F) is required to permit the internal valve to close automatically in case of fire. | ||
| Exemption: Filling connections, safety relief devices, and liquid level and pressure gauge connections are exempt from automatic excess flow valves and quick-closing internal valves. | ||
| Filling connections | Prevent back-flow in the event the filling connection breaks with at least one of the following: | |
| 1. | Automatic back pressure check valves; | |
| 2. | Excess flow check valves; | |
| 3. | Quick closing internal valves. | |
| Exemption: An automatic valve is not required if: | ||
| 1. | The filling and discharge connect to a common opening in the container shell; and | |
| 2. | The opening is fitted with a quick-closing internal valve. | |
| Nonrecessed container fittings and appurtenances | Are protected against physical damage by one of the following methods: | |
| 1. | A protected location; | |
| 2. | The vehicle frame or bumper. | |
| A protective housing that meets the following: | ||
| 1. | Is fabricated from material that is compatible with the containers design and construction requirements; | |
| 2. | Designed to withstand static loadings in any direction equal to twice the weight of the container and attachments when filled using a safety factor of not less than 4, based on the ultimate strength of the material used. | |
| Note: Protect nonrecessed container fittings and appurtenances with a weather cover as needed for proper operation of valves and safety relief devices. | ||
| Columnar-type gauges | 1. | Are restricted to stationary storage installations. |
| 2. | Are shielded against the direct rays of the sun. | |
| 3. | Are equipped with all of the following: | |
| a. | Shut off valves having metallic hand-wheels; | |
| b. | Excess flow valves; | |
| c. | Extra heavy glass that is adequately protected with a metal housing applied by the gauge manufacturer. | |
| Hydrostatic relief valves | Are installed between each pair of valves in the liquid ammonia piping or hose. |
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050. WSR 15-23-086, § 296-826-50020, filed 11/17/15, effective 12/18/15. Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. WSR 06-10-067, § 296-826-50020, filed 5/2/06, effective 9/1/06.]