Wash. Admin. Code § 296-826-50015
Important:
In addition to this section, you need to follow the Appurtenances requirements for all systems, WAC 296-826-50005.
(1) You must protect container appurtenances against the following:
(2) You must make sure safety relief devices have a total relieving capacity larger than either of the following:
(b) The amount based on using either one of the following fire exposure formulas (see note below for codes):
(i) Valve manufacturers who use weight of vapors to be relieved as the classifying basis, use this formula:
| W = | 34,500 F A (0.82) | |
| L |
(ii) Valve manufacturers that classify valves based on air flows, use this formula:
| Q(a) = | 633,000 F AO.32 | |
| LC |
(3) You must make sure safety relief devices meet the following additional requirements:
(4) You must provide shut off valves for all connections including plugs, safety valves, and thermometer wells.
Locate them as close to the tank as is practical.
| EXEMPTION: | Shut off valves do not need to be provided on connections with a No. 54 drill size restriction. |
| Note: | Install, when operating conditions make it advisable, both of the following: |
| 1. A check valve on the fill connection; | |
| 2. A remotely operated shut off valve on other connections located below the maximum liquid level. |
(5) You must follow requirements found in Table 10, Refrigerated Tank Appurtenances.
Table 10
Refrigerated Tank Appurtenances
| If you have: | Then make sure they: | |
| Shut off valves used as a means of lock out for inspection or repair | 1. | Are of adequate flow capacity. |
| 2. | Are arranged to be locked or sealed open and not closed except by an authorized person who does both of the following: | |
| a. | Remains there while the valve is closed; | |
| b. | Locks or seals the valve open when leaving the station. | |
| Discharge line and header | 1. | Are designed to accommodate the maximum flow. |
| 2. | Have a back pressure not greater than 10% of the design pressure of the storage container. | |
| 3. | Include the back pressure in the 120% of the maximum pressure of the design pressure. | |
| 4. | Do not have other containers or systems that exhaust into the discharge line or header. | |
| 5. | Have vent lines installed to prevent the accumulation of liquid in the lines. | |
| Note: Multiple safety relief valves on the same storage unit may be run through a common discharge header. | ||
| Vacuum breakers | Are provided with atmospheric storage. | |
| Stacks | Do both of the following: | |
| 1. | Prevent any obstructions by rain, snow, ice, or condensation; and | |
| 2. | Have an outlet size not smaller than the size of the safety relief valve outlet connection. |
(6) You must make sure appurtenances meet all of the requirements found in the following:
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050. WSR 15-23-086, § 296-826-50015, filed 11/17/15, effective 12/18/15. Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. WSR 06-10-067, § 296-826-50015, filed 5/2/06, effective 9/1/06.]