Wash. Admin. Code § 296-826-30055
| You must meet the requirements … | in this section: |
| Installation | WAC 296-826-30055 |
| Reinstallation | WAC 296-826-30060 |
(4) You must prevent accidental discharge of liquids from spreading into uncontrolled areas by providing, to the area surrounding a refrigerated tank or group of tanks, one of the following:
(5) You must meet, when using a diked enclosure or an impounding basin in a drainage system, the following requirements:
(a) Make the wall of earth, steel, or concrete. If made of earth, meet both of the following:
(b) Design the wall to be both:
(6) You must provide for drainage of rain water, that does not permit the release of ammonia, from diked or impounding areas.
| Note: | 1. It is recommended that the ground in an impounding basin or within a diked enclosure be graded so that small spills or the early part of a large spill will accumulate at one side or corner contacting both: |
| a. A relatively small area of ground; and | |
| b. Exposing a relatively small surface area for heat gain. | |
| 2. Shallow channels in the ground surface or low curbs of earth can help guide the liquid to these low areas without contacting a large ground area. |
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050. WSR 15-23-086, § 296-826-30055, filed 11/17/15, effective 12/18/15. Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. WSR 06-10-067, § 296-826-30055, filed 5/2/06, effective 9/1/06.]