(1) You must construct and test containers, when transported within the state of Washington, according to both of the following:
- (a) A minimum design pressure of 250 psig;
- (b) The Unfired Pressure Vessel Code.
- (2) You must construct containers used for interstate transport according to DOT regulations.
- (3) You must make sure the shell or head thickness of any container is at least 3/16 of an inch.
(4) You must make sure electrical lighting circuits meet all of the following:
- (a) Have suitable over-current protection, such as fuses or automatic circuit breakers.
- (b) Are suitably secured, insulated, and protected against physical damage.
- (c) Have wiring with sufficient carrying capacity and mechanical strength.
- (5) You must use only electric light.
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050. WSR 15-23-086, § 296-826-30025, filed 11/17/15, effective 12/18/15. Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. WSR 06-10-067, § 296-826-30025, filed 5/2/06, effective 9/1/06.]