Wash. Admin. Code § 296-800-30020
(1) You must perform inspections:
Make sure that portable fire extinguishers or hose systems (used instead of fire extinguishers) are visually inspected monthly.
(2) You must perform maintenance checks:
(b) Keep records of all annual maintenance checks and make available to the department upon request.
(c) Make sure that equal protection is provided when portable fire extinguishers are removed from service for maintenance and recharging
Exemption: Most stored pressure extinguishers do not require an internal examination. Examples of those that do require an internal examination are those containing a loaded stream agent.
(3) You must perform hydrostatic testing:
Exemption:
• Dry chemical extinguishers that have nonrefillable disposable containers are exempt from this requirement.
• Manually pressurized pumptanks are exempt from this requirement.
(4) You must make sure that portable extinguishers are hydrostatically tested:
(5) You must not perform hydrostatic testing on fire extinguishers if:
(e) Calcium chloride extinguishing agents have been used in a stainless steel shell.
| Note: | Specific rules regarding conducting hydrostatic tests are covered in WAC 296-24-59212. |
(6) You must maintain records showing that hydrostatic testing has been performed. Provide the following evidence to the department upon request:
(7) You must keep records until:
(8) You must empty and maintain stored-pressure dry chemical extinguishers requiring a 12-year hydrostatic test, every six years:
When recharging or hydrostatic testing is performed, the 6-year requirement begins from that date
Hydrostatic Test Table
| Type of Extinguisher | Test Interval (Years) |
| Stored pressure water and/or antifreeze | 5 |
| Wetting agent | 5 |
| Foam (stainless steel shell) | 5 |
| Aqueous film forming form (AFFF) | 5 |
| Loaded stream | 5 |
| Dry chemical with stainless steel | 5 |
| Carbon dioxide | 5 |
| Dry chemical, stored pressure, with mild steel, brazed brass or aluminum shells | 12 |
| Halon 1211 | 12 |
| Halon 1301 | 12 |
| Dry powder, cartridge or cylinder operated, with mild steel shell | 12 |
| Note: Due to a manufacturer's recall, stored pressure water extinguishers with fiberglass shell (pre-1976) are prohibited from hydrostatic testing. |
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 18-22-116, § 296-800-30020, filed 11/6/18, effective 12/7/18. Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. WSR 01-23-060, § 296-800-30020, filed 11/20/01, effective 12/1/01; WSR 01-11-038, § 296-800-30020, filed 5/9/01, effective 9/1/01.]