Wash. Admin. Code § 296-800-28027
This section applies to equipment that operates at 600 volts or less.
(2) You must make sure equipment likely to require examination, adjustment, servicing, or maintenance while energized has:
(d) Clear working space about service equipment, switchboards, panelboards, or motor control centers that extends from the grade, floor, or platform to a height of:
(ii) 6.5 Feet for installations built on or after August 13, 2007. If the height of the equipment is greater than 6.5 feet, the minimum headroom may not be less than the height of the equipment.
| Note: | • Other equipment associated with the electrical installation and located above or below the electric equipment may extend not more than 6 inches beyond the front of the electric equipment. |
(3) You must make sure working space is:
(5) You must provide adequate lighting (WAC 296-800-210) for all working spaces about service equipment, switchboards, panelboards, and motor control centers installed indoors. In electric equipment rooms, the illumination must not be controlled by automatic means only.
This table shows the area you must keep clear depending on the layout of the electrical equipment.
Table XX
| Conditions2 | Minimum Clear Distance3 | Minimum Clear Distance3 | |||
| 0 - 150volts to ground | 151 - 600volts to ground | ||||
| A1 | 3 ft. | 3 ft. | |||
| B | 3 ft.1 | 3 1/2 ft. | |||
| C | 3 ft. | 4 ft. |
| 1. | Minimum clear distances may be 0.7 m (2.5 ft) for installations built before April 16, 1981. |
| 2. | Conditions A, B, and C are as follows: |
| A = Exposed live parts on one side and no live or grounded parts on the other side of the working space, or exposed live parts on both sides effectively guarded by suitable wood or other insulating material. Insulated wire or insulated bus bars operating at not over 300 volts aren't considered live parts. | |
| B = Exposed live parts on one side and grounded parts on the other side. | |
| C = Exposed live parts on both sides of the workspace (not guarded as provided in condition A with the operator between the panels). | |
| 3. | Working space is not required in back of assemblies such as dead-front switchboards or motor control centers where there are no renewable or adjustable parts (such as fuses or switches) on the back and where all connections are accessible from locations other than the back. Where rear access is required to work on deenergized parts on the back of enclosed equipment, a minimum working space of 30 in. horizontally must be provided. |
| [if IE 9]><video style="display: none;"><![endif][if IE 9]></video><![endif] |
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 18-22-116, § 296-800-28027, filed 11/6/18, effective 12/7/18. Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060, and chapter 49.17 RCW. WSR 12-16-064, § 296-800-28027, filed 7/31/12, effective 9/1/12.]