Wash. Admin. Code § 296-52-69120
Explosives manufacturing plants that have buildings and magazines, where workers are regularly employed, must meet the quantity and separation distance requirements of Table H-23, intraexplosives plant quantity and distance table.
(2) Magazines. Magazines must be located away from manufacturing and nonmanufacturing buildings as required by Table H-23.
Table H-23
| explosives | Distance Feet | ||||
| PoundsOver | PoundsNot Over | Separate Building or Within Substantial Dividing Walls | |||
| . . . . | 10 | ||||
| 10 | 25 | 40 | |||
| 25 | 50 | 60 | |||
| 50 | 100 | 80 | |||
| 100 | 200 | 100 | |||
| 200 | 300 | 120 | |||
| 300 | 400 | 130 | |||
| 400 | 500 | 140 | |||
| 500 | 750 | 160 | |||
| 750 | 1,000 | 180 | |||
| 1,000 | 1,500 | 210 | |||
| 1,500 | 2,000 | 230 | |||
| 2,000 | 3,000 | 260 | |||
| 3,000 | 4,000 | 280 | |||
| 4,000 | 5,000 | 300 | |||
| 5,000 | 6,000 | 320 | |||
| 6,000 | 7,000 | 340 | |||
| 7,000 | 8,000 | 360 | |||
| 8,000 | 9,000 | 380 | |||
| 9,000 | 10,000 | 400 | |||
| 10,000 | 12,500 | 420 | |||
| 12,500 | 15,000 | 450 | |||
| 15,000 | 17,500 | 470 | |||
| 17,500 | 20,000 | 490 | |||
| 20,000 | 25,000 | 530 | |||
| 25,000 | 30,000 | 560 | |||
| 30,000 | 35,000 | 590 | |||
| 35,000 | 40,000 | 620 | |||
| 40,000 | 45,000 | 640 | |||
| 45,000 | 50,000 | 660 | |||
| 50,000 | 55,000 | 680 | |||
| 55,000 | 60,000 | 700 | |||
| 60,000 | 65,000 | 720 | |||
| 65,000 | 70,000 | 740 | |||
| 70,000 | 75,000 | 770 | |||
| 75,000 | 80,000 | 780 | |||
| 80,000 | 85,000 | 790 | |||
| 85,000 | 90,000 | 800 | |||
| 90,000 | 95,000 | 820 | |||
| 95,000 | 100,000 | 830 | |||
| 100,000 | 125,000 | 900 | |||
| 125,000 | 150,000 | 950 | |||
| 150,000 | 175,000 | 1,000 | |||
| 175,000 | 200,000 | 1,050 | |||
| 200,000 | 225,000 | 1,100 | |||
| 225,000 | 250,000 | 1,150 | |||
| 250,000 | 275,000 | 1,200 | |||
| 275,000 | 300,000 | 1,250 |
[Statutory Authority: RCW 49.17.010, [49.17].040, and [49.17].050. WSR 02-03-125, § 296-52-69120, filed 1/23/02, effective 3/1/02.]