Wash. Admin. Code § 296-304-02005
(1) Locations covered by this section. You must ensure that manual cleaning and other cold work are not performed in the following spaces unless the conditions of subsection (2) of this section have been met:
(2) Requirements for performing cleaning or cold work.
(c) Continuous ventilation must be provided at volumes and flow rates sufficient to ensure that the concentration(s) of:
(i) Flammable vapor is maintained below 10 percent of the lower explosive limit; and
| Note to (2)(c)(i): | Spaces containing highly volatile residues may require additional ventilation to keep the concentration of flammable vapors below 10 percent of the lower explosive limit and within the permissible exposure limit. |
(d) Testing must be conducted by the competent person as often as necessary during cleaning or cold work to assure that air concentrations are below 10 percent of the lower explosive limit and within the PELs and below IDLH levels. Factors such as, but not limited to, temperature, volatility of the residues and other existing conditions in and about the spaces are to be considered in determining the frequency of testing necessary to assure a safe atmosphere.
| Note to (2)(d): | See WAC 296-304-02013—Appendix B, for additional information on frequency of testing. |
(f) An employee may not enter a confined or enclosed space or other dangerous atmosphere if the concentration of flammable or combustible vapors in work spaces exceeds 10 percent of the lower explosive limit.
(iv) Respiratory protection, personal protective equipment, and clothing are provided in accordance with WAC 296-304-090 through 296-304-09007.
| Note to (2)(f): | Other provisions for work in IDLH and other dangerous atmospheres are located in WAC 296-304-090 through 296-304-09007. |
Exception: An employee may enter for emergency rescue or for a short duration for installation of ventilation equipment provided:
(i) Only explosion-proof, self-contained portable lamps, or other electric equipment approved by a National Recognized Testing Laboratory (NRTL) for the hazardous location must be used in spaces described in subsection (1) of this section, until such spaces have been certified as "safe for workers."
| Note to (2)(i): | Battery-fed, portable lamps or other electric equipment bearing the approval of a NRTL for the class, and division of the location in which they are used are deemed to meet the requirements of (i) of this subsection. |
(j) You must prominently post signs that prohibit sources of ignition within or near a space that has contained flammable or combustible liquids or gases in bulk quantities:
(l) Fans must have nonsparking blades, and portable air ducts shall be of nonsparking materials.
| Note to (2): | See WAC 296-304-02003(3) and applicable requirements of chapter 296-62 WAC, general occupational health standards, for other provisions affecting cleaning and cold work. |
[Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, and 49.17.060. WSR 18-04-096, § 296-304-02005, filed 2/6/18, effective 3/9/18; WSR 17-18-075, § 296-304-02005, filed 9/5/17, effective 10/6/17; WSR 07-17-034, § 296-304-02005, filed 8/7/07, effective 12/1/07. Statutory Authority: Chapter 49.17 RCW. WSR 95-04-006, § 296-304-02005, filed 1/18/95, effective 3/10/95; Order 74-25, § 296-304-02005, filed 5/7/74.]