Wash. Admin. Code § 246-272B-06250
(1) Treatment to produce effluent of a higher quality than STE is required when:
(5) To determine the minimum treatment level for a proposed LOSS, the design engineer shall:
(c) Increase the treatment level, if the drainfield is near areas where pathogens or other effluent parameters are a public health or environmental concern including, but not limited to:
(7) For LOSS with design flow of 14,500 gpd or less, the design engineer shall not use disinfection treatment to meet the fecal coliform standard in:
(8) For LOSS with design flow above 14,500 gpd, the department may allow disinfection treatment to meet the fecal coliform standard if all of the following conditions are met:
(9) The department may:
(d) Deny approval for LOSS designs that propose using specific technologies or treatment processes that have monitoring and sampling histories indicating inadequate or unreliable performance.
Table 5: Treatment Levels
| Effluent Parameters * | ||||||||||||
| Treatment Level | CBOD5(mg/L) | TSS(mg/L) | O&G(mg/L) | FC(#/100 ml) | TN(mg/L) | P(mg/L) | ||||||
| HQE | ** | ** | ** | ** | ** | ** | ||||||
| B | 15 | 15 | 1,000 | |||||||||
| C | 25 | 30 | 50,000 | |||||||||
| E | 125 | 80 | 20 | |||||||||
| N10 | 10 | |||||||||||
| N20 | 20 | |||||||||||
| P | ** |
| * | The values represent effluent maximum annual averages. |
| ** | Site specific; see WAC 246-272B-06250(7). |
Table 6: Requirement Minimum Treatment Levels for Various Conditions
| Conditions | Minimum Required Treatment Level |
| Project Specific1 | HQE2 |
| Vertical Separation of 2 to < 3 feet, design flow higher than 14,500 gpd | HQE |
| Soil Type 1 | B |
| Vertical Separation of 2 to < 3 feet, design flow 14,500 gpd or less | C |
| Sewage that is not residential strength | E |
| All sites not requiring B, C, E or HQE | STE |
| Sites where nitrogen or phosphorus is identified as a contaminant of concern | N10, N20, or P3 |
| Table 6 notes: | |
| 1. | As identified during the site review process. |
| 2. | HQE: High quality effluent; project specific standards are set case-by-case. Treatment Level HQE is required where Treatment Level B is inadequate, or may be chosen by the LOSS owner. |
| 3. | As required by the department, based on the environmental review. Nitrogen treatment higher than N10 may be required for some sites. Phosphorus or other treatment value will be project specific, determined in the environmental review or by local or state regulation. |
[Statutory Authority: RCW 70.118B.020. WSR 11-12-035, § 246-272B-06250, filed 5/25/11, effective 7/1/11.]