Wash. Admin. Code § 246-272B-06150
(1) The design engineer shall use the following minimum design flows, which include the appropriate peaking factors, for developments or portions of developments serving residential facilities such as single-family residences, multi-family dwellings, and mobile home parks with total LOSS design flows of 14,500 gpd or less:
(a) Modifications of existing developments:
(b) New residential developments and new mobile home parks:
(3) For commercial and nonresidential developments or portions of developments that serve commercial and nonresidential facilities, the department may accept the following:
(b) Design flows from other generally recognized sources, on a case-by-case basis.
Table 4: Typical Design Flows for Nonresidential Facilities
| Type of Facility | Design Unit1 | Design Flow (gpd) | |
| Schools with showers and cafeteria2 | per student | 16 | |
| Schools without showers and with cafeteria2 | per person | 12.6 | |
| Schools without showers and without cafeteria | per person | 10 | |
| Boarding schools2 | per person | 75 | |
| Temporary farm worker housing2 | per person | 50 | |
| Hotels, motels, and B&Bs | per room | 130 | |
| Restaurants2 | per seat | 50 | |
| Truck stops and Interstate restaurants2 | per seat | 180 | |
| Offices, with showers | per person, per 8-hr shift | 25 | |
| Offices, without showers | per person, per 8-hr shift | 15 | |
| Nursing homes2 | per bed | 200 | |
| Elder care facilities, retirement homes2 | per bed | 100 | |
| Laundromats2 | per machine | 500 | |
| Churches, without kitchen | per seat | 3 | |
| Churches, with kitchen2 | per seat | 5 | |
| Day care centers | per person | 20 | |
| Picnic areas | per person | 5 | |
| Campgrounds, RV parks with flush toilets only, no laundry or wet sewer hookup | per camp site | 50 | |
| Campgrounds, RV parks with flush toilets, showers, laundry, no wet sewer hookup | per camp site | 75 | |
| Campgrounds, RV parks with flush toilets, showers, and wet sewer hookup, with or without laundry2 | per RV space | 120 | |
| Trailer dump stations2 | per dump | 40 | |
| Resort cabin | per person | 40 | |
| Bar, cocktail lounge2 | per seat | 20 |
| 1. | Does not include employees and staff, unless indicated. |
| 2. | Indicates potential for waste strength to exceed that of residential strength sewage, requiring Treatment Level E or higher. |
(4) For the department to evaluate alternate design flows, a written request and the following information must be submitted:
(b) Comparable flow data from similar existing facilities, including:
[Statutory Authority: RCW 70.118B.020. WSR 11-12-035, § 246-272B-06150, filed 5/25/11, effective 7/1/11.]